1SDH001316R1002 Ekip Touch
1SDH001316R1002 Ekip Touch
SACE Emax 2
Instructions for using Ekip Touch protection trip units and Acces-
sories.
Glossary..................................................................................................3
Introduction.......................................................................................... 4
1 - Contents.......................................................................................4
2 - Safety............................................................................................5
Protections.......................................................................................... 14
1 - Protections - Introduction......................................................14
2 - Standard Protections..............................................................15
3 - Voltage protections.................................................................19
4 - Voltage Advanced protections............................................. 20
5 - Frequency protections............................................................21
6 - Power protections...................................................................22
7 - ROCOF protections..................................................................23
8 - Adaptive protections..............................................................23
9 - Additional protections and functions................................ 24
Accessories.......................................................................................... 29
1 - Measurement........................................................................... 29
Management operations....................................................................31
1 - Ekip Touch maintenance and troubleshooting..................31
Glossary
Term Description
SACE Emax 2 New series of ABB SACE air circuit-breakers
CB Circuit-breaker
Electronic unit connected to the CB, which provides measuring, monitoring and protection functions for the
Trip unit
CB if faulty operating conditions occur. In the event of an alarm, it commands a TRIP
Ekip Touch Trip unit for SACE Emax 2 CBs, equipped with touchscreen display and available in four different versions
Trip coil CB opening actuator controlled directly by Trip unit
Concluding action of protection timing or a test command which, except in special configurations applicable
TRIP to the trip unit, coincides with activation of the trip coil, which instantly opens the bars of each pole and
interrupts the circulating current
Vaux Auxiliary power supply
4P / 3P / 3P + N CB configuration: four-pole (4P), three-pole (3P) and three-pole with external neutral (3P + N)
If Fault current measured by Trip unit, useful for calculating the trip time t t
Introduction
1 - Contents
Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Emax 2 CBs,
among which:
1. general overview:
2. operating conditions
3. consultation of menus for changing parameters and displaying measurements
4. overview of protections, measurements, parameters and main accessories
5. management operations: maintenance, troubleshooting
Integrated informations A full description of Ekip Touch is available in document 1SDH001330R1002 (Emax 2 engineering manual)
available on the website ABB library.
recipients This manual refers to two user profiles, as defined by standard IEC 60050:
• skilled person, in the electrical field (IEV 195-04-01): person with sufficient training and experience
to enable him or her to perceive risks and avoid the dangers potentially created by electricity)
• instructed person, in the electrical field (IEV 195-04-02): person adequately advised or supervised
by electrically skilled persons to enjable him or her to perceive risks and to avoid danger which
electricity can create
IMPORTANT: operations which can be performed by persons trained on the subject of
electricity are specifically indicated in this manual. All the remaining operations described
in this manual must be performed by skilled persons, in the field of electricity. ABB
declines all liability for damage to persons or property caused by failure to comply with
the instructions in this document.
Specifications and supporting To ensure that Ekip Touch is installed and configured correctly, please read the information in this manual
documents and in the technical documentation of the product, supplied with the circuit-breaker or available in the
website ABB library
Document Description
Installation, operation and maintenance instructions for Sace Emax E1.2
1SDH000999R0002
CBs and Ekip Dip Trip units
Installation, operation and maintenance instructions for Sace Emax E2.2-
1SDH001000R0002
E4.2-E6.2 CBs and Ekip Dip Trip units
Manual for design engineers with full information about the trip units and
1SDH001330R1002
accessories for Emax 2
1SDH001140R0001 Communication System Interface for Emax 2 CBs
1SDC200023D0906 Sace Emax 2 CBs General catalog
1SDM000091R0001 Sace Emax 2 CBs Circuit diagrams
WARNING! carefully read the instructions for putting into service and maintenance given
in the manual 1SDH001330R1002.
Design notes The information in this manual was written in Italian and then translated into other languages to conform
to the laws and/or commercial requirements concerning the product.
2 - Safety
Safety requirements
HAZARD
ACCIDENTAL CONTACT WITH LIVE POINTS
CAN CAUSE SHOCK, BURNS AND RESULT
IN DEATH.
Figure 1
WARNING!
• detailed descriptions of the standard installation, operation, maintenance procedures and
principles for working safely are not included; it is important to note that this document
contains indications about safety and caution, against certain methods (concerning
installation, operation and maintenance) which could cause imjuries to the personnel,
damage devices or make them unsafe
• these warnings and alarms do not include all the conceivable methods of performing the
installation, operation and maintenance operations recommended by ABB and others, which
could be performed, or the possible consequences and complications of each conceivable
method, neither will ABB investigate all those methods
• anyone who is implementing procedures or using maintenance devices recommended by
ABB or not must check carefully that neither their personal safety nor the safety devices are
endangered by the installation, operation, maintenance method or by the tools used; contact
your nearest ABB representative for further information, explanations or specific problems
• this manual is written for qualified personnel only and is not intended to replace an adequate
training course or experience concerning the safety procedures of this device
• regarding products equipped with communication systems, the purchaser, installer or end
customer are responsible for applying all the IT security measures to prevent risks deriving
from connection to communication networks; among others, these risks include use of
the product by unauthorized persons, alteration of its normal operation, access to and
modification of the information
• the purchaser, installer or end customer are responsible for ensuring that safety warnings
and notices are affixed and moreover, that all points of access and operating devices are
securely blocked when the switchgear is left even momentarily unattended
• all information in this document is based on the latest product data available at the time of
printing. We reserve the right to make changes to the document at any time and without
prior notice
Warnings WARNING! READ THIS MANUAL WITH CARE BEFORE INSTALLING, OPERATING OR REPAIRING
THE CIRCUIT-BREAKER
• file this manual with all the other available documents concerning the circuit-breaker
• to facilitate the work, these documents must be readily available when the CB is installed,
operated and serviced
• the unit must be installed in accordance with the environmental, electrical and mechanical
limitations described in the product documentation
• this circuit-breaker has been designed to operate with voltage and current values within the
rating plate limits: do not install in systems that operate at values exceeding these rated
limits
• comply with the safety procedures required by your Company.
• do not open covers or doors, do not work on devices before having disconnected all circuits
from the electricity sources and after having made sure of this with a measuring instrument
1 - General characteristics
Main functions SACE Emax 2 can be configured using the Ekip Touch trip unit, which is available in several versions and
able to provide, protection, measurement and signalling functionalities.
Emax 2 can be provided with mechanical, electronic and testing accessories, and is supported by many
different types of software and applications enabling the functions of the Trip unit and circuit-breaker to
be expanded.
Detailed information is available in manual 1SDH001330R1001. 1SDH001330R1002.
Default functions and Every Ekip Touch module has default measurement and protection functions, which can be extended with
extensions the aid of additional software packages.
The extensions (additional SW packages) can be pre-engineered when the circuit-breaker is ordered or at
a later date (in this case, via ABB Ability Marketplace TM
Description Lists of the main characteristics of the protections and measurements of each package are given in the
next chapters.
A description of the Datalogger and Network Analyzer functions is available in manual 1SDH001330R1002.
Internal and external The functions of Ekip Touch can be expanded by further internal and external accessories, which differ as
accessories to function and assembly position; certain accessories can also be configured with Ekip Dip.
In manual 1SDH001330R1002 Contains the lists and descriptions of all the available accessories, the
support software and all the additional functions.
Electrical characteristics The Ekip Touch measurement and protection functions described in this document are provided with
primary voltage and current values within the following nominal ranges:
Parameter Rated operating range
Primary current 0,004 ÷ 16 In (1)
Primary voltage 5 ÷ 690 V AC (2)
Rated frequency 45 ... 55 Hz (with fn= 50 Hz) / 54 ... 66 Hz (with fn= 60 Hz)
Peak factor Complying with standard IEC 60947-2
(1)
range with reference to each phase; In refers to the rated size defined by the Rating plug installed
on the Trip unit, available in models from 100 A to 6300 A, depending on the circuit-breaker model
used
(2)
for Ekip Touch rated highest line-to-line voltage connected directly to Trip unit, also to sockets
inside the CB; external transformers must be used for higher voltage values, consult the chapter
dedicated to the Measurement modules
Self-supply The internal current sensors are able to supply the Trip unit directly; Ekip Touch versions Hi-, G, G Hi- are
also fitted with the Measurement enabler with voltage sockets module, which allows the Trip unit to be
supplied by the installation voltages as well:
Parameter Operating limits
> 30 A (E1.2-E2-2-E4.2 with Rating Plug < 400 A)
Minimum three-phase turn-on current > 80 A (E1.2-E2-2-E4.2 with Rating Plug ≥ 400 A)
> 160 A (E6.2)
Minimum three-phase turn-on voltage > 80 V
Auxiliary power supply Ekip Touch can be connected to an external auxiliary supply source, which is useful when certain functions
such as communication via Local Bus, recording manual operations, certain measurements and the
datalogger must if available.
Auxiliary power supply can be provided by modules from the || Ekip Supply|ii| range or by direct
connection to the terminal box; a direct connection can also be made. Details are available in the manual
1SDH001330R1002.
1 - Presentation of interface
Components The Ekip Touch interface includes a touchscreen, short-cut push-buttons, status leds and a service
connector for certain external accessories:
Figure 2
Pos. Description
A Single-touch color touchscreen display
B LED Power
C LED Warning
D LED Alarm
E HOME push-button
F iTEST push-button
G Service connector
If on at the same time, the Warning and Alarm leds provide further signals:
• LEDs on and flashing fast: absence of communication between Trip unit and Mainboard or T
protection timing
• leds on with slow flashing: internal error
These cases need assistance from ABB.
Push-buttons Push-
Description
button
Allows different areas of the menu to be accessed:
HOME • from pages HOME, Histograms, Measuring instruments, Measurements, Main
measurements open the page Main page;
• from pages Main page, Alarm list, at any point of the menu area open: HOME page.
Allows certain pages of information about the unit to be rapidly consulted; press the
button in succession to display the following pages:
• Alarm list, if messages are present;
• Info, if Customer Page option is active;
• Protection unit, with information about Ekip Touch;
iTest • Circuit breaker, with information about the CB;
• Last trip, with information about the last trip, if available.
Consultation is active from pages: HOME, Histograms, Measuring instruments,
Measurements, Main measurements
NOTE: with Ekip Touch off and the internal battery charged, press iTEST to
temporarily switch on the Power led and, in the case of a trip, the display with
information about the trip protection and the Alarm led
Service connector The service connector enables Ekip Touch to be connected to Ekip TT, Ekip T&P and Ekip Programming,
allowing the unit to be temporarily supplied, parameter configuration prior to putting into service, tests
and extension of the configuration functions.
IMPORTANT: only use cables supplied by ABB or with ABB accessories
2 - Navigation
Levels and pages The Ekip Touch menu is divided into several levels, all accessible using the touchscreen display and
buttons available in the units:
Level 1 (HOME)
Page shown on power up; appears when push-button of the same name appears, as described on page
9; from here you can:
1. access the MAIN PAGE (level 2), by pressing the HOME button
2. access the Alarm list, by selecting the diagnostic bar at the bottom
3. access the Summary pages of some of the measurements by pressing on the edges
Level 1 Level 3
Level 2 Level 4
Figure 3
Changing parameters Comply with the following procedure to change one or more parameters:
IMPORTANT: parameters can be changed with Trip unit in the Local mode and in the
absence of timing alarms
Figure 4
4. When the new value has been selected/confirmed, the menu of the parameter is accessed automatically,
the changed item presents the new value in light blue and a tick to confirm:
Figure 5
Figure 6
Figure 7
Commands Selection of a command implies its immediate execution or opening of an intermediate confirm window.
Correct execution is indicated by a confirm window, which disappears automatically from the display.
Certain commands, selection of which immediately activates the respective test sequences without any
confirm window, are an exception to this rule:
• Auto Test
• Ekip Signalling 2K module commands
IMPORTANT: confirmation on the display refers to launching the command, not to
verification of the operation required, which is at the user's charge whichever type of
command is concerned: reset parameters, display, open/close contacts
Exceptions Before validating a change to a parameter, the Trip unit checks all its parameters to make sure there is no
conflict or incorrect condition:
• if the Trip unit detects an incorrect condition, the relative details appear on the display and
parameter modification is annulled.
Before executing a command, the Trip unit checks all its parameters to ensure there is no conflict or
incorrect condition:
• if the Trip unit detects an incorrect condition, the relative details appear on the display and
command execution is annulled.
WARNING! aborting the programming affects all the parameters modified during the
same session
Safety WARNING! the user is responsible for security against unauthorized access and
modification: configure all Trip unit access points (display menu and, if present, Ekip
Connect and remote communication systems) using the access PIN and controlled and
authorized connection systems
Function The PIN code enables access to certain areas of the Trip unit and prevents unintentional setting errors
from being entered via the display.
However, parameters can still be modified without having to enter the PIN via:
• service connector, using Ekip T&P or Ekip Programming and the Ekip Connect application
• bus, in the presence of Ekip Com modules and with Trip unit configured as Remote (page 27).
To ensure your unit is in secure conditions, the Wizard window immediate asks you to change the PIN
code on first power up; this is strongly recommended by ABB.
Description The PIN code is a number formed by five digits, each of which can be given a value from 0 to 9; the default
value is: 00001 and can be changed in the Settings-New PIN menu.
The PIN code must be entered to:
• change a parameter (including the PIN code itself)
• access the Test menu
Once the PIN code has been entered, all menus can be browsed for two minutes: once two minutes have
elapsed, the PIN code must be entered again (depending on the case in question).
NOTE: the PIN code must also be entered again if a programming session has been annulled
(page 11).
Entry The following page will appear when the PIN code is requested: change (1) and confirm (2) each digit to
complete the entry process.
Figure 8
NOTE:
• if the PIN is wrong, “Wrong PIN” will appear for three seconds after which the entry page will
be displayed again; use the command at the top left to quit
• there is no limit to the number of wrong PIN that can be entered
Disabling The PIN code can be disabled by entering its value as: 00000; In this case, the PIN is only required to
change the PIN itself in the Settings menu.
Protections
1 - Protections - Introduction
Operating principle The protection functions are available with all Ekip Touch models and versions.
Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
operating principle is the same:
1. If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/
or alarm condition).
2. The alarm appears on the display and, after a period of time (timing t t), depending on the
protection parameters set, can convert into a trip command (TRIP) transmitted to the internal
Trip Coil of the CB.
NOTE:
• if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
Touch quits the alarm and/or timing status and returns to the normal operating condition
• all protections have a default configuration: check the parameters and change to suit the
installation requirements before putting into service
• to allow circuit-breaker tripping to be controlled by a specific protection, the protection
itself must be enabled
References Many of the protection thresholds are displayed in two different quantities: absolute value and relative
value.
The relative value depends on the type of measurement:
Type of protection Reference Description
Current In Nominal current of the Rating plug
Voltage Un Line-to-line voltage setting
Frequency fn Frequency setting
Power Sn √3 x In x Un
2 - Standard Protections
List
The Standard protections available for all Ekip Touch models, are:
Th- Fun-
Name Type of protection Time Additional functions (6)
reshold ction
L Overloads with inverse long-time delay Thermal memory, Pre-alarm threshold
Trip enable, Zone Selectivity, Thermal
S Short-circuit with adjustable delay
Memory, Startup enable, Lock
Trip Enable, Zone Selectivity, Startup
S2 Short-circuit with adjustable delay
enable, Lock
I (3) Instantaneous short-circuit Startup enable, Lock
Trip enable, Zone Selectivity, Startup
G (2)(5) Earth fault with adjustable delay
enable, Locking, Pre-alarm threshold
Instantaneous short-circuit on circuit-
MCR (4) Monitoring period, Locking
breaker closing
Instantaneous short-circuit Zone selectivity, activation function and
2I
programmable mode, Delay ON/OFF
IU Current unbalance Trip enable, Algorithm
Neutral Different protection on neutral phase
T Abnormal temperatures Trip enable
Iinst (1)
Instantaneous short-circuit
Harmonic
Distorted waveforms
distortion (7)
Hardware Trip Internal connection errors
Current thresholds
(7) Control thresholds exceeded Direction of current flow
(1)
protection cannot be deactivated; its trip parameters are set by ABB and cannot be edited
(2)
not available with LSI version of Trip unit
(3)
can be activated with protection MCR = Disable
(4)
can be activated with protection I = Disable
(5)
if the presence of sensor S.G.R. is activated, the submenu of protection G will be replaced by that of protection Gext, in the Advanced
menu; with Trip unit models Ekip Hi-Touch and Ekip G Hi-Touch, the two protections are available at the same time
(6)
Thermal memory available with curve t=k/I 2; Zone selectivity available with curve t=k; Block configuration available via Ekip Connect
(7)
the protections do not handle the TRIP, just signaling
Neutral Protection Neutral protection is used to characterize protections L, S and I differently on the neutral phase.
Represented as a percentage, it defines the multiplication factor applied to the tripping thresholds of the
protections (example: 50% = the tripping threshold of the neutral is half the phase threshold).
The protection is available with the 4P and 3P + N configuration; the configuration parameters can be
accessed via the Settings menu
NOTE: the Trip unit will not accept changes to the thresholds of protection L (I1) and of the
Neutral (InN) unless the following limtation is complied with: (I1 x InN) ≤ Iu; Iu is the size of
the circuit-breaker
WARNING! With 150% and 200% threshold; if the measured neutral current exceeds 16In,
the Trip unit resets the protection to 100% by itself
T Protection T protection protects against abnormal temperatures measured and transmitted to the sensor inside the
unit; temperature verification is always active and includes three operating states:
State Temperature range [°C] Ekip Touch actions
Standard -25 < t < 70 Normal operation; display state depending on type (1)
Warning led @ 0.5 Hz; display state depending on type
Warnings -40 < t < -25 or 70 < t < 85 (1)
with Ekip Touch, the display remains on within range: -20°C / +70°C; with Ekip LCD, the display
(1)
Other protections The Iinst, Harmonic distortion, Hardware trip and Current threshold protections are described in detail in
the manual 1SDH001330R1002.
NOTE: the performance of the additional Startup and Zone selectivity functions is described in the manual 1SDH001330R1002.
(1)
ANSI / IEEE C37-2 codification
(2)
t t calculation is valid for If values that have exceeded the trip threshold of the protection. Use fault current and threshold values
expressed in In to calculate t t, as shown in the example.
(3)
Tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits. The tolerance values of the table after the notes apply if the conditions are not guaranteed
(4)
All thresholds can be selected in the presence of auxiliary power supply. In self-supply conditions, the minimum threshold is limited to:
0.3 In (with In = 100 A), 0.25 In (with In = 400 A) or 0.2 In (for all the other sizes)
(5)
Time MCR is the time for which the protection remains active after the circuit-breaker has closed. Similarly to protection I, the trip time
cannot be adjusted
(6)
Startup can only be activated with function set at fixed time
(7)
For the startup functions, the time indicated is the period during which the protection remains active with the different threshold,
calculated from the point in which the startup threshold is exceeded
(8)
With t4 = instantaneous, the maximum tolerance is 50 ms
(9)
L protection: the trip time of the protection is forcibly set at 1 s if the calculation results give a lower theoretical tt value and/or if the
current reading is more than 12 In
(10)
G protection: the protection deactivates automatically if disconnection of one or more sensors is detected or if current If is more than
8 In (with I4 ≥ 0.8 In), 6 In (with 0.5 In ≤ I4 < 0.8 In), 4 In (with 0.2 In ≤ I4 < 0.5 In) or 2 In (with I4 < 0.2 In)
(11)
S and G protection: with curve t= k/I 2, the protection trip time is forced to the set value if the calculation results give a theoretical tt
value lower than the parameter itself
(12)
A maximum value of I4= 1200 A is allowed for UL versions; if an attempt is made to set a higher value, the trip unit signals an alarm and
interrupts the modification
(13)
For UL versions, t2 and t4 can be set at 0.4 s maximum
3 - Voltage protections
List
The Voltage protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in the remaining models
as additional SW package, are:
Th-
Name Type of protection Time Additional functions (2)
reshold
UV Minimum voltage Trip enable, Block
OV Maximum voltage Trip enable, Block
UV2 (1) Minimum voltage Trip enable, Block
OV2 (1) Maximum voltage Trip enable, Block
VU Voltage unbalance Trip enable, Block
Phase Sequence Phase sequence error
(1)
protections UV2 and OV2 are not available by default with Ekip G Touch. However, they can be integrated by requesting the relative SW
package
(2)
Block configuration available via Ekip Connect
Summary table
Tolerance Calculation
ABB ANSI (5) Threshold Time Tolerance t t (4)
threshold formula t t (3)
The best of the two values: ± 10% or ±
U8 = 0,5…1 Un t8 = 0,05...120 s
UV 27 ± 2 % (7) t t = t8 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U9 = 1…1,5 Un Step t9 = 0,05…120 s
OV 59 ± 2 % (7) t t = t9 40 ms (for set time < 5 s) / ± 100 ms (for
= 0,001 Un Step = 0,01 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U15 = 0,5…1 Un t15 = 0,05…120 s
UV2 27 ± 2 % (7) t t = t15 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U16 = 1…1,5 Un t16 = 0,05…120 s
OV2 59 ± 2 % (7) t t = t16 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U14 = 2…90 % Step t14 = 0,5…60 s
VU (6) 47 ±5% t t = t14 40 ms (for set time < 5 s) / ± 100 ms (for
=1% Step = 0,5 s
set time ≥ 5 s)
Phase
47 1-2-3 / 3-2-1
Sequence
(3)
calculation of t t is valid for values which have exceeded the trip threshold of the protection
(4)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(5)
ANSI / IEEE C37-2 codification
(6)
protection not active if the higher of the voltages measured is less than 0.3 Un
(7)
the trip unit considers 3% hysteresis for quitting alarm condition
List
The Advanced Voltage protections, available by default for the Ekip G Touch and Ekip G Hi-Touch models and configurable in the remaining
models as additional SW package, are:
Name Type of protection Threshold Time Additional functions (3)
S(V) Short-circuit with voltammetric control Mode, Trip enable, Block
S2(V) (1) Short-circuit with voltammetric control Mode, Trip enable, Block
RV (2)
Residual voltage Trip enable, Block
(1)
S2(V) protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
(2)
available for 4P or 3P circuit-breakers configured with external neutral voltage
(3)
Block configuration available via Ekip Connect
Summary table
Calculation
ANSI Tolerance
ABB Threshold (7)(8) Time formula t Tolerance t t (5)
(6)
threshold (4)
t
I20 = 0,6...10 In step = 0,1 In ;
(9)
The best of the two values: ± 10% or ±
Ul = 0,2...1 Un step = 0,01 Un (9); t20 = 0,05...30 s
S(V) 51V ± 10 % t t = t20 40 ms (for set time < 5 s) / ± 100 ms
Uh = 0,2...1 Un step = 0,01 Un (9); Step = 0,01 s
(for set time ≥ 5 s)
Ks = 0,1…1 step = 0,01 (9)
I21 = 0,6...10 In step = 0,1 In (10);
The best of the two values: ± 10% or ±
Ul2 = 0,2...1 Un step = 0,01 Un (10); t21 = 0,05...30 s
S2(V) 51V ± 10 % t t = t21 40 ms (for set time < 5 s) / ± 100 ms
Uh2 = 0,2...1 Un step = 0,01 Un (10); Step = 0,01 s
(for set time ≥ 5 s)
Ks2 = 0,1…1; step = 0,01 (10)
The best of the two values: ± 10% or ±
U22 = 0,05...0,5 Un Step = 0,001 t22 = 0,05...120 s
RV 59N ± 5 % (11) t t = t22 40 ms (for set time < 5 s) / ± 100 ms
Un Step = 0,01 s
(for set time ≥ 5 s)
(4)
calculation of t t is valid for values which have exceeded the trip threshold of the protection
(5)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(6)
ANSI / IEEE C37-2 codification
(7)
S(V) protection: in the Linear mode, the current trip threshold for voltage values between Ul and Uh is calculated by performing linear
interpolation between thresholds Uh and I20 (first point of the line) and Ul and Ks * I20 (second point of the line). I threshold = [I20 * (1 - Ks) *
(U measured - Uh)] / (Uh - Ul) + I20
(8)
S2(V) protection: in the Linear mode, the current trip threshold for voltage values between Ul2 and Uh2 is calculated by performing
linear interpolation between thresholds Uh2 and I21 (first point of the line) and Ul2 and Ks2 * I21 (second point of the line). I threshold = [I21 *
(1 - Ks2) * (U measured – Uh2)] / (Uh2 - Ul2) + I21
(9)
the threshold Ks setting must ensure the following limitation: Ks * I20 ≥ 0.6 In; parameter Uh is available in the Linear mode; the setting
must comply with the following limitation: Uh > Ul
(10)
the threshold Ks2 setting must ensure the following limitation: Ks2 * I21 ≥ 0.6 In; parameter Uh2 is available in the Linear mode; the
setting must comply with the following limitation: Uh2 > Ul2
(11) tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current
values within operating limits; the tolerance value is ± 10% if the conditions are not guaranteed
5 - Frequency protections
List
The Frequency protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in the remaining
models as additional SW package, are:
Name Type of protection Threshold Time Additional functions (2)
UF Minimum frequency Trip enable, Block
OF Maximum frequency Trip enable, Block
UF2 (1)
Minimum frequency Trip enable, Block
OF2 (1)
Maximum frequency Trip enable, Block
(1)
protections UF2 and OF2 are not available by default with Ekip G Touch. However, they can be integrated by requesting the relative SW
package
(2)
Block configuration available via Ekip Connect
Summary table
Calculation
Tolerance
ABB ANSI (5) Threshold (7)(8) Time formula t Tolerance t t (4)
threshold (3)
t
The best of the two values: ± 10 % (min = 30 ms) or ±
f12 = 0,9...1 fn t12 = 0,06...300 s
UF (6) 81L ± 1 % (7) t t = t12 40 ms (for set time < 5 s) / ± 100 ms (for set time ≥ 5
Step = 0,001 fn Step = 0,01 s
s)
f13 = 1...1,1 fn t13 = 0,06...300 s The best of the two values: ± 10% or ± 40 ms (for set
OF (6) 81H ± 1 % (7) t t = t13
Step = 0,001 fn Step = 0,01 s time < 5 s) / ± 100 ms (for set time ≥ 5 s)
The best of the two values: ± 10 % (min = 30 ms) or ±
f17 = 0,9...1 fn t17 = 0,06...300 s
UF2 (6) 81L ± 1 % (7) t t = t17 40 ms (for set time < 5 s) / ± 100 ms (for set time ≥ 5
Step = 0,001 fn Step = 0,01 s
s)
f18 = 1...1,1 fn t18 = 0,06...300 s The best of the two values: ± 10% or ± 40 ms (for set
OF2 (6) 81H ± 1 % (7) t t = t18
Step = 0,001 fn Step = 0,01 s time < 5 s) / ± 100 ms (for set time ≥ 5 s)
(3)
calculation of t t is valid for values which have exceeded the trip threshold of the protection
(4)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(5)
ANSI / IEEE C37-2 codification
(6)
the protection excludes itself if the maximum value of the line-to-line voltage is less than 32 V with hysteresis at 36 V
(7)
tolerance valid for frequencies within range: fn ± 2%; a ± 5% tolerance is available for off range frequencies
6 - Power protections
List
The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
SW package, are:
Name Type of protection Threshold Time Additional functions (3)
RP Reverse active power Trip enable, Block
Trip enable, Directional Zone Selectivity (4),
D (2) Directional short-circuit with adjustable delay
Startup enable, Block, Direction Min Angle
OQ (1) Maximum reactive power Trip enable, Block
OP (1)
Active overpower Trip enable, Block
UP (1)
Active underpower Trip enable, Block, Startup enable
RQ (1)(2) Reverse reactive power Trip enable, Block
CosΦ Minimum cosφ
(1)
the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
(2)
the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
(3)
Block configuration available via Ekip Connect
(4)
Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G
WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit. Power flow
must be configured and verified on the basis of your installation to ensure that all the protections of the Power Protections
package function correctly
Summary table
Calculation
Tolerance
ABB ANSI (7) Threshold Time formula t Tolerance t t (6)
threshold (5)
t
The best of the two values: ± 10% or ±
P11 = -1...-0,05 Sn step = t11 = 0,5...120 s
RP 32R ± 10 % t t = t11 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,01 s
set time ≥ 5 s)
t7 Fw/Bw = ± 40 ms (for t7 ≥ 400 ms) / whichever is
I7 Fw/Bw = 0,6...10 In step ± 7 % If ≤ 6 In
D (8) 67 0,1...0,8 s step = t t = t7 higher, ± 20 ms or ± 10 % (for t7 < 400
= 0,1 In ± 10 % If > 6 In
0,01 s ms)
The best of the two values: ± 10% or ±
Q27 = 0,4...2 Sn step = t27 = 0,5...100 s
OQ 32OF ± 10 % t t = t27 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
P26 = 0,4...2 Sn step = t26 = 0,5...100 s
OP 32OF ± 10 % t t = t26 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s
set time ≥ 5 s)
The best of the two values: ± 10% or ±
P23 = 0,1...1 Sn step = t23 = 0,5...100 s
UP (9) 32LF ± 10 % t t = t23 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s
set time ≥ 5 s)
Q24 = -1...-0,1 Sn step =
The best of the two values: ± 10% or ±
0,001 Sn; Kq = -2…2 step t24 = 0,5...100 s
RQ 40 / 32R ± 10 % t t = t24 40 ms (for set time < 5 s) / ± 100 ms (for
= 0,01; Vmin = 0,5...1,2 Un step = 0,5 s
set time ≥ 5 s)
step = 0,01
Cosφ = 0,5...0,95 step =
CosΦ 78 - - - -
0,01
(5)
calculation of t t is valid for values which have exceeded the trip threshold of the protection
(6)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(7)
ANSI / IEEE C37-2 codification
(8)
the protection does not detect the fault current direction for < 5 V voltages.
(9)
not active if the circuit-breaker is open (TRIP OFF is signaled); the protection is also active for negative active power, but is independent
of RP protection (Protection from inverse active power)
(10)
UP protection startup should be considered as the temporary deactivation time of the protection, from the point in which the startup
threshold is exceeded
7 - ROCOF protections
Description
The ROCOF Protection package includes the protection of the same name and is available by default for Ekip G Hi-Touch; it can be configured in
the remaining models as additional SW package
ROCOF Protection protects against rapid frequency variations and has the following additional functions: Trip Enable, Trip Direction and Block.
Further details about the protections are given in document 1SDH001330R1002.
Summary table
Tolerance Calculation
ABB ANSI (3) Threshold Time Tolerance t t (2)
threshold formula t t (1)
The best of the two
f28 = 0,4...10 Hz / s
ROCOF (4) 81R ± 10 % (5) t28 = 0,06...300 s step = 0,01 s t t = t28 values: ± 20% or 200
step = 0,2 Hz / s
ms
(1)
calculation of t t is valid for values which have exceeded the trip threshold of the protection
(2)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value becomes ± 20% if the conditions are not guaranteed
(3)
ANSI / IEEE C37-2 codification
(4)
not active for voltage values < 30 V
(5)
± 20% for threshold 0.4 Hz / s
8 - Adaptive protections
Description
The Adaptive Protection package includes the Double Set protection and is available by default for Ekip G Hi-Touch; it can be configured in the
remaining models as additional SW package
The Double Set function enables two different protection configurations to be made, one as an alternative to the other, by means of a set change
with programmable events.
Parameters
The function can be activated and the Set of the main protections configured in the Settings - Double Set menu; the event that determines Set
change (from main to secondary) can be programmed in the Advanced - Functions menu.
Additional protections Some protections have additional functions which extend their characteristics and performance:
Additional protections Installation of certain accessories allows the additional protections to be activated:
Th- Fun-
Name Type of protection Time Additional functions
reshold ction
Earth fault with current Trip enable, Zone Selectivity,
Gext reading by S.G.R. Startup enable, Locking, Pre-alarm
external sensor threshold
Residual current with
Rc corrent reading by
external toroid Rc
Synchronism between
two independent
Synchrocheck voltage sources or
energizing of a busbar
not active
Earth fault with current Trip enable, Zone Selectivity,
MDGF reading by MDGF Startup enable, Locking, Pre-alarm
external sensor threshold
Programmable Functions and Ekip Touch has eight programmable commands, which activate on the basis of signals or events. Each
Commands command allows the activation function and event monitoring time to be programmed.
Name Description Menu path
External Trip Sends a TRIP command
RESET Trip TRIP signal reset Advanced - Functions
Activate SET B Changes the protections set, from Set A to Set B
Energy RESET Resets the energy meters Measurements - Energy
Command YO Sends a command to opening coil YO
Settings - Functions
Command YC Sends a command to closing coil YC
Changes the configuration, from Remote to
LOCAL Switch On Settings - Modules
Local
- Functions
Signaling RESET Reset the contacts of the signalling modules
List and performance Presence of the Class 1 Power & Energy Metering package allows higher measuring accuracy to be
obtained for the following quantities:
Normal operating Accuracy of
Measurement Monitor time (min-max) range read value
Standard IEC 61557-12,
Phase currents (6) (8) 0,004 ÷ 64 In 0,5 % (1)
tables 20-22
Internal earth fault Standard IEC 61557-12,
0,08 ÷ 64 In 0,5 % (1)
current (2) table 20
Line frequency 30 ÷ 80 Hz (3)
fn ± 10 % (4) ± 0,02 Hz
Total active and |Pmin ÷ Pmax| (5) Standard IEC 61557-12, 1% (1)
apparent power (7) tables 8-11-14
Active and apparent Standard IEC 61557-12,
|Pmin ÷ Pmax| (5) 1% (1)
phase power tables 8-11-14
Total active and 1 kWh ÷ 2 TWh; 1 kVARh ÷ 2 TVARh; Standard IEC 61557-12, 1 % (1)
apparent energy 1 kVAh ÷ 2 TVAh tables 8-11-14
Standard IEC 61557-12,
Power factor 0,5 ÷ 1 1% (1)
table 27
(1)
the accuracy values refer to the normal operating intervals and conditions established by IEC
61557-12, for each quantity and class declared
(2)
available with LSIG versions
(3)
available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un ≥ 277 V)
(4)
47 ÷ 55 Hz with fn = 50 Hz; 54 ÷ 66 Hz with fn = 60 Hz
(5)
Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
(6)
the higher phase currents are also available in the Histograms, Measuring instruments and
Measurement summary pages
(7)
the higher total powers are also available in the Measuring instruments and Measurement
summary pages
(8)
internal phase current; in the presence of an external Neutral, the accuracy of current Ne is 1%
Functional characteristics The measuring performance of the Class 1 Power & Energy Metering package is guaranteed in the
following conditions (from table 43 of standard IEC 61557-12):
Characteristic Value
Classification of performance measuring and
monitoring device (PMD) in accordance with chapter PMD-DD
4.3 of the standard
Operating: T= -25°C to +70°C; Storage: T =
Temperature -30°C to +70°C; Class: K70
Up to 90% relative humidity without
humidity and altitude condensation; From 0 to 2000 meters
Performance class for active energy and power 1
Information page Presence of the Class 1 Power & Energy Metering package activates the IEC 61557-12 information page,
which can be consulted in the About menu
Figure 9
The page shows the activation state of the Class 1 Power & Energy Metering package (Activated/
Deactivated) and the serial numbers of certain accessories installed on the CB for the specific purpose of
conforming to the characteristics of the package (electronic units and internal current sensors)
1 - Main settings
Foreword All the following parameters are available either directly, or from the Settings menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
Consult manual 1SDH001330R1002 for any Main settings in the menu which are not described below
and for the Integrative settings (available by accessing the unit by means of a service connector via Ekip
Connect or by communication via system bus):
• Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
• Phase Sequence
• Monitor time
• Power Controller
• Load Shedding
• Network Analyzer
• Datalogger
• Dual Set
• Functions
• View
• Maintenance
• Programmable states
• Filters
• TAG Name, User data, Clients Page
• LED Alive
• Supplementary settings for commands, zone selectivity, Wizard
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be
activated, is available for the 3P CB.
Activation of the configuration with External neutral (3P + N) enables:
• histograms of phase Ne in the Histograms page
• neutral current measurements
• submenu for configuring the Neutral protection (Neutral Protection)
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection In the earth Circuit-breaker-Protections menu of the LSIG version of Ekip Touch you can:
• activate/deactivate the presence of external toroid S.G.R and relative Gext protection.
• activate the presence of Rc Toroid and relative protection.
• activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE: Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
Bluetooth Low Energy - Details of connection Security are available in manual 1SDH0013300R1002.
Connection security
IMPORTANT: when Bluetooth Low Energy antenna is on, communication on the service
connector is not available
Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
Ekip Com (in the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset and if
necessary replace the battery inside Ekip Touch (page 31).
Accessories
1 - Measurement
Configurations available Consult the manual for the electrical specifications and connection to the isolation transformer with
respect to the available configurations 1SDH001330R1002.
Electrical characteristics The Measurement modules function correctly in the electrical conditions described on page 7.
Installations with up to 1200 VAC line-to-line voltage can be connected and configured in the presence of
connections to external sockets and an isolation transformer.
Isolation transformer The isolation transformer must conform to standard IEC 60255-27 and possess the following
characteristics:
Characteristics Description
• Accuracy class: ≤ 0,2
• Performance: ≥ 10 VA
• Overload: 20 % permanent
• Insulations: 4 kV between inputs and outputs, 4 kV between shield and
Electrical
outputs, 4 kV between shield and inputs
• Frequency: Fn +-10%
• Primary voltage: 100 to 1200 V (nominal, to be configured via menu)
• Secondary voltage: 100 to 230 V (nominal, to be configured via menu)
Parameters The specific configuration area will activate in the Settings - Modules - Ekip Measuring menu if the
Measurement module is detected correctly by the trip unit.
The following items can be configured in this menu:
• the rated voltage
• presence of the isolation transformer and the mode in which the values of the relative parameters
are selected
• the power flow
• presence of external neutral voltage (with 3P circuit-breaker)
Replacement The Measurement module can be replaced on its Trip unit, for details consult document 1SDH001000R0528.
If the Measurement module is replaced, module change is indicated on the display by an alarm in the
diagnosis bar when the apparatus is powered for the first time.
To install the new module:
• Confirm the installation module which appears automatically on the display
WARNING! if the Class 1 Power & Energy Metering package is present, module replacement
will impair the performance values indicated on page 25; consult ABB to assess solutions
able to comply with your requirements
Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
exception of the protections listed below:
Protection Configuration
I1= 1 In; t1= 12 s; curve= t= k/I 2; prealarm: 90% I1I1= 1 In;
L (excluding Ekip M Touch)
t1= 48 s; curve= t= k/I 2; prealarm: 90% I1
I1= 1 In; t1= 22 s (Class= 10E); Thermal Memory= On;
L (only Ekip M Touch) Prealarm: 90 % I1I1= 0,4 In; t1= 45 s (Class= 20E); Thermal
Memory= On; Prealarm: 90 % I1
L (1) I1= 1 In; t1= 144 s; curve= t= k/I 2; prealarm: 90% I1
I3= 5.5 In (all except Ekip M Touch) / 6 In (Ekip M Touch);
I
startup= OFF
I I3= 4 In; startup= OFF
Harmonic distortion On
Rc (1) Idn= 3 A; Tdn= 0,06 s
Rc (2) Idn= 3 A; Tdn= 0,06 s
(1)
protection always active; a model L Disable rating Plug must be used to disable it
(1)(2)
protection available and active if model Rc Rating Plus is present
Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
following configurations:
Parameters Configuration
Frequency 50 Hz (IEC) / 60 Hz (UL)
Configuration 3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Neutral Off (3P circuit-breaker) / 50% (4P circuit-breaker)
Rated voltage 400 V
Power flow Bottom → Top
Phase Sequence 1-2-3
Local bus Off
Mode Local
Language English
Bluetooth Low Energy Off
Password 00001
Home page Histograms
LED Alive Disabled
View Horizontal
Maintenance On
Test Bus On
Modbus RTU par Address: 247; baudrate: 19.2 kbit/s
Profibus Address: 125
DeviceNet TM MAC ID: 63; baudrate: 125 kbit/s
Modbus TCP/IP Static IP: [Link]
Management operations
Introduction Correct maintenance of the unit and connected devices ensures they operate correctly over time.
The maintenance operations must be performed by expert personnel, as required by the safety regulations
and maintenance schedule described in this document and in the manuals 1SDH000999R0002 and
1SDH001000R0002).
If faults are discovered, find out what is causing them and eliminate them before putting the unit back
into service.
WARNING! Detecting faults must only be managed by (electrically) skilled persons (IEV
195-04-01: person with relevant education and experience to enable him or her to perceive
risks and to avoid hazards which electricity can create), as it may be necessary to perform
insulation and dielectric tests on part or all the installation
Alarms displayed and A list of faults that may appear on the Ekip Touch display is given below along with suggestions on how
suggestions to resolve them:
Signal Suggestions
Numerical alarm
Internal error; contact ABB if this typoe of error occurs
(e.g. 30002)
Unit on with auxiliary supply, Local Bus parameter enabled but connection
to modules not present, incorrect or communication lost (for more than five
Local bus seconds); check:
• connection and powering of modules in terminal box or external
• that the moldules connected are compatible with Ekip Touch
CB has failed to open and/or current still present after a TRIP command:
Trip fail command
comply with the procedure proposed in the next chapter 'Faults, causes and
(BF)
remedies'
Check:
• Rating plug of model compatible with Ekip Touch and CB size
• If present, protection parameters do not conflict with size of current of unit
Configuration details on page 14)
• In the absence of Vaux threshold I4 and/or I41 > 100 A
• In the absence of Vaux time t4 and/or t41 > 100 ms
• RC protection active and Rating Plug not RC
Ekip CI module not detected or absent, with Ekip M Touch and Open Mode
Ekip CI
configuration = Normal
Problem of Ekip Com Hub module with: certificates, connected devices,
Ekip Com Hub missing Com modules (RTU or with Ethernet connection), API TLS device, Hub
events, parsar configuration
Fault in Ekip Link module: check for loss of connection with one or more actors
Ekip Link Bus
(modules) connected to Link Bus
Ekip Sign 3T Alarm for connection of one or more analog inputs to Ekip Signalling 3T
connection module
Ekip Sign 3T One or more thresholds of the Ekip Signalling 3T module has/have been
threshold exceeded
Signal Suggestions
Internal error Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP
SNTP error
synchronization reference module
Measuring Error Measurement module parameter reading error, contact ABB
Ethernet
No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE 1588 synch Synchronization problem of IEEE 1588 synchronization reference module
Ekip Com module detected with incorrect / not allowed MAC address, contact
MAC Address
ABB.
Ekip Installation Installation error between HMI and Mainboard, contact ABB
Measuring Install Measurement module (Settings-Circuit breaker-Installation-Measuring-
installation Install) menu
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and
RatingPlugInstallation
check connection if there are further faults
Maintenance alarm: carry out maintenance and then reset the alarm via Ekip
Maintenance
Connect (see 1SDH001330R1002)
PC Power exceed The average power limit setting of the Power Controller has been exceeded
Rating plug not present, value or size incompatible with Ekip Touch
Rating plug
parameters
Zone Selectivity
Error in zone selectivity connections (Hardware Selectivity)
Diag
S.G.R. Toroid Check connection and state of toroid
Fault in connection of sensors to Trip unit; check status of sensors, including
Sensor L1/L2/L3/ external Neutral, or call ABB
Ne
Check current sensors, status of terminal and cables connecting to Ekip Touch
Configuration TFTP server enabled and/or configuration session open on module Ekip Com
Session IEC 61850 or Ekip Hub
IMPORTANT! Ignore the message if all the following conditions are
present at the same time:
• Vaux absence
• Absence of Ekip TT/Ekip T&P/Ekip Programming
• Presence of primary current near to self supply powering minimum
value (condition in which the Power LED flashes)
• After having pressed and held the Trip unit test button for at least three
seconds
__logo__note_tab__NOTE: |I|for further confirmation that the alarm is
Software Not unwarranted and must therefore be ignored, temporarily power by even only
Compatible one of these sources and check that the alarm is no longer displayed:|ii|
• Vaux (24 VDC) -> K1 K2. For further details, consult page#s#7
• Ekip TT/Ekip T&P/EKIP Programming
If the conditions indicated above are not present, the software versions
between Mainboard and display (Ekip Touch) are not compatible with
each other: to restore compatibility, please contact ABB
NOTE: modification of all parameters is inhibited via display; if
present, protections L, I and Iinst are active and function with the
parameters prior to the alarm (parameters of previous unit are
active if display has been replaced)
CB status CB state incorrect (esample: current present but CB in open state)
Switchboard Actor
communication Check configuration and connection of Ekip Link module
Error
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear Make sure that the contacts/poles are in good condition.
Protections
In the event of protection or measurement alarms, the associated signals are reported:
Signal Type of alarm
Trip Test Trip test performed signal. Press iTEST to reset the message
Protection timing (for example: L
Specific protection in time delay mode
timing)
Protection prealarm (for example:
Specific protection in prealarm
Prealarm G)
Protection (Trip off) [for example: Specific protection, configured with trip disabled, in alarm
S (Trip off) ] state
2I Protection Active 2I Protection active
Load LC1 / Load LC2 Current threshold 1 I1 / 2 I1 exceeded and in alarm state
Iw1 Warning / Iw2 Warning Current threshold Iw1 / Iw2 exceeded and in alarm state
Harmonic dist. Harmonic Distortion protection in alarm state
Power factor Power factor measurement (cosφ) less than set threshold
Phase cycle Phase sequence protection in alarm state
Frequency Frequency measured off range (<30 Hz or >80 Hz)
5th harmonic above Th / I sopra
Th / THD I above Th / THD V Single or total harmonic measurement above threshold
above Th
Faults, causes and remedies A list of possible faulty situations for Ekip Touch, their possible causes and suggestions about how to
resolve them are given below.
NOTE: check error messages on display before consulting the table; if the suggestions given
fail to resolve the problem, call the ABB assistance service and provide the report produced
by the Ekip Connect software if possible