IMB.e technical data
Rating (kVA) 5 10 15 20 30 40 50 5 10 15 20 30 40 50 60 80 100
Nominal power (kW) 4 8 12 16 24 32 40 4 8 12 16 24 32 40 48 64 80
Input
DC input voltage 110 Vdc (90÷160 Vdc range) 220 Vdc (180÷300 Vdc range)
110/115/120 or 220/230/240 Vac 1-phase ±20%
Bypass input voltage
(adjustable according to inverter output voltage)
Output
Nominal voltage 110/115/120/220/230/240 Vac 1-phase
Frequency 50/60 Hz (selectable)
Voltage regulation ±1% static; ±5% dynamic (80% load change), <40 ms recovery time
Overload capacity 125% for 10 min; 150% for 1 min; 200% for 100 ms
Harmonic Distortion THDv <2% linear load; <5% non-linear load
Due to our policy of continuous development, data in this document is subject to change without notice and becomes contractual only after written confirmation
System
Isolation Battery to load isolation included; input/output isolation available with additional
bypass transformer
Dimensions WxD (mm) Height is 2100 mm, width and depth vary with output
rated power and voltage (see the table below)
Rating 5 10 15 20 30 40 50 5 10 15 20 30 40 50 60 80 100*
110÷120 Vac 600x800 800x800 1000x800 600x800 800x800 1000x800 1400x800
Output voltage
220÷240 Vac 600x800 800x800 1000x800 600x800 800x800 1400x800
Maximum weight (kg) 320 360 400 440 500 550 610 320 360 400 440 470 500 550 600 730 830
Cooling Forced ventilation
Efficiency 94%
Colour RAL 7035
Protection degree
IP20 (other options)
(IEC 60529)