Nice 3000+
X1-
X2-Doorzone-F502=003
X3-
X4-Overload-F504-046
X5-Fullload-F505=047
X6-Run monitor feedback-F506=038
X7-Brk monitor feedback-F507=039
X8-Stop=004
X9-Inspection Signal-F509=040
X10-Inspection up-F510=009
X11-Inspection dn-F511=010
X12-Up direction limit-F512=044
X13-Dn direction limit-F513=045
X14-Up reset limit-F514=048
X15-Dn reset limit-F515=049
X16-
X17-
X18-
X19-
X20-UPS Mode-F520=027
X21-Firemann-F521=011
X22-
X23-Shorting contact feedback-F523=030
X24-DCL-005(Not applicable when there is both side opening)
X25-Safety complete feedback-F537=004
X26-Landing gate-F538=005
X27-Car gate-F539=005
Y1-Run Coil-F526=1
Y2-Brk Coil-F527=2
Y3-PMSM SHORT CONTACTOR Coil-F528=12
After putting all parameters we have to input the motor data
F101-Rated motor Power,
F102-Rated motor Voltage,
F103-Rated Current,
F104-Rated frequency,
F105-Rated Speed
F125-1 for synchronous machine
Encoder data
F100-Encoder type=0(Sin-Cos/ENDAT)
F112-Encoder PPR=2048
F004-Motor rated speed in m/s
F003-Lift speed in m/s
F311-Inspection speed in m/s
F8-01=2(pre torque)
After putting all of these value we have to tune the motor.
Put F1-11=5 then press up/dn key of controller
For motor direction change put F210=0/1
Set
F200=20,
F201=0.2
F203=20
F204=0.3
F211=15
F212=0.2(0.1-0.2 as per site performance)
F213=0.3(02-0.3 as per site performance)
F600=Total no of opening(For example if the lift is g+4,then F600=5
F601=1
CTB PROGRAMME-
F525- Bit0-X1-Sensor1-1
Bit1-X2-Sensor2-1
Bit2-X3-Dol1-1
Bit3-X4-Dol2-1
Bit4-X5-Dcl1-1
Bit5-X6-Dcl2-1
Bit6-X7-Fullload-1
Bit7-X8-Overload-1
Make Fd07=0,Fd08=0(Firemann, Firefighter)
F640-Bit9=1(Reverse call enable)
F642-Bit3=1(For in running mode continue doorclose command)
F6 43 bit 0=1(For attender)
Bit 1=1
F9 00=0
F9 01=1
F9 02=0
F903= year
F904= month
F905= day
F906= hour
F907= min
FE00=0(Both collective)
FE01=1912(Gnd floor),1912(Basement floor)
FE01=1901(1st floor)
FE02=1902(2nd floor)
Normal-
Programme all the [Link] sure that all connection of car top junction box is
[Link] sure no shoting in Controller or field.
Locate the car at bottom most floor check the LEDS in motherboard.
Make sure,
X20-On,
X6-On,
X7-On,
X8-On,
X12-On,
X13-On,
X14-On
X24-On
Select F111=3,for shaft [Link] that adjust the levelling of the elevator.
For levelling adjustment use F400 and Fr00
Parameter
For ard,
F520=27,
F809=0.05 m/s (ard speed)
F810=1
Fb06-Door open protection time
Fb08-Door close protection time
Fb11,Fb12,Fb13(Door opening time)
F900=0
F902=0
Double door operation(Special Case)
F8-16=N(> F600)
Make back side lop programme
G=N+1 as on
Fb00= No of door machine=2
Fb02=Door machine 1 operation floor
(If the 1st door machine operates in all floor don't chang the default
programme(65535),if it is not operating in all floor then calculate the value using binary
code [Link] an example,let the 1 St door is operated in Gnd,1st,2nd floor then the
programme should be (2^0+2^1+2^2=00007))
Fb04=Door machine 2 operation floor(same as door machine 1)
FC04=1