V7 Mini Parameters
V7 Mini Parameters
PARAMETER LISTING
The Drive control circuits use various parameters to select functions and characteristics of the
Drive. Changing of parameter settings must be done in the Program mode, or by use of the
Function LEDs, if available (see Section 4).
The following table lists all parameters in numerical order. For each parameter, reference
paragraph(s) in Section 5 are listed (if applicable) where the features of the Drive affected by that
parameter are described.
A1-1
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
Accel/Decel Time 0: 0.1
n018 1 (sec) 0 5.2
Setting Unit 1: 0.01
n019 Acceleration Time 1 (Note 4) 0.00 to 600.0 0.01 (sec)
n020 Deceleration Time 1 (Note 4) or or 10.0 5.2
n021 Acceleration Time 2 (Note 4) 0.0 to 6000 0.1 (sec)
n022 Deceleration Time 2 (Note 4) (Dependent on n018 setting)
0: No S-curve
1: 0.2 second
n023 S-curve Selection 1 0 5.3
2: 0.5 second
3: 1.0 second
n024 Frequency Reference 1 (Note 4) 6.00
n025 Frequency Reference 2 (Note 4) 0.00
n026 Frequency Reference 3 (Note 4) 0.01 (Hz) 0.00
n027 Frequency Reference 4 (Note 4) 0.00 to 400.00 (< 100 Hz) 0.00
n028 Frequency Reference 5 (Note 4) or 0.00 5.11
n029 Frequency Reference 6 (Note 4) 0.1 (Hz) 0.00
n030 Frequency Reference 7 (Note 4) (>= 100 Hz) 0.00
n031 Frequency Reference 8 (Note 4) 0.00
n032 Jog Frequency Reference (Note 4) 6.00 5.12
Frequency Reference Upper
n033 0. to 110 1(%) 100
Limit
5.9
Frequency Reference Lower
n034 0. to 110 1(%) 0
Limit
0: 0.01 Hz (less than 100 Hz) / 0.1 Hz
Digital Operator 1: 0.1%
n035 1 0 5.30
Display Mode 2 - 39: rpm
40 - 3999: custom
0.1 to 49.5
0.1 (A) (Note 1) 5.25
n036 Motor Rated Current (Up to 150% of drive rated current)
0: Short term rating
Electronic Thermal Overload
n037 1: Standard rating 1 0
Protection (for OL1 fault)
2: Disabled 5.25
Electronic Thermal Overload
n038 1 to 60 1 (min) 8
Protection Time Constant
0: Operates only when drive is running
Cooling Fan Operation (continues operation for 1 minute after
n039 1 0
Selection drive is stopped)
1: Operates with power applied to drive
0: Rotate C.C.W.
n040 Motor Rotation 1 0
1: Rotate C.W. (or opposite direction)
Acceleration Time 3
n041 0.00 to 600.00 0.01 (sec)
(Note 4)
Deceleration Time 3
n042 or or 10.0 5.2
(Note 4)
Acceleration Time 4
n043 0.0 to 6000.0 0.1 (sec)
(Note 4)
Deceleration Time 4
n044 (Dependent on n018 setting)
(Note 4)
0: Fwd / Rev command (3 wire control)
n050 Multi-function Input [can only be set in n052] 1 1
Selection 1 (Terminal S1) 1: Forward run (2 wire control) (1)
2: Reverse run (2 wire control)
3: External Fault (N.O.)
Multi-function Input 1 2 5.18
n051 4: External Fault (N.C.)
Selection 2 (Terminal S2) (2)
5: Fault Reset
6: Multi-step speed ref. cmd. A
Multi-function Input 1 3
n052 7: Multi-step speed ref. cmd. B
Selection 3 (Terminal S3) (0)
8: Multi-step speed ref. cmd. C
A1-2
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
9: Multi-step speed ref. cmd. D
Multi-function Input 1 5
n053 10: JOG Selection
Selection 4 (Terminal S4) (5)
11: Accel/Decel time change cmd.
12: External Base Block (N.O.)
Multi-function Input 1 6
n054 13: External Base Block (N.C.)
Selection 5 (Terminal S5) (6)
14: Speed search from max. freq.
15: Speed search from set freq.
Multi-function Input 1 7
n055 16: Accel/Decel hold command
Selection 6 (Terminal S6) (7)
17: Remote/Local selection
18: Serial Communication / control ckt.
selection
5.18
19: Fast Stop - Fault (N.O.)
20: Fast Stop - Alarm (N.O.)
21: Fast Stop - Fault (N.C.) 1 10
n056 Multi-function Input
22: Fast Stop - Alarm (N.C.) (10)
Selection 7 (Terminal S7)
23: PID control off
24: I value reset (PID)
25: I value hold (PID)
26: Over Heat Pre-alarm OH3
27: Accel/Decel Time Select 2
34: Up
0: Fault
1: During running
Multi-Function Output
2: Speed Agree
n057 Selection 1 1 0
3: Zero Speed
(Terminals MA, MB & MC)
4: Frequency detection 1
5: Frequency detection 2
6: Overtorque detection (N.O.)
7: Overtorque detection (N.C.)
8: Undertorque Detection (N.O.)
9: Undertorque Detection (N.C.) 1 1
Multi-Function Output
10: Minor Fault
n058 Selection 2 5.19
11: During Base Block
(Terminals P1 & PC)
12: Local / Remote
13: Ready
14: During auto restart
15: During undervoltage
Multi-Function Output
16: During reverse run
n059 Selection 3
17: During speed search 1 2
(Terminals P2 & PC)
18: Serial Comm. Controlled
19: PID feedback loss
20: Frequency Reference Loss Detect (N.O.)
``
21: Overheat Pre-alarm OH3 (N.O.)
Analog Frequency Reference
n060 0 to 255 1 (%) 100
Gain (term. FR to FC) (Note 4)
5.8
Analog Frequency Reference
n061 -100 to 100 1 (%) 0
Bias (term. FR to FC) (Note 4)
Analog frequency reference
n062
filter time constant 0.00 to 2.00 0.01 (sec) 0.10
(term. FR to FC) (Note 4)
Frequency Reference Loss 0: No Detection
n064 1 0 5.33
Detection 1: Continue to run at 80% of max. frequency
Monitor Output0: Analog monitor output
n065 1 0 5.17
Selection 1: Pulse monitor output
0: Output frequency (10V = 100% Fmax)
1: Output Current (10V = 100% drive
rated current)
2: DC Bus Voltage
Multi-function Analog Output (10V = 400 VDC [800 VDC])
n066
(Terminals AM & AC) 3: Motor Torque 1 0 5.17
(10V = Motor rated torque)
4: Output Power
(10V = Drive Capacity kW)
5: Output Voltage 10V = (voltage max)
6: Frequency Reference
n067 Analog Monitor Gain (Note 4) 0.00 to 2.00 0.01 1.00
Analog Frequency Reference
n068 -255 to 255 1% 100
Gain (CN2, Voltage Ref Input)
5.32
Analog Frequency Reference
n069 -100 to 100 1% 0
Bias (CN2, Voltage Ref Input)
A1-3
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
A1-4
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
0: Detection Disabled
1: Detect only at set frequency;
operation continues
2: Detect only at set frequency;
n096 Overtorque Detection (OL3) coast to stop 1 0
3: Detect during all frequency conditions;
operation continues
4: Detect during all frequency conditions;
coast to stop 5.20
Overtorque Detection 0: Detected by output torque
1 0
n097 Selection (OL3) 1: Detected by output current
Overtorque Detection
n098 30 to 200 1 (%) 160
Level (OL3)
Overtorque Detection
n099 0.1 to 10.0 0.1 (sec) 0.1
Delay Time (OL3)
Up/Down Hold 0: Disabled
n100 1 0 5.10
Memory 1: Enabled
Speed Search
n101 0.0 to 10.0 0.1 (sec) 2 5.18
Deceleration Time
Speed Search Operation
n102 0 to 200% 1 (%) 150 5.18
Level
Torque Compensation Gain
n103 0.0 to 2.5 0.1 1.0
(Note 4)
Torque Compensation
n104 0.0 to 25.5 0.1 (sec) (Note 2) 5.26
Time Constant
Torque Compensation 0.1 (W) or
n105 0.0 to 6550 (Note 1)
Iron Loss 1 (W)
n106 Motor Rated Slip (Note 4) 0.0 to 20.0 0.1 (Hz) (Note 1) 2.2, 5.22
Motor Line-to-line
n107 0.000 to 65.50 0.001 (ohm) (Note 1)
Resistance
Motor Leakage 0.01 (mH)
n108 0.00 to 655.0 (Note 1)
Inductance (Note 1) or 0.1 (mH)
Torque Compensation
n109 0 to 250 1 (%) 150 5.26
Limit
n110 Motor No-load Current 0 to 99 1 (%) (Note 1) 2.2
n111 Slip Compensation Gain (Note 4) 0.0 to 2.5 0.1 (Note 2)
Slip Compensation Primary
n112 0.0 to 25.5 0.1 (sec) (Note 2)
Delay Time 5.22
Slip Compensation Selection 0: Disabled
n113 1 0
During Regeneration 1: Enabled
0: Disabled
Stall Prevention Above Base (level is based on setting of n094)
n115 1 0
Speed During Run 1: Enabled
(level at Fmax is n094 x 0.4)
5.23
0: Follows acc/dec #1 (n019, n020)
or acc/dec #2 (n021, n022)
Stall Prevention During Run,
n116 Note: Multi-Function input selectable 1 0
Accel/Decel Time Select
1: Follows acc/dec #2 (n021, n022)
always
0: Undertorque detection disabled
1: Detected during constant speed running.
Operation continues after detection
2: Detected during constant speed running.
n117 Undertorque Detection 1 0
Operation stops during detection
Select (UL3)
3: Detected during all frequency conditions.
Operation continues
4: Detected during all frequency conditions.
5.34
coast to stop
0 to 200%
Undertorque Detection Inverter rated current = 100%; if n097 = 0
n118 1(%) 0
Level (UL3) (detection by torque); motor rated torque
becomes 100%
Undertorque Detection
n119 0.1 to 10.0 0.1 (sec) 0.1
Time (UL3)
n120 Frequency Reference 9 (Note 4) 0.00
n121 Frequency Reference 10 (Note 4) 0.01 (Hz) 0.00
n122 Frequency Reference 11 (Note 4) (< 100 Hz) 0.00
n123 Frequency Reference 12 (Note 4) 0.00 to 400.00 or 0.00 5.11
n124 Frequency Reference 13 (Note 4) 0.1 (Hz) 0.00
n125 Frequency Reference 14 (Note 4) (>= 100 Hz) 0.00
n126 Frequency Reference 15 (Note 4) 0.00
n127 Frequency Reference 16 (Note 4) 0.00
A1-5
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
0: PID control disabled
1: D = Feed Forward
2: D = Feedback
3: Reference + PID (D = Feed Forward)
4: Reference + PID (D = Feedback) 1 0
n128 PID Control Selection 5: Inverse PID - D = Feed Forward
6: Inverse PID - D = Feedback
7: Inverse PID - Reference + PID
(D = Feed Forward)
8: Inverse PID - Reference + PID
(D = Feedback)
n129 PID Feedback Gain (Note 4) 0.00 to 10.00 0.01 1.00
n130 PID Proportional Gain (Note 4) 0.00 to 25.00 0.1 1.0
n131 PID Integral Time (Note 4) 0.00 to 360.00 0.1 s 1.0 5.28
n132 PID Derivative Time (Note 4) 0.00 to 2.50 0.01 0.00
n133 PID Offset Adjustment (Note 4) -100 to 100 1% 0
n134 Integral Value Limit (Note 4) -100 to 100 1% 100
n135 PID Output Lag Filter Time (Note 4) 0.0 to 10.0 0.1 s 0.0
0: Disabled
Feedback Loss
n136 1: Enabled - Alarm (operation continues) 1 0
Detection Selection ( ) 2: Enabled Fault (coast to stop)
Feedback Loss
n137 0 to 100 1% 0
Detection Level
Feedback Loss
n138 0.0 to 25.5 0.1 s 1.0
Detection Time
Energy Saving Selection 0: Energy saving disabled
(Note 2) 1: Energy saving enabled
n139 1 0
(Energy Saving) Note: Energy saving becomes enabled by
V/f control mode
Energy Saving Gain
n140 0.00 to 6550 0.1 or 1 (Note 1)
K2 (Energy Saving)
Energy Saving Voltage
0 to 120 1% 50
n141 Lower Limit at 60 Hz
(Energy Saving)
Energy Saving Voltage
0 to 25 1% 12
n142 Lower Limit at 6 Hz
5.31
(Energy Saving)
Time of Average kW 1 1
n143 1 to 200
(Energy Saving) (x 24 ms) (24 ms)
Voltage Limit of Tuning
n144 1 to 100 1% 0
(Energy Saving)
Step Voltage of Tuning to
n145
100% Output Voltage 0.1 to 10.0 0.1% 0.5
(Energy Saving)
Step Voltage of Tuning to
n146
5% Output Voltage 0.1 to 10.0 0.1% 0.2
(Energy Saving)
3072
n149 Pulse Train Input Scaling 100 to 3300 1 (x 10 Hz) 5.11
(30,720 Hz)
Output Frequency Monitor:
0: 1440 Hz / Max. output frequency
1: 1f output
6: 6f output
12: 12f output
24: 24f output 0, 1, 6, 12,
Pulse Monitor Output 36: 36f output 24, 36, 40,
n150 0 5.17
Frequency Selection Frequency Reference Monitor: 41, 42, 43,
40: 1440Hz / Max. output frequency 44, 45
41: Frequency reference * 1
42: Frequency reference * 6
43: Frequency reference * 12
44: Frequency reference * 24
45: Frequency reference * 36
0: Fault - Coast to stop
1: Fault - Ramp to stop (n020)
Modbus Time Out
n151 2: Fault - Ramp to stop (n022) 1 0 5.14
Detection
3: Alarm - operation continues
4: Disabled
A1-6
Table A1-1. Drive Parameters - Continued
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
0: 0.1 Hz
Modbus Frequency 1: 0.01 Hz
n152 1 0
Reference Unit2: 30000/100%
3: 0.1 %
n153 Modbus Slave Address 0 to 32 1 0
0: 2400 bps
1: 4800 bps 5.14
n154 Modbus Baud Rate 1 2
2: 9600 bps
3: 19200 bps
0: even parity
n155 Modbus Parity Selection 1: odd parity 1 2
2: no parity
n156 Modbus Send Waiting Time 10 to 65 1 (msec) 10
0: RTS control enabled
n157 Modbus RTS control 1: RTS control disabled 1 0
(RS-422A 1 to 1 communication)
n158 Motor Code 0 to 70 1 (Note 1)
Energy Saving Voltage
n159
Upper Limit At 60 Hz 0 to 120 1% 120
(Energy Saving)
Energy Saving Voltage
n160
Upper Limit At 6 Hz 0 to 25 1% 16
(Energy Saving) 5.31
Power Supply Detection
n161 0 to 100 1% 10
Hold Width (Energy Saving)
Power Supply Detection 1 5
n162 0 to 255
Filter Time Constant (x 4 ms) (20 ms)
n163 PID Output Gain 0.0 to 25.0 0.1 1.0
0: Terminal FR (Voltage 0 - 10V)
1: Terminal FR (Current 4 - 20mA)
2: Terminal FR (Current 0 - 20mA)
3: Multi-Function Analog Input
n164 PID Feedback Selection 1 0 5.28
(Voltage 0 - 10V)
4: Multi-Function Analog Input
(Current 4 - 20mA)
5: Pulse input
Input Phase Loss
n166 0 to 100 (%) 1% 0
Detection Level
Input Phase Loss
n167 0 to 255 (sec) 1 sec 0
Detection Time
Output Phase Loss
n168 0 to 100 (%) 1% 0
Detection Level
Output Phase Loss
n169 0.0 to 2.0 (sec) 0.1 sec 0
Detection Time
n173 DC Injection P Gain 1 to 999 1 (0.001) 83 (0.083)
25
n174 DC Injection I Time 1 to 250 1 (4ms)
(100ms)
0: Disabled
n175 Reduce Carrier
1: Carrier Frequency reduced to 2.5kHz 1 0 5.5
at low speed selection
when Fout <= 5Hz & Iout >= 110%
rdy : READY status rdy
rEd: READ executes rEd
Digital Operator Parameter Cpy: COPY executes Cpy
n176 rdy 5.29
Copy Function Selection vFy: VERIFY executes vFy
vA: Inverter capacity display vA
Sno: Software No. displaySno
Digital Operator
n177 0: Read disabled
Parameter copy 1 0 5.29
1: Read allowed
Access Selection
n178 Fault History (Note 3) N/A N/A 6.2
n179 Software Number (Note 3) N/A N/A 4.4
A1-7