ROUTINE Page 1 of 15

TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Customer
CENTRAL POWER CORPORATION
Contract: 2107-KFW 3.2 -G02 -46 -CPC-
Customer reference TOJI Country
Project:Efficient Power Grids in Small and
Medium Sized cities - Phase 2
Reference Project
Ref: TOJI-CNTHB-202107126
502863466

Breaker type Serial number


LTB145D1/B-3P 1361557131-001

Mechanism type Serial number


BLK222 1361557131-001-A1

Standard Test completed


IEC62271-100 10/26/2021

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Quality Department

........................................................... Date: 10/26/2021


xzl

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Rated data
Rated filling pressure for operation: 0.50 MPa(abs)

Check of rating plates Approved: xzl

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361557131-001-A1
Closing coil 1 211 - -
Opening coil 1 209 - -
Opening coil 2 211 - -
Antipumping relay 1 31300 - -
Extra relay 1 30200 - -
Density blocking relay 1 30400 - -
Density blocking relay 2 30000 - -
Heater anticondense 672 - -
Heater total 230 - -

All resistances checked Approved xzl


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Check of Approved
Wiring acc. To circuit diagram xzl
Local/remote operation xzl
Blocking relays xzl
Extra relays xzl
On-line-motor starter does not trip for 10 consecutive operations xzl
Auxiliary contacts xzl
Thermostat settings xzl
Counter xzl
All adjustments and paint marking xzl

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0 - -
Closing spring charge ° 123.0 - -
Trip spring setting mm 50.0 - -

Approved: xzl

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 10.7 - -
Motor current A 6.1 - -

Approved: xzl

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 99 - -
Trip coil 1 VDC 88 - -
Trip coil 2 VDC 88 - -

Approved: xzl

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: xzl
1 second 50 Hz 2.0 kV,motor Approved: -
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
A µOhm 35
B µOhm 33
C µOhm 34
Approved: xzl

Power frequency test


60 seconds 50 Hz breaking unit 275 kV Approved: xzl
60 seconds 50 Hz to earth: 275 / kV Approved: xzl

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: xzl

Tightness test on each pole Approved: xzl

OPERATING TEST

Test assumptions
Technical provision: -
Fill pressure: 0.50 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 187 187 154 154
5 Close and Open Max 242 242 242 242
5 Close and Open Nom 220 220 220 220
5 Close-Open Nom 220 220 220 220
5 Open-0.3s-Close Nom 220 220 220 220

Operating test
At least 25 operations as above Approved: xzl
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 27.7 27.8 28.3 110.8 4.8 3.5 9.4 2.0 4.4 -11.1
Open 6 Min. - 1 24.2 24.3 24.2 110.9 5.1 -0.1 0.4 14.0 -5.9 8.5
Close 15 Max. 1 - 26.6 26.7 27.2 110.7 4.9 3.5 9.5 2.1 4.4 -11.0
Open 16 Max. - 1 22.0 22.3 22.2 110.9 5.0 0.2 0.4 14.1 -5.8 8.7
Close 25 Nom. 1 - 27.0 27.1 27.6 110.8 4.8 3.5 9.4 2.1 4.5 -11.1
Open 26 Nom. - 1 22.3 22.6 22.3 110.9 5.0 0.0 0.3 14.1 -5.8 8.8
Open 40 Nom. - 2 22.4 22.7 22.3 110.9 5.1 -0.1 0.4 14.2 -5.8 8.8

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 32.9 33.9 33.0 4.3 -11.2
O-C 37 Nom. 1 1 254.8 254.4 255.2 -5.8 8.7
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Close Min. Operation No 5

120

110

A1
100
B1
C1
90
1a

80 1b

70
mm

60

50

40

30

20

10

T1
0
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
187 VDC 187 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.7 (0.0 - 40.0)
B1 27.8 (0.0 - 40.0)
C1 28.3 (0.0 - 40.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 32.1 4.4
1b 16.6 -11.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 4.8 (4.6 - 5.0)
Travel speed 2 m/s 3.5 (3.1 - 3.9)
Contact Stroke mm 110.8 (109.5 - 111.7)
OverTravel mm 9.4 (6.6 - 11.0)
Rebounce mm 2.0
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Open Min. Operation No 6

T1
110

100

A1
90
B1
C1
80
1a
1b
70

60
mm

50

40

30

20

10

0
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
187 VDC - 154 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 24.2 (19.0 - 25.0)
B1 24.3 (19.0 - 25.0)
C1 24.2 (19.0 - 25.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 18.3 -5.9
1b 32.7 8.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 5.1 (5.0 - 5.2)
Contact Stroke mm 110.9 (109.5 - 111.7)
OverTravel mm -0.1
Rebounce mm 0.4
Damping time ms 14.0 (13.5 - 100.0)
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Close Max. Operation No 15

120

110

A1
100
B1
C1
90
1a

80 1b

70
mm

60

50

40

30

20

10

0 T1
1.0
0.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
242 VDC 242 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 26.6 (0.0 - 40.0)
B1 26.7 (0.0 - 40.0)
C1 27.2 (0.0 - 40.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 31.0 4.4
1b 15.6 -11.0
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 4.9 (4.6 - 5.0)
Travel speed 2 m/s 3.5 (3.1 - 3.9)
Contact Stroke mm 110.7 (109.5 - 111.7)
OverTravel mm 9.5 (6.6 - 11.0)
Rebounce mm 2.1
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Open Max. Operation No 16

T1
110

100

A1
90
B1
C1
80
1a
1b
70

60
mm

50

40

30

20

10

0
1.0
0.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
242 VDC - 242 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 22.0 (19.0 - 25.0)
B1 22.3 (19.0 - 25.0)
C1 22.2 (19.0 - 25.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.2 -5.8
1b 30.7 8.7
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 5.0 (5.0 - 5.2)
Contact Stroke mm 110.9 (109.5 - 111.7)
OverTravel mm 0.2
Rebounce mm 0.4
Damping time ms 14.1 (13.5 - 100.0)
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Close Nom. Operation No 25

120

110

A1
100
B1
C1
90
1a

80 1b

70
mm

60

50

40

30

20

10

T1
0
1.0
0.5
A

Ic1
0
-0.5
0 20 40 60 80 100 120 140
ms

Operation data
Motor Close coil 1 Trip coil -
220 VDC 220 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.0 (0.0 - 40.0)
B1 27.1 (0.0 - 40.0)
C1 27.6 (0.0 - 40.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 31.5 4.5
1b 15.9 -11.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 4.8 (4.6 - 5.0)
Travel speed 2 m/s 3.5 (3.1 - 3.9)
Contact Stroke mm 110.8 (109.5 - 111.7)
OverTravel mm 9.4 (6.6 - 11.0)
Rebounce mm 2.1
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Open Nom. Operation No 26

T1
110

100

A1
90
B1
C1
80
1a
1b
70

60
mm

50

40

30

20

10

0
1.0
0.5
A

Ic1
0
-0.5
0 20 40 60 80 100 120 140
ms

Operation data
Motor Close coil - Trip coil 1
220 VDC - 220 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 22.3 (19.0 - 25.0)
B1 22.6 (19.0 - 25.0)
C1 22.3 (19.0 - 25.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.5 -5.8
1b 31.1 8.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 5.0 (5.0 - 5.2)
Contact Stroke mm 110.9 (109.5 - 111.7)
OverTravel mm 0.0
Rebounce mm 0.3
Damping time ms 14.1 (13.5 - 100.0)
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Close-Open Nom. Operation No 31

120

110

100 A1
B1
90 C1
1a
80 1b

70
mm

60

50

40

30

20

10

T1
0
1.0
0.5
A

Ic1
0
-0.5
0 20 40 60 80 100 120 140 160 180 200 220 240
ms

Operation data
Motor Close coil 1 Trip coil 1
220 VDC 220 VDC 220 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.1 (0.0 - 40.0) 32.9 (0.0 - 42.0)
B1 27.1 (0.0 - 40.0) 33.9 (0.0 - 42.0)
C1 27.6 (0.0 - 40.0) 33.0 (0.0 - 42.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 31.4 24.7 4.3
1b 15.9 53.9 -11.2
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Open-0.3s-Close Nom. Operation No 37

120

T1
110

A1
100
B1
C1
90
1a

80 1b

70
mm

60

50

40

30

20

10

0
1.0
0.5
A

Ic1
0
-0.5
0 50 100 150 200 250 300 350 400
ms

Operation data
Motor Close coil 1 Trip coil 1
220 VDC 220 VDC 220 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 22.2 (19.0 - 25.0) 254.8
B1 22.5 (19.0 - 25.0) 254.4
C1 22.2 (19.0 - 25.0) 255.2
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.4 264.9 -5.8
1b 30.9 235.0 8.7
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Main Test sequence Open Nom. Operation No 40

T1
110

100

A1
90
B1
C1
80
1a
1b
70

60
mm

50

40

30

20

10

0
1.0
0.5
A

Ic1
0
-0.5
0 20 40 60 80 100 120 140
ms

Operation data
Motor Close coil - Trip coil 2
220 VDC - 220 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 22.4 (19.0 - 25.0)
B1 22.7 (19.0 - 25.0)
C1 22.3 (19.0 - 25.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.6 -5.8
1b 31.2 8.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 5.1 (5.0 - 5.2)
Contact Stroke mm 110.9 (109.5 - 111.7)
OverTravel mm -0.1
Rebounce mm 0.4
Damping time ms 14.2 (13.5 - 100.0)
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB145D1/B (CSB1-3P) Order No: 502863466
Mechanism: BLK222 Serial No: 1361557131-001

Free Test Spring charge Nom. Mechanism No 1 Operation No 1

12

10

8
A

Im1
0

0 1 2 3 4 5 6 7 8 9 10 11 12
s

Operation data
Motor Close coil 1 Trip coil -
220 VDC 220 VDC -

Spring charge for mechanism 1


Description Unit Result Limits
Charge current A 6.1
Charge time s 10.7

You might also like