ABB Industries L.L.C


Test Report ELSE Service

ACB Service & Test Report


Serial. No: Page- 1 of 3

10.10.1. General Details:


Project: ACB SERVICE & TEST Test Date: 18/11/2024
Client: Order No:
Customer: EMIRATES GLOBAL ALUMINIUM Panel Name: PCM-2152MTS-21A
Consultant: - Location: ABB FACTORY

10.10.2. ACB Nameplate Details:


ACB Make: SACE ABB ACB Type: WITHDRAW
ACB Model: E2S 20 No of Poles: 4
Protective Release Model: PR122/P ACB Rated Current: 800A
ACB Serial No: AM21039759 ACB Protections: NA
Protective Release Serial No: E0179Q01D Neutral Pole Rating: 100%
Operation Counter NA

10.10.3. Accessories Check List:


Yes /
Sl. No Accessories Coil Voltage Sl. No Accessories Yes / No
No
Spring Charged
3.1 NO 3.8 Measuring Module:PR120/V: NO
Motor:
3.2 Closing Coil: NO 3.9 Com Module:PR122/D-M: NO
3.3 Opening Coil: NO 3.10 Signaling Module: PR122/K: NO
[Link] Module:PR122/D-
3.4 Under Voltage Coil: NO 3.11 NO
BT:
3.5 Open/Close PB Padlock / Cover: NO 3.12 Trip Reset : YES
3.6 Mechanical operation counter: NO 3.13 Mechanical interlock: NO
3.7 Key lock in open position: NO 3.14 Rack IN/OUT Padlock Key: NO

10.10.4. General Service Check List:


Sl. No General Result Remarks
4.1 Lubrication of moving parts OK
4.2 Lubrication of electrical parts OK
4.3 Contacts surface cleaning OK
4.4 Arc chutes cleaning OK

10.10.5. Operating Coils Resistance Verification:


Sl. No General Pin No. Resistance Value Remarks
5.1 Spring Charged Motor: U1-U2 NA
5.2 Closing Coil: C1-C2 NA
5.3 Opening Coil: C11-C12 NA
5.4 Under Voltage Coil: D1-D2 NA

Form No-ATLVS-S-2014-003, Rev-00, ABB Industries L.L.C, P B No-11070, Dubai, U A E, Tel -+971 4 3147500, +971 4 3401777, Fax - + 971 4 3401532

ABB Industries L.L.C


Test Report ELSE Service

ACB Service & Test Report


Serial. No: Page- 2 of 3

10.10.6. Functional Verifications:


Sl. No General Result Remarks
6.1 Spring charging by handle: OK
6.2 Close / Open operations: OK
6.3 Spring charging by motor: NA
6.4 Closing coil operations: NA
6.5 Opening coil operations: NA
6.6 Under voltage coil operation: NA
6.7 Trip contacts operation: NA
6.8 Auxiliary contacts operation: OK
6.9 Protective release verification: OK

10.10.7. ACB Indications Verification:


Sl. No General Result Remarks
8.1 ACB ON / OFF status: OK
8.2 Spring charged / Discharged: OK
8.3 ACB Disconnected Position: OK
8.4 ACB Test Position: OK
8.5 ACB Connected Position: OK

10.10.8. ACB Accessories Verification:


Sl. No General Result Remarks
9.1 Key lock ( Lock in Open position ) NA
9.2 Operation Counter NA
9.3 Trip Contact Reset NA
9.4 Push button Padlock device NA
9.5 Push button Transparent Protective Cover NA
9.6 Key Lock for Rack in / Rack out NA

10.10.9. Insulation Resistance Test:


L1 (L2+L3+N shorted with L2 (L1+L3+N shorted with L3 (L1+L2+N shorted with N (L1+L2+L3 shorted with
Breaker Status
Earth) Earth) Earth) Earth)

Closed 687GΩ 601GΩ 721GΩ 830GΩ

Open 1.902TΩ 1.886TΩ >2TΩ >2TΩ

10.10.10. ACB Contact Resistance Test:


Pole Injected Current Contact Resistance(µΩ Remarks
L1.1 100A 10.9 µΩ
L2.1 100A 11.7 µΩ

L3.1 100A 11.1 µΩ

N1 100A 11.6 µΩ

Form No-ATLVS-S-2014-003, Rev-00, ABB Industries L.L.C, P B No-11070, Dubai, U A E, Tel -+971 4 3147500, +971 4 3401777, Fax - + 971 4 3401532

ABB Industries L.L.C


Test Report ELSE Service

ACB Service & Test Report


Serial. No: Page- 3 of 3

10.10.11. Test Instrument details:


Instrument Make Instrument Model Instrument Serial No Calibration Certificate No Calibration due date
MEGGER M1T1025 101738330 C02408339.01 16-08-2025
FLUKE 1587 98650137 C-24431 24-09-2025
MEGGER MJOLNER 600 1090583 C-23240 06-12-2024

10.10.12. Remarks:
1 SENSOR CT REPLACED ALONG WITH CABLE
2 PR REPLACED
3 MEASURING MODULE REPLACED IN PR
4 FRONT SHIELD COVER NOT MATCHING WITH THE ACB (SERIAL No. & Rating)

10.10.13. Undersigned Representatives:


General Serviced By Tested By Approved By
Name: DIPU / SOORAJ

Signature:

Date: 18/11/2024
Company: ABB

Form No-ATLVS-S-2014-003, Rev-00, ABB Industries L.L.C, P B No-11070, Dubai, U A E, Tel -+971 4 3147500, +971 4 3401777, Fax - + 971 4 3401532