0% found this document useful (0 votes)
5 views1 page

Ups Panel

The document outlines specifications for electrical components including cables, MCCBs, and panels, emphasizing that only written dimensions should be followed and discrepancies reported to the site engineer. It details various electrical setups including HVAC panels, UPS panels, and capacitor banks, along with their respective ratings and configurations. The document is part of a project for the Department of Roads in Lalitpur, Nepal, and includes engineering and design details for electrical distribution systems.

Uploaded by

Gokul Mainali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views1 page

Ups Panel

The document outlines specifications for electrical components including cables, MCCBs, and panels, emphasizing that only written dimensions should be followed and discrepancies reported to the site engineer. It details various electrical setups including HVAC panels, UPS panels, and capacitor banks, along with their respective ratings and configurations. The document is part of a project for the Department of Roads in Lalitpur, Nepal, and includes engineering and design details for electrical distribution systems.

Uploaded by

Gokul Mainali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Note:-

1. Only written dimensions shall be


followed, drawings shall not be
measured.
2. Any discrepancy if found shall be
reported to the site engineer.

2x3.5x240 sq.mm. Cu XLPE Cable from ATS PANEL

600 A MCCB, with O/L, S/C, E/F microcontroller based relay


50 kA

Am, Vm, Hz Meter+RYB 1000A TPNE COPPER BUSBAR

160A TP MCCB 160A TP MCCB 160A TP MCCB 160A TP MCCB 40A TP MCCB 40A TP MCCB 50A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB
25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA

HVAC PANEL 1 HVAC PANEL 2 HVAC PANEL 3 PLANT ROOM LIFT 1 LIFT 2 DB-LVL1/1 PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB PDB
PANEL

MAIN ELECTRICAL PANEL

3.5X120 sq.mm. CU XLPE cable from Main Electric Panel


3.5x120 sq.mm. CU XLPE Cable from UPS

160A TP MCCB
25 kA
160 A TP MCCB Incomer from Transformer Incomer from DG

25 kA
600 A, 4 Pole MCCB, 50 kA
with O/L, S/C, E/F Motorized Interlocking 600 A, 4 Pole MCCB, 50 kA
with O/L, S/C, E/F
Microcontroller Relay M M
Microcontroller Relay
400V,50Hz,3Ø,4WIRE,1250A,CU
200A TPNE COPPER BUS BUS
Digital Am, Vm, Hz Meter+RYB

Am, Vm, Hz Meter+RYB 200A TPNE COPPER BUSBAR

4X10 sq.mm. Cu UA 4X10 sq.mm. Cu UA 4X10 sq.mm. Cu UA 4X10 sq.mm. Cu UA 4X10 sq.mm. Cu UA 4X10 sq.mm. Cu UA
600 A, 4 Pole MCCB, 50 kA
M with O/L, S/C, E/F
Microcontroller Relay

40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 40A TP MCCB 25A TP MCCB
36 kA 36 kA 36 kA 36 kA 36 kA 36 kA 36 kA
32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB
25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA
Outgoing Feeder

60A Contactor with Phase


Failure & reversal protection
60A Contactor with Phase
Failure & reversal protection
60A Contactor with Phase
Failure & reversal protection
60A Contactor with Phase
Failure & reversal protection
60A Contactor with Phase
Failure & reversal protection
60A Contactor with Phase
Failure & reversal protection 600A ATS PANEL

EDB EDB EDB EDB EDB EDB EDB EDB EDB EDB EDB VRF-ODU VRF-ODU VRF-ODU VRF-ODU VRF-ODU VRF-ODU SPARE

UPS PANEL FREE STANDING WATER PROOF OUTDOOR TYPE AC PANEL

3.5X300 sq.mm. AL XLPE cable from Main LT Panel 4X25 sq.mm. copper cable Unarmoured

400 A, 4 Pole MCCB, 50 kA


with O/L, S/C & Thermal
Magnetic Relay
50A TP MCCB
25 kA

Auto Power Factor Correction (APFCR) 500A TPNE COPPER BUS


RYB 60 A TPNE COPPER BUS
Client-
Digital Multifunction Meter (VAF)

Department of roads, Chakupat, Lalitpur


60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA 60 A TP MCCB, 36 kA
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay
with O/L, S/C & Thermal
Magnetic Relay 6A 6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 6A 6A 6A 6A 6A Project-
TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty TP Capacitor Duty
DETAIL ENGINEERING SURVEY, DESIGN &
Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR Contactor 25 kVAR
ESTIMATION OF DEPARTMENT OF ROADS
CENTRAL BUILDING WITH SUPERVISION AT
MINBHAWAN KATHMANDU.
HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP HEAVY DUTY MPP
R-PHASE Y-PHASE B-PHASE 3 PHASE AC CIRCUIT
CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V CAPACITOR BANK @400V
Consultant-
200 kVAR CAPACITOR PANEL DB-LVL1/1
A-NOT/ITECO /HOMELAND JV

4X16 sq.mm. copper cable Unarmoured 4X10 sq.mm. copper cable Unarmoured
Sheet Title-
Single Line Distribution Diagrams
40A TP MCCB 32A TP MCCB
25 kA 25 kA
Electrical Engineer-
RYB 60 A TPNE COPPER BUS RYB 60 A TPNE COPPER BUS Er.Sangit Lal Nakarmi [nec-133 (ele.)'a']
Checked By-

6A 6A 6A 6A 16A 16A 16A 16A 16A 16A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A 16A 16A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A 16A 16A 16A 16A 6A
6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 16A 16A 16A 16A 6A
Recommended By-

Approved By-
SP

R-PHASE Y-PHASE B-PHASE R-PHASE Y-PHASE B-PHASE


DRG. NO PROJ.NO.
SCALE

TYPICAL POWER DBS (PDB) TYPICAL UPSDBS (EDB)


NTS REVISION SUFFIX

DATE REMARKS SHEET NO.


JULY 2018

DRAWN BY