• Ask an authorised Daikin dealer to install Daikin products. Do not try to install the product yourself
or get it installed by any unauthorised dealer. Improper installation can result in water or refrigerant
leakage, electrical shock, fire or explosion. Warranty of the product shall be void if not installed by
an authorised Daikin dealer.
• Use only those parts and accessories supplied or specified by Daikin. Ask authorised Daikin dealer
for any repair or component. Warranty of the product / component shall be void if
non-specified spares are used or repaired by a non Daikin dealer.
PRESENTING THE NEW
• Please ensure to install ELCB (Earth Leakage Circuit Breaker) for outdoor units to prevent ground
fault effects.
• Read the user's manual carefully before using the product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
For any enquiry, either call the numbers mentioned below or contact your nearest Daikin dealer.
Heat Pump | Cooling Only
Ahmedabad-Tel: 079-40013100 Kolkata-Tel: 033-40608019/40659544 To know more, give a missed call or SMS:
Bengaluru-Tel: 080-25722336/25722337 Lucknow-Tel: 0522-4309858/59/60 <DAIKIN> to 9210188999
Bhubaneshwar-Tel: 0674-2554677 Ludhiana-Tel: 0161-5077028/29/30 Visit us at: [Link]
Chandigarh-Tel: 0172-4947200/30 Mumbai-Tel: 022-62321666
Chennai-Tel: 044-40807676 Patna-Tel: 0612-2582282 Follow us on:
Cochin-Tel: 0484-4038646 Pune-Tel: 020-25560300 [Link]/daikinindia
Delhi-Tel: 011-43834400/5500 Raipur-Tel: 0771-4911225 [Link]/daikinindia
Ghaziabad-Tel: 0120-4205851 Ranchi-Mob: 7008704566 [Link]/daikinindia
Indore-Tel: 0731-4005864 Secunderabad-Tel: 040-49134283 [Link]/daikin–airconditioning-india-pvt.-ltd.
Jaipur-Tel: 0141-2218903/04/05/06 Vijayawada-Tel: 0866-2952226/24/25 [Link]/user/DaikinACIndia
SALIENT FEATURES 6
SPECIFICATIONS 48
OPTION LIST 72
CONTROL SYSTEMS 76
1
WHAT DAIKIN STANDS FOR
The world leader in air conditioning
We are present in USA, Europe and Russia, The Middle East, Africa,
Asia, Oceania and Middle-South America. We aim to serve our
customers in each of these markets by providing optimal air
conditioning solutions.
Daikin Daikin Daikin Hui Zhou Daikin Daikin Device Daikin Fluoro
Air conditioning Air conditioning Air conditioning Suns (Suzhou) Coating
Central Europe Spain Italy Air conditioning Shanghai
2
Osaka Head Office
Production Site
Tokyo Office
Overseas Affiliate
3
Exploring new R&D frontiers
DEVELOPMENT
Product Development
Group
IT RESEARCH
Solution Product Environment Technology
Development Centre Research Laboratory
4
Environmental Technology Research Laboratory: Intensive
Research on Environmentally Conscious, Energy Saving
Air Conditioning Technology.
Technology & Innovation Centre, Japan: Research & Development Centre, India:
Aiming for new value creation as a core base for Reiterating to its commitment to Indian market,
technology development. Daikin India R&D is dedicated to provide customised
solutions to its customers.
5
SALIENT FEATURES
First launched in Japan in 1982, the Daikin VRV system has been embraced by the world markets for over
three decades. Now, we at Daikin introduce the next generation VRV X system to reinforce our industry
leadership. The system offers an enhanced line-up to meet an ever widening variety of needs, while improving
energy savings, comfort and ease of installation.
The VRV X is the most advanced air conditioning system in the world and is ideal for small and large spaces.
X’ TENDED
X’ CELLENT
X’ TENSIVE RELIABILITY
TECHNOLOGY
RANGE Auto-Optimisation
4D Inverter
Up to 60 HP Refrigerant
System
Charging
6
X’ TENSIVE RANGE UP TO 60 HP
Standard Type
Line-up
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
Cooling Only/
Heat Pump
7
X’ TRA POWER SAVING
Operation period
annual operation period.
of 50% or less for 70% of their
annual operation period.
Hardware
New scroll compressor* technology
•Compressor efficiency*
Compressor efficiency
New compressor
Refrigerant leakage is minimised Conventional compressor
during low-load operation.
Operation loss due to refrigerant
The back pressure control mechanism increases
leakage is reduced by the proprietary the efficiency during low-load operation.
back pressure control mechanism to Load factor
*Graph shown above is for illustration purposes only.
ensure stable low-load operation. For More information
'Scan Me'
8
Energy saving
Coordinated control
The smooth control • Changes in the air-conditioned room temperature during low-load operation*
(which keeps the Conventional air-conditioning method Fully automatic energy-saving
refrigerant control
compressor running) Changes in the room temperature: Large
The power consumption attributed to the Changes in the room temperature:
saves energy and start-stop loss also increases the load. Small wasted power consumption is
Start also minimised.
ensures comfort
Temperature
during low-load Room setting
temperature Turned off by Turned off by Turned off by
operation. the thermostat the thermostat the thermostat
Note:
• For the classification of indoor units (VRT smart control and VRT control), refer to page 20.
• In case system is having both VRT Control and VRT Smart Control types of Indoor units, system will operate under VRT Control.
• If a system has air handling unit or outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.
0
6 HP 8 HP
Cooling operation conditions: Indoor temp, of 27°CDB, 19°CWB and outdoor temp, of 35°CDB.
9
VRT - VARIABLE REFRIGERANT TEMPERATURE
The new VRV X system features VRT technology. VRT automatically adjusts refrigerant temperature to individual
building and climate requirement, thus further improving annual energy efficiency and maintaining comfort.
Typical changes in evaporating temperature and COP depending on changing indoor load
100%
Required capacity changes
C ooling load
Capacity
changes changes according to
to match outdoor temperature.
heat load
25%
High
VRT
temp. / Te(°C)
Automatic control to
adjust temperature
Low
VRT
Energy efficiency is
High
improved without
COP
sacrificing comfort.
Lo w
Without VRT
10
Fine control to match user preference
available through mode selection
Basic mode is selected to maintain optimal comfort.
35 35
30 30
Av. max. temp.
25 25
20 20
Av. min. temp.
15 15
(Typical example) Av. min. temp. (Typical example)
0 0
Mar. J un. Sep. Dec. Mar. Jun. Sep. Dec.
11
X’ CELLENT TECHNOLOGY
Coil
end
Small size coil end using concentrated winding, reduces copper loss(winding resistance).
Improves motor efficiency in low rpm range (improves intermediate efficiency).
Improves performance by increasing heat exchanger area while maintaining the same installation space.
20 HP
3 rows with small pipe design,
increase heat transfer efficiency
12
4D Inverter Technology
Improved reliability by introducing Daikin 3-phase capacitor-less 4D Inverter technology
• Drive technology
Excellent Performance
13
ADVANCE TECHNOLOGY ACHIEVED
Excellent Performance
Comfort
Sound level (dBA)
Lower operation sound 6 HP 8 HP 10 HP 12 HP
Improves heat exchanger efficiency, helps VRV X 56 56 5
57 59
to reduce operation sound.
Quiet night-time operation function
Large airflow, high static pressure and quiet technology.
Outdoor PCB automatically memorises the time when the
Without increasing operation sound, advanced analytic peak outdoor temperature appears. It enables quiet
technologies are utilised to optimise fan design, operation mode after 8 h*1 and returns to normal mode
increase airflow rate and external static pressure. after it keeps this on for 9 h*2.
Night mode
(%)
100
discharge of
swirling airflow,
further reducing 50
0 8 hrs 9 hrs
60
Streamlined scroll fan 57
Operating
sound (dB)
Ease of Maintenance
VRV X series provides a maintenance feature* which allows the shut down of indoor unit without shutting down the whole
VRV system. This feature comes in handy during maintenance period as the remaining indoor units continue to operate.
14
X’ TENDED RELIABILITY
Conventional
1 2 3 4 5
Calculate necessary Recalculate refrigerant Charge refrigerant Regularly check Complete by
refrigerant amount amount from final refrigerant weight on manually closing
from design drawing installation drawing weighing scale valves when proper
weight is reached
15
X’ TENDED RELIABILITY
Simplified commissioning
and after-sales service
Function of information display 7-segment digital display Conventional LED display
by luminous digital tube Figures out
system
VRV X system utilises the 7-segment luminous operation
Displays information by
digital tubes to display system operation system reading light
operation emitting state
information, enabling the operational state to be information of different
directly. diodes, which
visually displayed whilst facilitating simplified
is both
commissioning and after-sales service. inefficient and
fallible.
VRV configurator
• The VRV configurator is an advanced solution that allows Simplified
for easy system configuration and commissioning. commissioning
• Less time is required on the roof configuring the
outdoor unit.
• Multiple system at different sites can be managed in exactly
the same way, thus offering simplified commissioning for
key accounts. Retrieve initial
• Initial setting on the outdoor unit can be easily retrieved. system settings
16
MORE FLEXIBLE SYSTEM DESIGN
Max. 90m*1
1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and
requirements have to be met to allow utilisation of 90 m piping length.
2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased. If the outdoor unit is above the indoor unit,
a dedicated setting on the outdoor unit is required.
Connection ratio
Conditions of VRV indoor unit connection capacity
Connection capacity
at maximum is 200%. Applicable Other VRV indoor
VRV indoor units unit models*1
Connection ratio FXDQ, FXMQ-PB, FXAQ, models
200%
200%
Double outdoor units 160%
Connection ratio = Triple outdoor units 130%
Total capacity index of the indoor units *
1 For the FXFQ25 and FXVQ models, maximum connection ratio is 130% for the entire range of outdoor units.
Capacity index of the outdoor units Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the
indoor units.
*Refer to page 65 for outdoor unit combination details.
17
High external static pressure
VRV X outdoor unit has achieved
high external static pressure up to 78.4 Pa
78.4 Pa, ensuring the efficient heat More options in the
More options in the
opening/angle of louvre
dissipation and stable operation of Outstanding heat dissipation
equipment in either hierarchical or effect in both hierarchical and
intensive arrangement
intensive arrangement.
18
OUTDOOR UNIT LINE-UP
Outdoor Units
• The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but
also bringing the system flexibility to a new level.
• With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Standard Type
32, 34, 36, 38, 40 HP 42, 44, 46, 48, 50, 52 HP 54, 56, 58, 60 HP
Line-up
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
Cooling Only/
Heat Pump
19
INDOOR UNIT LINE-UP
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 7 HP 8 HP 10 HP 16 HP 20 HP
Capacity Index 20 25 32 40 50 63 71 80 100 125 140 170 200 250 400 500
Ceiling Mounted
Cassette Round FXFSQ-ARV16
Flow & Round Flow VRT
with Sensing (Optional) VRT Smart Control
Ceiling Mounted
Cassette VRT FXZQ-AVM
(Compact Multi Flow) VRT Smart Control
Ceiling Mounted
Cassette VRT FXCQ-AVM
(Double Flow)
FXDQ-PDV36
VRT (with drain pump)
VRT Smart Control (700mm width type)
Slim Ceiling
Mounted Duct FXDQ-NDV36
VRT (with drain pump)
VRT Smart Control (900/1,100mm width type)
FXMQ-PAVE/PBV36
VRT
VRT Smart Control
Ceiling Mounted Duct
VRT FXMQ-NVE
Concealed
Floor Standing VRT FXNQ-MAVE
Floor Standing
Duct VRT FXVQ-NY1(6)
VRT
FXBQ-PVE
VRT
Clean Room
Air Conditioner
VRT FXBPQ-PVE
20
At Daikin, we offer a wide range of indoor units, including both VRV and residential models, responding to a
variety of needs of our customers that require air conditioning solutions.
New
FXDQ-PDV36 FXMQ-PBV36
FXMQ-ARV16
FXDQ-NDV36 FXMQ-NVE
FXUQ-AVEB FXHQ-MAVE
This slim and stylish indoor unit Slim body with quiet and
achieves optimum air distribution, wide airflow.
and can be installed without the
need for ceiling cavity.
21
INDOOR UNIT LINE-UP
FXVQ-NY16
(High static pressure type) Concealed Floor Standing
Type
FXNQ-MAVE
Large airflow type for large spaces. Suitable for perimeter zone air
Flexible interior design for each tenant. conditioning.
FXAQ-ARVE6
FXBQ-PVE
FXBPQ-PVE
Stylish flat panel design harmonised Suitable for hospitals and other clean
with your interior décor. spaces.
FXPQ-AVM
New
22
VRV Indoor Units
Ceiling Mounted Cassette Round Flow & Round Flow with Sensing (Optional)
C
B D
Infrared floor sensor
A
The sensor detects the floor temperature and
Detecting the
average temperature
automatically adjusts operation of the indoor
of indoor floor unit to reduce the temperature difference
between the ceiling and the floor.
Ceiling height 2.7m 3.5m 4.0m
Detection range approx. approx. approx.
(diameter)*4 11m 14m 16m
Various sensing functions *4. The infrared floor sensor detects at the floor surface.
When there are no people in a room, the set temperature is shifted automatically.
The system automatically saves energy by detecting whether or not the room is
occupied. The set temperature is shifted automatically if the room is unoccupied.
• Cooling setpoint: 26°C • Shift temperature: 1.0°C
Example
• Shift time:30 min. • Limit cooling temperature:30°C
28 28°C
27 27°C If people do not
26 26°C 26°C return, the air
Setpoint (°C)
*1.
Applicable when sensing panel (BYCQ140EEF6/BYCQ125EEK) is installed.
*5.
These functions are not available when using the group control system.
*6.
User can set these functions with remote controller.
23
INDOOR UNIT LINE-UP
Absent stop time can be selected from 1 to 24 hrs in 1 hr increments with remote controller.
*7.
3OHDVHQRWHWKDWXSRQUHHQWHULQJWKHURRPDLUFRQGLWLRQHUZLOOQRWVZLWFKRQDXWRPDWLFDOO\
• With Auto airflow direction mode, flaps • When human is detected, air direction is
are controlled to deliver optimal airflow set to “Swing (narrow)” to deliver cool air
when the room is unoccupied. to users.
24
Comfort and energy saving preventing over cooling*9
$LUIORZGLUHFWLRQDQGDLUIORZUDWHVKRXOGEHVHWWR´$XWRµ
Area around feet gets too cold because air conditioner The floor temperature, Automatic control using
which is lower than near the temperature near the
continues until the temperature near the ceiling reaches
the ceiling, is detected. person as the room
the set temperature. temperature.
(QHUJ\ The temperature near the person is automatically calculated by detecting the temperature of the
savings IORRU(QHUJ\LVVDYHGEHFDXVHWKHDUHDDURXQGWKHIHHWGRHVQRWJHWWRRFROG
1. Blows horizontally
Individual Airflow
New Direct Airflow Direction Control
25
INDOOR UNIT LINE-UP
Circulation Air Flow *1. Applicable when wired remote controller BRC1E62 is used.
*2. Not applicable when using individual airflow direction control.
Circulation airflow cools the entire room to deliver comfort that never feels cold
During 2-way horizontal flow
Hot
outdoor air
Cool air moves down along Comfort without Cools by airflow blocking
the walls and to every cold air pockets at out hot air near windows
corner of the room. floor level. and walls.
Comfort to the entire room with even temperatures and no cold air pockets at floor level
30.0 Comparison Conditions
4-way cassette (Swing) 29.0
Room size:
28.0
27.0 Width 7.5m x depth 7.5m
26.0 x height 2.6m
25.0 Indoor unit capacity:71 class
24.0
23.0 Outdoor air temperature:35ʝ
22.0 Airflow rate and air direction:
21.0 high / swing
20.0
Full comfort is
provided with no
cold feet.
Cools areas around Cools entire room Cools areas around Cools entire room Note: Results may vary depending on
equipment conditions, room size
walls using using 4-way walls using using 4-way and distance from indoor unit to walls.
2-way horizontal flow swing flow 2-way horizontal flow swing flow
26
Three technologies that achieved circulation airflow
Flow-out is straight, horizontally and strong, so the air travels far and even reaches the wall from which it falls to the floor. This
approach and technology makes circulation airflow possible.
1
1 Use of new wide flaps (Straight)
Compared to conventional models, the new Conventional flap*4 New wide flap
wide flap increases straightness of the airflow,
so coverage is approximately doubled.
Approx.
doubled
Velocity
*5
10%
increase
*5
*[Link] 2 outlets are controlled by changing the flap direction (angle) to suppress airflow volume.
27
INDOOR UNIT LINE-UP
Airflow direction can be Easy setting is possible with a wired remote controller.
individually adjusted for each air
discharge outlet to deliver optimal
air distribution.
There are
identification
marks near
the air outlets.
Position 0 Remote controller
((KWGFCKRĝOVěO BRC1E63 screen
highest position)
When individual airflow is selected, airflow direction can be adjusted to room layout.
Position
Position Position
0 0
For offices The airflow is at the
highest setting (Position 0)
for people who
Swing dislike air blowing
Discussions near Swing is set for directly on them.
a hot window meetings near
quickly heat up. the windows.
Swing
Swing is
selected for
areas near No individual (Auto)
the windows.
Auto is set for people
sitting farthest from
Sitting here is hot The seats here the entrance.
because of the hot air are comfortable
from outside. though…
28
New
Wide variety of decoration panels (Option)
• Designer choice has been given a boost with the increase in number of new types of decoration panels.
New
Designer panel (Option)
FLAT C L E AN ROUND
Decoration
coration Panel Line
Line-up
u (Option)
Standard panel*1 Standard panel*1 Designer panel*1 *1. Sensing function is applicable
when sensing panel is installed.
BYCQ125EAF6
YCQ125EAF6 (Fresh White
White) BYCQ125EAK (Black) BYCQ125EAPF (Fresh White)
New
Auto grille panel (Option)*1
29
INDOOR UNIT LINE-UP
Easy maintenance
There are areas of
uneven temperature.
• Internal hygiene can be easily checked without
removing the whole panel. Simply opening the suction
panel allows the internal drain pan to be checked.
New
New
• 24mm diameter drain outlet
30
Example of airflow patterns
All-round flow is available, as well as 2-way to 4-way flows, so you can choose the most suitable airflow pattern depending
on location or room layout.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing
material (option) must be used to close each unused outlet.
All-round flow is available, as well as 2-way to 4-way flows, so you can choose the most
suitable airflow pattern depending on location or room layout.
• An antibacterial treatment that uses silver ions has been applied to the drain pan,
preventing the growth of slime, mould and bacteria that cause blockages and odours.
(The lifespan of a silver ion cartridge depends on the usage environment, but should be
changed once every two to three years.)
• The air filter has an anti-mould and antibacterial treatment that prevents the growth
of mould generated from dust or moisture that may adhere to the filter.
New
• Control of the airflow rate can be selected from 5-step control and auto.
31
INDOOR UNIT LINE-UP
VRT Smart
Individual airflow direction control: Flexibility to suit every room layout without changing the location of the unit.
32
Ceiling Mounted Cassette (Double Flow) Type
33
INDOOR UNIT LINE-UP
New
FXKQ32AV / FXKQ40AV
FXKQ50AV / FXKQ63AV
This new Indoor unit has been awarded with Good Design Award
34
Installation with Panel Spacers
It has the flexibility to install on several height false ceiling i.e its ceiling height can be minimize with multiple optional by spacers
(25mm each) from 25mm to 75mm
Note- Spacer colour- Dark gray
Further Further
Standard Ceiling Height Reduced by 25mm Reduced by 25mm Reduced by 25mm
175mm (6.88 Inches) 150mm (5.9 Inches) 125mm (4.9 Inches) 100mm (3.9 Inches)
145mm IDU height + 30mm clearance
25
(mm) Item/Images NA NA
App. Model/Qty. 2 2 1 X
Spacer 50
Assembly (mm) Item/Images NA
App. Model/Qty. 3 3 1 1
75
(mm) Item/Images
BKF25CA6 BKF50CA6
75mm Spacer
Detail View
BKF25A6 BKF75SA6
35
INDOOR UNIT LINE-UP
Great for
hotel use
200mm
900mm
200mm
Only 700mm * 1,100mm in width for the FXDQ63ND model.
AIR 240mm
Discharge grille *
Suction grille *
AIR
* To be obtained locally
FXDQ-PD/ND 20/25/32 40 50 63
Sound level
33/31/29 34/32/30 35/33/31 36/34/32 750mm
(HH/H/L)
36
High Static Pressure Ceiling Mounted Duct Type
FXMQ170N/FXMQ200N
FXMQ250N
37
INDOOR UNIT LINE-UP
38
Ceiling Suspended Type
Sophisticated design
Flap neatly closes when
not in use.
3-step.
Quiet operation
Drain pump kit (option) includes a silver ion antibacterial Uses quiet stream fan and other quiet technologies.
agent that assists in preventing the growth of slime, (FXHQ32-100MA)
bacteria, and mould that cause smells and clogging. Sound absorption
member
dBA
Sound level
Indoor unit
H M L
FXHQ32MA 36 ----- 31
FXHQ63MA ----- 34
FXHQ100MA 45 ----- 37
FXHQ125A 46 41 37
FXHQ140A 48 42 37
39
INDOOR UNIT LINE-UP
FXAQ20A / FXAQ25A
FXAQ32A / FXAQ40A
FXAQ50A / FXAQ63A
• Stylish flat panel design creates a graceful harmony that enhances any interior space.
• Flat panel can be cleaned with only the single pass of a cloth across their smooth surface.
• Vertical auto-swing realises efficiency of air distribution. The louvre closes automatically when the unit stops.
40
Floor Standing Type
FXLQ32MA / FXLQ50MA
FXLQ63MA
FXNQ32MA / FXNQ50MA
FXNQ63MA
Refrigerant
• A long-life filter is equipped as a standard piping
accessory.
* Applies also to Floor Standing type
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
(FXLQ-MA).
41
INDOOR UNIT LINE-UP
FXVQ125N / FXVQ200N
FXVQ250N / FXVQ400N
FXVQ500NY16
Air Air
processing airconditioner. conditioning conditioning
*When using the unit as an outdoor-air
processing unit, there are some restrictions.
Outdoor air Outdoor air
introduction introduction
* Air introduced from the outside and circulated air must be mixed in the
air conditioner primary side before introduction into the air conditioner.
42
4-Way Flow Ceiling Suspended Type
FXUQ71A / FXUQ100A
Position 3 Swing
.SJCPGFVCXĝOV
43
VRV INDOOR UNIT
FXBQ40/FXBQ50
FXBQ63/FXBPQ63
Construction work is simple and a ceiling installation is possible. Easy to increase the cleanness and air-conditioning effect.
Features
Dust filtering and air-conditioning can be started immediately. A low flow speed prevents drying of the affected part and the experience of drafts.
Applications: Surgery prep rooms, recovery rooms, nurse stations, etc. Applications: Operating theatres, delivery rooms, etc.
Blow
method
• Somewhat concentrated air conditioning • Total air conditioning with an emphasis
centered directly under the outlet on cleanliness
• Can provide air conditioning in rooms • Maintenance possible from a different
Outlet Air
Separate with irregular shapes unit conditioner room Intake
outlet unit (sourced locally)
model
Applications: CCU*2, sterile rooms, etc. Applications: Premature nurseries, newborn nurseries, ICU*3, etc.
*1. Cleanliness class. A scale expressing the cleanliness of air established by NASA (National Aeronautics and Space Administration). Class 10,000 represents a state of less than 10,000 minute particles of diameter under 0.5 μm per cubic foot.
For comparison, the cleanliness of a typical office is around class 1,000,000.
*2. CCU (Cardiac Care Unit). A ward dedicated to the admission of patients with myocardial infarctions and other heart diseases.
*3. ICU (Intensive Care Unit). A ward for the careful treatment and nursing of patients with serious illnesses, injuries, or recovering from operations.
44
Filtration FXB(P)Q-P
Class 10,000 clean room condition achieved with a
HEPA filter (sold separately)
The low pressure-loss HEPA filter (sold separately) demonstrates superior
dust filtering performance and easily accomplishes an air cleanliness of
class 10,000.
The HEPA filter has a structure • HEPA filter
incorporating a pleated glass fibre filter
medium, making it highly efficient and
suitable for clean rooms, etc.
Installation example (in a medical facility)
*It may not be possible to maintain cleanliness in rooms with low air tightness.
Antibacterial
Suppresses the propagation of bacteria in the duct with a proprietary antibacterial coating.
The filter implements an antibacterial treatment with a new coating, combining a silver-based inorganic antibacterial material
(an organic antibacterial material that is effective against germs) that prevents mould. This enhances the antibacterial properties of the duct.
An antibacterial treatment using a silver-based organic substance reduces mould.
Fan
* Please be aware that antibacterial products suppress the propagation of bacteria but do not have a sterilising
effect. Also, mould may grow in places where dust or soot accumulates.
* A material for which the registered safety was verified by Japanese chemicals and dangerous substances
regulation law
(Act on the Evaluation of Chemical Substances and Regulation of Their Manufacture, etc.) is used for the
antibacterial material.
Outlet panel HEPA filter Sheet steel Intake panel * Periodic maintenance is required (such as cleaning the air filter and washing the inside to the unit).
(punched) drain pan (punched)
(antibacterial treated)
Labour-saving
Filter maintenance unnecessary for about five years
Easy access from underneath unit provides easy maintenance.
The HEPA filter has an exceptionally long life and does not require maintenance
· HEPA filter · Fan · Drip pan inspection
for about five years. Daikin has aimed to reduce maintenance work from a variety
replacement inspection · Pre-filter replacement
of perspectives, including a service access system that eliminates the necessity for
service panels.
*The maintenance period differs significantly according to the cleanliness of the room and hours of air conditioner operation.
Quiet
All models incorporate an industry-leading quiet design, operating at under 41dB.
Operating noise is substantially reduced by employing a proprietary double-structure outlet filter chamber, sound absorbing
insulation and a low pressure-loss HEPA filter. Sound level of all models are under 41dB (38dB during low-fan speed operation).
*Operating noise may be greater than these values in highly reflective locations.
45
VRV INDOOR UNIT
FXPQ25AVM New
Suspended Rested
• Stand installation • Direct installation
(stand sold separately)
46
Adjustable comfort for
Easy relocation/expansion individual users
Only requirement is connection to preinstalled Shut-off Valve Each Spot Air Conditioner can be controlled with a
kit for additional indoor units (Option). dedicated wired remote controller. Individual users
can set the temperature and
airflow volume.
Shut-off Valve kit for additional indoor unit (Option) Moreover, since each unit
can be turned ON and OFF,
it is possible to reduce power
consumption resulting from
unnecessary operation and
to eliminate associated costs.
*3. Please contact your local
sales representative for
details on the Shut-off
Valve kit for additional
indoor units (Option).
The large propeller fan provides a gentle, comfortable breeze and greater wind volume.
Additionally, by installing an optional air discharge adaptor and straightening plate, strong airflow can be achieved that
extends even further.
Comfort for people nearby Standard type Comfort for people far away Long-distance type
Wind velocity distribution map (horizontal section) Wind velocity distribution map (horizontal section)
A gentle breeze Strong airflow
T covers delivers comfort
T
the work area
T T
<Conditions> Cooling operation, high airflow volume, 60 Hz
* Distribution map for direct airflow volume Air discharge adaptor *6. Installation of the optional items "air
(KDF87C28) discharge adaptor (KDF87C28)" and
"straightening plate for air discharge adaptor
TZ Straightening plate for (KPW87A28)" is necessary.
air discharge adaptor
(KPW87A28)
For the heat exchanger cooling pipe, a To minimize condensation, the air duct Air duct / Blowout tube
material with 3 to 6 times*7 the durability and blowout tubes are double Double insulation structure
of standard materials has been selected. insulated. This enables use in kitchens
and other highly humid environment.
The fan and
motor can be
replaced from
Leakage failsafe Simple maintenance the front.
47
SPECIFICATIONS
48
SPECIFICATIONS
MODEL FXFSQ25ARV16 FXFSQ32ARV16 FXFSQ40ARV16 FXFSQ50ARV16 FXFSQ63ARV16 FXFSQ80ARV16 FXFSQ100ARV16 FXFSQ125ARV16 FXFSQ140ARV16
Power supply 1-phase, 220-240V, 50Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 54,600 54,600
Heating capacity
kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 16.0
Casing Galvanised steel plate
m3/min 13/12.5/11.5/11/10 17/13.5/12.5/12/11 23/20.5/19/14.5/11 23.5/21/20/16/13.5 24.5/22/20.5/20/15 33.5/30.5/27/23.5/21 34.5/31.5/28.5/25.5/23 35.5/32.5/29.5/26.5/23
Airflow rate (H/HM/M/ML/L)
cfm 459/441/406/388/353 600/477/441/424/388 812/724/671/512/388 830/742/706/565/477 865/777/724/706/530 1,183/1,077/954/830/742 1218/1112/1006/901/812 1,254/1,148/1,042/936/812
Sound level (H/HM/M/ML/L) dBA 30/29.5/28.5/28/27 35/29.5/29/28/27 38/35/34.5/29.5/27 38/36/35.5/31.5/28 39/37/36/35.5/31 44/41/38/35/33 45/42.5/39.5/37/35 46/43.5/40.5/38/35
Dimensions (H×W×D) mm 256×840×840 298×840×840
Machine weight kg 19 22 25 26
Liquid (Flare) ø 6.4 ø 9.5
Piping
Gas (Flare) mm ø 12.7 ø 15.9
connections Drain VP25 (External Dia, 32/Internal Dia, 25)
Standard Model BYCQ125EAF6 (Fresh White)
panel (Non mm
Dimensions (HxWxD) 50x950x950
sensing)
(White) Weight kg 5.5
Sensing Model BYCQ140EEF6 (Fresh White)
panel Dimensions (HxWxD) mm 50x950x950
(White) Weight kg 5.5
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
Note: When opting Black panel, wireless remote controller model will be BRC7M634K
49
SPECIFICATIONS
50
Ceiling Mounted Cassette Corner Type
MODEL
Fuse
BYKQ63AHW / BYKQ63AHS / BYKQ63AW
White / Silver
41 x 1390 x 595
6.6
51
SPECIFICATIONS
MODEL
6.6
52
Slim Ceiling Mounted Duct Type (700 mm width type)
53
SPECIFICATIONS
54
Ceiling Mounted Duct Type
0.8TR 1.025
1.2
MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PBV36 FXMQ50PBV36
55
SPECIFICATIONS
56
4-way Flow Ceiling Suspended Type
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Sound level (H/L) dBA 35/31 36/31 38/31 39/34 42/37 47/41
57
SPECIFICATIONS
58
Clean Room Type Air Conditioner
*In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build in redundancy with two or more
outdoor units.
MODEL FXPQ25AVM
Power Supply 1 Phase, 50Hz, 220-240 V
Cooling 2800
Capacity (watt)
Heating 3200
Dimension (HXWXD) mm 455X555X470
Casing Galvanised Steel plate
Type Propeller Fan
59
SPECIFICATIONS
Outdoor Units
Combination units – – – – – –
Compressor No. of
compressor 1 1 1 1 1 2
Operation
range
Cooling °CDB 10 ~ 49
Type R410A
Refrigerant
Charge kg 5.9 6.7 6.8 7.4 8.2
60
VRV X (Cooling Only)
Compressor No. of
compressor 2 2 1+1 1+1
Type R410A
Refrigerant
Charge kg 8.4 11.8 6.7+6.8 6.8+6.8
Liquid mm ø 15.9
Piping
connections
Gas mm ø 28.6 ø 34.9
61
SPECIFICATIONS
Outdoor Units
Compressor No. of
1+1 1+2 1+2 1+2 2+2 2+2
compressors
Operation
range Cooling °CDB 10 ~ 49
Type R410A
Refrigerant
Charge kg 6.8+7.4 6.8+8.2 6.8+8.4 7.4+8.4 8.2+8.4 8.4+8.4
62
VRV X (Cooling Only)
(1,657X930X765)+ (1,657X1,240X765)+
(1,657X1,240X765)+ (1,657X930X765)+ (1,657X1,240X765)+
(1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
10 ~ 49
R410A
8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 7.4+7.4+11.8 7.4+8.2+8.4 7.4+8.4+8.4
ø 19.1
ø 41.3
63
SPECIFICATIONS
Outdoor Units
Compressor No. of
compressors 2+2+2
Operation
range Cooling °CDB 10 ~ 49
Type R410A
Refrigerant
Charge kg 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8
Liquid mm ø 19.1
Piping
connections
Gas mm ø 41.3
64
VRV X (Heat Pump)
Combination units – – – – – –
Compressor No. of
1 2
compressors
65
SPECIFICATIONS
Outdoor Units
Compressor No. of
compressors 2 1+1
Liquid mm ø 15.9
Piping
connections
Gas mm ø 28.6 ø 34.9
66
VRV X (Heat Pump)
Compressor
No. of
1+2 2+2
compressors
Type R410A
Refrigerant
Charge kg 7.6+9.1 7.6+9.3 7.6+11.8 9.3+9.3 9.3+11.8
Liquid mm ø 19.1
Piping
connections
Gas mm ø 34.9 ø 41.3
67
SPECIFICATIONS
Outdoor Units
Compressor No. of
compressors 2+2 1+1+2
(1,657X930X765)+
mm (1,657X1,240X765)+
Dimensions (H×W×D) (1,657X930X765)+
(1,657X1,240X765)
(1,657X1,240X765)
Liquid mm ø 19.1
Piping
connections
Gas mm ø 41.3
68
VRV X (Heat Pump)
3 - 100 2 - 100
Ivory white (5Y7.5/1)
Hermetically Sealed Scroll Type
2+2+2
(1,657X1,240X765)+
(1,657X1,240X765)+ (1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)
(1,657X1,240X765)
ø 19.1
ø 41.3
69
OUTDOOR UNIT
COMBINATIONS
& OPTIONS LIST
70
OUTDOOR UNIT COMBINATIONS
VRV X
Note: *1 For multiple connection of 22 HP systems and above, the outdoor unit multi connection piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double
outdoor units, and 130% for triple outdoor units. Refer to page 17 for notes on connection capacity of indoor units.
71
OPTION LIST
4 Fresh air intake kit type 5,6 With T-duct joint KDDP55B160K (Components: KDDP55C160-1, KDDP55B160K2) 8
Note:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate 2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and
may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when more fresh air is necessary.
8. Please order using the names of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
*These panels do not contain the sensing function.
Notes:
1. Option relay wire harness adaptor (BER01A1) is necessary when installing decoration panel (BYFQ60B3W1).
2. Installation box*2 is necessary for each adaptor marked +.
3. Up to 2 adaptors can be fixed for each installation box.
4. Only one installation box can be installed for each indoor unit.
72
Ceiling Mounted Cassette (Double Flow) Type
FXCQ32A
No. Item Type FXCQ25A FXCQ50A FXCQ63A FXCQ80A FXCQ125A
FXCQ40A
73
OPTION LIST
5 Front suction filter Front suction base flange KD-9A140 KD-9A200 KD-9A280 KD-9A400 KD-9A560
6 chamber for high Suction grille KDGF-9A140 KDGF-9A200 KDGF-9A280 KDGF-9A400 KDGF-9A560
7 efficiency filter Replacement Long-life filter *3 KAF-91B140 KAF-91B200 KAF-91B280 KAF-91B400 KAF-91B560
8 filter *2 High efficiency 65% KAF-92B140 KAF-92B200 KAF-92B280 KAF-92B400 KAF-92B560
9 filter 90% KAF-93B140 KAF-93B200 KAF-93B280 KAF-93B400 KAF-93B560
10 Plenum chamber *4 KPCJ140A KPC5J KPC8J KPCJ400A KPC15JA
11 Pulley for plenum chamber *4 KPP8JA KPP9JA KPP10JA —
12 Fresh air intake kit KD106D10 KDFJ906A560
13 Rear suction kit KDFJ905A140 KDFJ905A200 KDFJ905A280 KDFJ905A400 KDFJ905A560
14 Discharge grille for plenum side KD101A10 KD101A20
15 Wood base KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15
16 Vibration isolating frame K-ABSG1406A K-ABSG1407A K-ABSG1408A K-ABSG1409A K-ABSG1410A
*1 A front suction base flange and suction grille are required (option). *2 A filter chamber for high efficiency is required (option).
*3 Different from the filter attached as standard. *4 Use the plenum chamber and pulley for plenum chamber in combination.
74
VRV X
RX(Y)Q6ARY6
RX(Y)Q14ARY6
Optional Accessories RX(Y)Q8ARY6 RX(Y)Q12ARY6
RX(Y)Q16ARY6
RX(Y)Q10ARY6
KHRP26M22H,
Distributive (Max. 4 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H
REFNET header
piping KHRP26M33H (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
(Max. 8 branch)
RX(Y)Q18ARY6
Optional Accessories
RX(Y)Q20ARY6
RX(Y)Q26ARY6 RX(Y)Q34ARY6
RX(Y)Q28ARY6 RX(Y)Q36ARY6
Optional Accessories RX(Y)Q22ARY6 RX(Y)Q24ARY6 RX(Y)Q30ARY6 RX(Y)Q38ARY6
RX(Y)Q32ARY6 RX(Y)Q40ARY6
KHRP26M22H
(Max.4 branch),
KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header
(Max.8 branch), (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Distributive KHRP26M72H
piping (Max.8 branch),
KHRP26A22T,
REFNET joint KHRP26M33T, KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26M72T,
RX(Y)Q46ARY6
RX(Y)Q48ARY6
RX(Y)Q50ARY6
RX(Y)Q42ARY6 RX(Y)Q52ARY6
Optional Accessories
RX(Y)Q44ARY6 RX(Y)Q54ARY6
RX(Y)Q56ARY6
RX(Y)Q58ARY6
RX(Y)Q60ARY6
75
CONTROL
SYSTEMS
76
OFFICE | HOME | HOTEL
Reiri for Office is the ideal building management solution for all sizes of commercial
[nbe]bg`l%^li^\bZeer_hklfZeemhf^]bnf&lbs^][nbe]bg`l%k^`Zk]e^llh_eh\Zmbhg'Mabl
smart building solution provides affordable and scalable building control and energy
management, allowing users greater control and automation of building utilities such as
Zbk&\hg]bmbhgbg`Zg]eb`ambg`%Zg]mhfhgbmhkZg]fZgZ`^^g^k`ri^k_hkfZg\^Zg]
indoor air quality.
Expanded Features
Reiri for Home is the complete smart home solution with seamless integration
capabilities, allowing users to control and monitor all smart home devices
conveniently from just a single mobile app. From security and safety
enhancements to indoor air quality and energy management, Reiri for Home is the
ideal home automation system for every homeowner.
R i i for
Reiri f Home
H Reiri for Home
DCPH01 Lite Version
DCPH02
K^bkb_hkAhm^e^__^\mbo^erlZo^l^g^k`rZg]\hlmpabe^ikbhkbmbsbg``n^lml\hf_hkmZg]
satisfaction. With this smart hotel solution, energy consumption is optimised without
\hfikhfblbg`hgma^`n^lmlbg&khhf\hf_hkm'Ahm^efZgZ`^klZg]lmZ__Zk^ZelhZ[e^
to conveniently monitor the status and manage the settings of every room.
77
CONNECTABLE
Various types of equipment in a building
can be controlled by a single controller.
Smart Devices
Connect to a wide variety of smart devices,
ranging from IP cameras to locks and sensors,
and access all of them from just one Reiri app.
78
BENEFITS OF REIRI
Energy Saving
By automating air-conditioning and
lighting controls through available functions such
as scheduling and interlocking, energy consumption
is greatly minimized while maximising
comfort and efficiency.
Integration Capabilities
Reiri is able to integrate and connect to various sensors
and smart devices, thus making it the ideal all-in-one
platform to monitor and control every room's indoor
environment, such as temperature, humidity, indoor air
quality and illuminance.
Other
12%
Office
Devices HVAC
16%
48%
Lighting
24%
79
CONTROL SYSTEMS
Clear display
• Dot matrix display
A combination of fine dots enables various
icons. Large text display is easy to see.
• Backlight display
Backlight display helps operating in dark rooms.
Simple operation
BRC1E63 &
BRC1F61 (Only for FXEQ Series) • Large buttons and arrow keys
Large buttons and arrow keys enable easy
operation. Basic setting such as fan speed
and temperature can be intuitively operated.
For other settings, just select the function
from the menu list.
• Guide on display
The display gives an explanation of each setting for easy operation.
Energy saving
80
Convenience
• Weekly schedule
• Five actions per day can be scheduled for each day of the week.
• The holiday function will disable schedule timer for the days that have been set as holiday.
• Three independent schedules can be set (e.g. summer, winter, mid-season).
Comfort
• Individual airflow direction (*1)
Airflow direction of each of the four air outlets can be controlled individually.
(Positions 0 to 4, Swing, and No individual settings are selectable).
1 2
Outlet mark
1
3
3 4
81
CONTROL SYSTEMS
A complete redesigned
controller focused to
enhance user experience For More information
'Scan Me'
Easy setting via Bluetooth App with smartphone (for Installer/Facility Manager)
Keep hotel room comfortable
• Improved setback function by setting the lower
temperature limit in cooling mode.
82
Stylish remote controller (Option)
Intuitive design
• By using pictograms, the user- friendly interface enables convenient and easy operation.
Compact size
• Measuring only 85 x 85 mm, the new remote controller is extremely compact and
complements any interior design.
• The same operation mode and setting as with wired remote controllers are possible.
*Individual airflow direction, auto air-flow rate and sensor control can be set only via
wired remote controller BRC1E62. They cannot be set via other remote controllers.
• A compact signal receiver unit (separate type) to be mounted into wall or ceiling is
included.
• A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Signal receiver unit Compact Multi Flow, Double Flow) type, Ceiling Suspended Type and Wall Mounted
(Installed type)
type is mounted into the Indoor unit.
*Wireless remote controller and signal receiver unit are sold as a set.
*Refer to page 90 for the name of each model. Signal receiver unit
(Installed type)
83
CONTROL SYSTEMS
Unified on/off
controller
(DCS301BA61).
Connection of
up to 8 units Independent
possible. and centralised
Address setting of central control can be control of Heat
performed from the remote controller. Reclaim
Ventilator is
possible.
Connectable number
of centralised control
equipment
Central remote Group control of up to 16 units is possible
controller 2 units (group control via automatic address setting)
Unified remote
controller 8 units
Forced
shut-down
input Central control Wiring
adaptor kit Adaptor for Outdoor air
(DTA107A55) other air- processing
conditioners unit can be
(DTA103A51) connected.
Central remote
controller Interface adaptor for Sky Air
(DCS302CA61) Series
(DTA112BA51)
Up to 2 unit
connectable
84
Residential remote controller (Optional)
DCS301BA61
85
CONTROL SYSTEMS
DCM601A51
Pump Fan
86
For Energy Saving & Comfort
The 10.4" LCD touch screen is easy to use with three different screen views to include the floor plan layout view, icon
view and list view and menus for system configurations.
It is also easy to use with standardised remote Web Access from your PC.
It can manage a total of 650 management points consisting of up to 512 Daikin indoor unit groups
(up to 1024 indoor units) along with building equipment control / monitoring with Digital Inputs / Output
(Di/Dio), Analog Inputs / Output (Ai/Ao) and Pulse input (Pi) optional devices.
Schedule the operation time for each application. Define the set point range that users can change.
With Remote controller
This heat is killing me.
It can not
Why? be set
Common area: below this Oh! Cool.
Meeting room: 9:00-17:00
No schedule
22°C
Turn the unit OFF, if a user didn’t. Reset set point regularly.
Change to 20°C
Stop Start
87
CONTROL SYSTEMS
[Overview of control]
• Up to 5 DALI modules can be connected to a (Each group corresponds to a management point • DALI BAS simplifies wiring and setting work by
single BACnet® controller. of the Intelligent Touch Manager.) daisy chain wiring and automatic address setting.
• Up to 64 DALI LED drivers (64 addresses) can • Up to 16 scenes can be set to a single DALI
be connected to a single DALI module. module.
• 64 DALI addresses can be freely assigned to up • Up to 12 sensors (occupancy, illuminance) can be
to 16 groups using a single DALI module. connected to a single DALI module.
OFF OFF
88
Tenant Management (PPD Option)
With the PPD function, power consumption can be calculated for each indoor unit (Optional)
The energy consumption is proportionally
calculated for each indoor unit. The data can be Operational information
of individual indoor units
used for energy management and calculation of air Tenant A
conditioning usage fees for respective tenants. HIGH
Operation duration
Room temperature
Expansion valve
Operational information of individual indoor units opening ratio
Tenant B
are monitored, based on distribution of power LOW
consumption of outdoor units. Automatic calculation of
me om
total power consumption of
h l fr
ter
individual indoor units
Daikin’s PPD keeps track of power distribution for
kW igna
the se s
Tenant C
each indoor unit. It performs air conditioning
l
MEDIUM
Pu
Tenant B
billing calculations quickly and automatically. Tenant A
Tenant C
It is easy to output PPD data.
PPD data is output in CSV format to a PC or USB memory device
kWh meter Total power consumption
and can be freely processed and managed.
User’s PC
calculation and issuance of VRV electricity bills.
[ Main functions ]
• Register tenants.
• Set the electricity unit price for 5 time zones.
• Calculate power consumption and electricity charge for each tenant.
• Show aggregation results in the specified period for each tenant.
• Output the results (Printout and CSV file).
89
CONTROL SYSTEMS
System Structure
Up to 512 groups
Intelligent Touch Manager System Overview (1024 indoor units)
Web Access
via Internet
Web Access
via LAN Up to 7 Adaptors
BACnet® / IP
WAGO I / O system
BACnet® controller DALI module
750-831 753-647
DALI BUS
DALI BUS
DALI BUS
90
Air Conditioning Network Service System
Preventive Maintenance
The Intelligent Touch Manager can be connected to Daikin’s own Air Conditioning Network Service System for remote monitoring
and verification of operation status for VRV system. By its ability to predict malfunctions, this service provides customers with
additional peace of mind.
Enhanced convenience with link to the Air Conditioning Network Service System
The Intelligent Touch Manager connects seamlessly to Daikin’s 24-hour Air Conditioning Network Service System.
ACC centre
Personnel at the centre monitor the
occurrence of malfunctions and track their
Trouble
cause via the Internet.
Advance malfunction warnings help prevent
the sudden occurrence of problems later.
Even malfunctions difficult to identify
Air Conditioning Network Service System*
can be monitored remotely.
Repair *Because of restrictions
Allows dispatching of Enable prompt repairs as in applicable areas and
service engineers without service engineers know the release times, please consult
cause of the problem a Daikin representative
a call from customers. separately for details.
beforehand.
Other Home
VRV Indoor unit Appliances
Home Automation
Use of Modbus protocol Master Controller Television
RS485 Mod
Modbus
dbus Protocol
Wire length is up to 500m Electric curtains
91
CONTROL SYSTEMS
The high speed transmission of DIII-NET enables more advanced control of the VRV system, providing you
with enhanced comfort.
(DCS601C51)
(DCM601B51)
Via internet
Home Automation
Master Controller
Home Automation
Interface Adaptor
(DTA116A51)
BMS
(Obtain locally)
Wiring adaptor
for electrical appendices
(KRP2A61/62/53)
92
Integrated Building Monitoring System
DIII-NET Line
The DIII-NET system provides for:
BACnet®/Ethernet or LONWORKS®
Network Communication Line • Close control and monitoring by integrating a wide variety of air conditioners in the
entire building.
Contact Signal Line • Saving the in-building cabling using non-polar, two-wire cables. Easier wiring work with
tremendously fewer wiring errors.
RS485 Modbus Line • Additional set-ups readily up and running. An extendable cabling up to 2 km in total.
• Different control equipment flexibly joined in the system for hierarchical risk
WAGO Connection diversification.
• Daikin's total heat exchangers and other devices all under integral control.
VRV
VRV
Caution:
Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.
93
CONTROL SYSTEMS
Option List
Operation Control System Optional Accessories
10 External control adaptor for outdoor unit ÌDTA104A61 DTA104A61 ÌDTA104A62 ÌDTA104A61 DTA104A61 DTA104A62
11 Adaptor for multi tenant ÌDTA114A61 — — ÌDTA114A61 —
12 External control adaptor for cooling / heating — KRP6A1
13 Remote controller with key — KRCB37-1
Function List Round Flow with Sensing Type For Control Model
FXFSQ-A
Remote controller
Wired BRC1E63 Wireless Heat Pump BRC7M530W
(for grid ceiling panel)
Remote controller
Wireless —
Remote controller
Dual sensors *1 Wireless Heat Pump BRC7E530W
(for decoration panel)
Direct airflow *1
Sensing sensor low mode *1 Navigation remote controller BRC1E63
Notes: Multi tenant unit (24V free type) for indoor ÌBRP114A61
1. Installation box is necessary for each adaptor marked Ì.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
7. Individual airflow direction, auto airflow rate and sensing sensor control can be set only via
wired remote controller BRC1E63. Cannot be set via other remote controllers.
8. Since the control panel is equipped as standerd, use the option for 2 remote control system.
9. When using BRC1E63, be sure to remove the control panel and since BRC1E63 cannot be
stored inside the indoor unit, please place it separately.
94
6\VWHP&RQÀJXUDWLRQ
Type
No. Item Model No. Function
Note 2 • Up to 16 groups of indoor units (128 units) can be easily controlled using the
1 Residential central remote controller DCS303A51 large LCD panel. ON/OFF, temperature settings and scheduling can be
controlled individually for indoor units.
2 Central remote controller DCS302CA61 • Up to 64 groups of indoor units (128 units) can be connected, and ON/OFF,
temperature setting and monitoring can be accomplished individually or
2-1 Electrical box with earth terminal (3 blocks) KJB311AA simultaneously. Connectable up to 2 controllers in one system.
3 Unified ON/OFF controller DCS301BA61 • Up to 16 groups of indoor units (128 units) can be turned, ON/OFF individually or
3-1 Electrical box with earth terminal (2 blocks) KJB212AA simultaneously, and operation and malfunction can be displayed. Can be used in
3-2 Noise filter (for electromagnetic interface use only) KEK26-1A combination with up to 8 controllers.
• Programmed time weekly schedule can be controlled by unified control for up to
4 Schedule timer DST301BA61
64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.
5-room centralised For CDXS, FDK(X)S, Note 3 • Up to 5 indoor units can be controlled. This is a low cost system which can only
5 controller for residential
FTK(X)S KRC72A control ON/OFF.
indoor units
Interface adaptor for For CDXS, FDK(X)S, • Adaptors required to connect products other than those of the VRV System to the
6 KRP928BB2S
residential indoor units FTK(X)S high-speed DIII-NET communication system adopted for the VRV System.
Interface adaptor for For FCQ-B, FFQ-B,
7 ÌDTA112BA51
SkyAir-series FHQ-BV, FBQ-B
* To use any of the above optional controllers, an appropriate adaptor must be
8 Central control adaptor kit For UAT(Y)-K(A), FD-K ÌDTA107A55
installed on the product unit to be controlled.
9 Wiring adaptor for other air-conditioner ÌDTA103A51
• Use of the Modbus protocol enables the connection of the VRV system
5 Home Automation Interface Adaptor DTA116A51
with a variety of home automation systems from other manufacturers.
Notes:
*1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
®
*2. LonWorks is a trademark of Echelon Corporation registered in the United States and other countries.
®
95
AIR HANDLING UNIT
Capacity range : 6 - 60 HP
System overview
96
HEADER PACK
Advantage
• Installation time saving: Up to 1/3 of conventional method.
• Easy to Install: Hanging points available.
• Safety: Consists of faring method, no brazing required*.
• Space saving: Head pack to Indoor unit soft drawn pipe, top side of
refrigerant pipe doesn’t need space for brazing torch movement.
Header Pack • Quality Installation: Elimination of difficult process, enhancing quality
installation.
Quick, flare
nut connection
No need of
brazing
Easy,
soft copper
tube piping
97
DAIKIN GAS TIGHT JOINT (DGT)
• Double edged claw catches the pipe to form tight mechanical sealing.
• 3 types of connectors suitable for most pipe sizes and applications.
• Unique mechanical and resin sealing prevent gas leak completely.
• It is durable up to 4 times (17.2MPa) of max. operating pressure.
98
Daikin Gas Tight Joint Line up
(Matching for various piping sizes)
Dimension (mm)
Figure Model Name Weight /pc (g)
ND AF L
SDGTB06 φ 6.4 19.0 50.4 43
SDGTB09 φ 9.5 22.2 55 79
SDGTB12 φ 12.7 23.8 59 113
SDGTB15 φ 15.9 29.7 74 210
SDGTB19 φ 19.1 35.0 76.8 273
SDGTB22 φ 22.2 38.0 83.4 292
SDGTB28 φ 22.6 45.0 88 515
BDGTA34 φ 34.9 51.1 101.5 686
BDGTA41 φ 41.3 58.3 103.5 881
99
AIR TREATMENT EQUIPMENT LINE-UP
Components
of Indoor Air Quality
Ventilation *TMKFKĂECěKON
Air Processing*
A recent trend rapidly gaining popularity is the need for air treatment along with air
conditioning. Our Outdoor Air Processing Unit can combine fresh air treatment and air
conditioning, supplied from a single system. It adjusts the temperature of air from outdoors using
a fixed discharge temperature control. Along with Outdoor Air Processing Units, we also offer
Heat Reclaim Ventilator systems. The Heat Reclaim Ventilator VAM-GJ series units in particular
have been praised for their compactness, energy conservation and extensive operation range
of outdoor temperatures. This series provides higher enthalpy efficiency due to the greatly
enhanced performance of the thin film element. Furthermore, improved external static pressure
offers more flexibility for installation. The Heat Reclaim Ventilator VKM-GAM series units,
equipped with a DX-coil and a humidifier, provide further advanced features, such as
temperature adjustment to suit conditions indoors and to prevent cold air from blowing on
people directly during heating operation. The series also realises significant energy savings by
exercising heat recovery.
100
Outdoor Air Heat Reclaim Ventilator
Processing Unit VKM-GAM Type VKM-GA Type VAM-GJ Type
Humidifier — Fitted — —
High Efficiency Filter Option Option Option
Ventilation System Air supply only Air supply & air exhaust Air supply & air exhaust
Power Supply 220-240 V, 50 Hz 220-240 V, 50 Hz 220-240 V/220 V, 50 Hz
250 m3/h
101
AIR TREATMENT EQUIPMENT LINE-UP
Lineup
Model Name FXMQ125NFRV16 FXMQ200NFRV16 FXMQ250NFRV16
Capacity Index 125 200 250
Air Outdoor
Conditioning Air Supply
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
• When outdoor-air processing units are connected, the total connection capacity index must be 50% to 100% of the capacity index of the outdoor units.
• When outdoor air processing units and standard indoor units are connected, the total connection capacity index of the outdoor air processing units must not exceed 30% of the
capacity index of the outdoor units.
• Outdoor air processing units can be used without indoor units.
102
Standard Specifications
Indoor unit
Type Ceiling Mounted Duct Type
Model FXMQ125NFRV16 FXMQ200NFRV16 FXMQ250NFRV16
Power supply 1-phase 220- 240 V (also required for indoor units), 50 Hz
kcal/h 12,000 19,300 24,100
Cooling capacity *1 Btu/h 47,800 76,400 95,500
kW 14.0 22.4 28.0
kcal/h 7,700 12,000 15,000
Heating capacity *1 Btu/h 30,400 47,400 59,400
kW 8.9 13.9 17.4
103
AIR TREATMENT EQUIPMENT LINE-UP
Line-up
With DX Coil & Humidifier Type
Model Name VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
Capacity Index 31.25 50 62.5
For More information
'Scan Me' With DX Coil Type
Model Name VKM50GAV1 VKM80GAV1 VKM100GAV1
Capacity Index 31.25 50 62.5
VKM80GAV1
Humidifier
The line-up includes models with a humidifier, in
response to diversifying customer requirements.
(VKM50/80/100GAMV1 only)
DX-coil
The Heat Reclaim Ventilator features DX-coil that
contributes to the prevention of cold airflow hitting
people directly during heating operation, due to the
after-cool, after-heat operations done beforehand.
Efficient outdoor air introduction is possible
The Heat Reclaim Ventilator (VKM series) series introduces fresh High static pressure
outdoor air with minimum heat losses, while a wide variety of High external static pressure means enhanced
features responds to customer requirements. design flexibility.
Outdoor Air
Return
Air Air
Air Conditioning Air Supply
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
• When the Heat Reclaim Ventilator VKM series units are connected, the total connection capacity index must be 50% to 130% of the capacity index of the outdoor units.
104
A compact unit packed with our cutting-edge technology
Exhaust Fan
Heat Exchanger Elements
EA Damper Motor
(Exhaust air to outdoors) Damper
SA
Temperature Integrally-
and humidity formed liner
RA
26°C RA
50% RH
*GCěKNICNFJTMKFKĂECěKONPROEGSS
Structure of
VKM series Outdoor Indoor
Humidification Humidification: 5.4kg/h (VKM100GAMV1)
Heating
Natural Evaporating
by DX-Coil Pan Type Humidifier
The outdoor air is heated from 16.6°C to 36.5°C with DX-coil,
Heat exchange Natural Evaporating Pan Type Humidifier is passed and
humidification capacity is improved.
16.6°C 36.5°C
Exhaust Air Supply Air
To the Outdoor 10.4°C
To the Indoor 24.5°C
'ėGEěOHEOOĚKNI 40
with minimal cooling capacity through the use of outdoor air. Heating and cooling
+
Humidifying Indoor temperature during cooling
'ėGEěOH
Indoor temperature during heating JTMKFKĂECěKON
20
105
AIR TREATMENT EQUIPMENT LINE-UP
Specifications
MODEL VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 VKM50GAV1 VKM80GAV1 VKM100GAV1
Refrigerant R-410A
Power Supply 1-phase, 220–240 V, 50 Hz
Airflow rate m3/h 500 750 950 500 750 950
Ultra-high
Static pressure Pa 160 140 110 180 170 150
Airflow Rate & Static Airflow rate m3/h 500 750 950 500 750 950
Pressure (Note 7) High
Static pressure Pa 120 90 70 150 120 100
Airflow rate m3/h 440 640 820 440 640 820
Low
Static pressure Pa 100 70 60 110 80 70
Notes: 1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. When 11. Power consumption and efficiency depend on the above value of airflow rate.
calculating the capacity as indoor units, use the following figures: VKM50GAMV1/GV1: 3.5 kW, 12. Temperature exchange efficiency is the mean value for Cooling and Heating. Efficiency is measured under the following
VKM80GAMV1/GV1: 5.6 kW, VKM100GAMV1/GV1: 7.0 kW. condition: Ratio of rated external static pressure outdoor to indoor is kept constant at 7 to 1.
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB. 13. In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the system goes into
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB. defrost operation. During defrost operation, the fans of the unit continue driving (factory setting). The purpose of this is to
4. Humidifying capacity is based on the following conditions: Indoor temperature: 20°C DB, 15°C WB, Outdoor maintain the amount of ventilation and humidifying.
temperature: 7°C DB, 6°C WB. 14. When connecting with a VRV system heat recovery outdoor unit and bringing the RA (exhaust gas intake) of this unit
5. The operating sound measured at the point 1.5 m below the centre of the unit is converted to that measured in an directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit (master unit), and use group-linked
anechoic chambar built in accordance with the JIS C 1502 conditions. The actual operating sound varies operation. (See the Engineering Data for details).
depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally 15. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor
higher than this value. unit, perform group-linked operation, and make the direct duct connection settings from the remote controller. (Mode No.
For operation in a quiet room, it is required to take measures to lower the sound. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the indoor unit.
For details, refer to the Engineering Data. Depending on the fan strength and static pressure, the unit might back up.
6. The noise level at the air discharge port is about 8–11 dBA or higher than the unit’s operating sound. Feed clean water (city water, tap water or equivalent). Dirty water may clog the valve or cause dirt deposits in the water
For operation in a quiet room, it is required to take measures to lower the sound. container, resulting in poor humidifier performance. (Never use any cooling tower water and heating-purpose water.)
7. Airflow rate can be changed over to Low mode or High mode. Also, if the supply water is hard water, use a water softener because of short life.
8. In case of holding full water in humidifier. * Life of humidifying element is about 3 years (4,000 hours) under the supply water conditions of hardness: 150 mg/l. (Life
of humidifying element is about 1 year (1,500 hours) under the supply water conditions of hardness: 400 mg/l.)
9. OA: fresh air from outdoor. RA: return air from room.
Annual operating hours: 10 hours/day x 26 days/month x 5 months = 1,300 hours.
10. Specifications, design and information here are subject to change without notice.
106
Heat Reclaim Ventilator - VAM Series
Good quality air for every day
Room temperature
1 increases due to
unconditioned outside air.
EA
(Exhaust air to outdoors)
Total heat exchange ventilation RA
OA (Return air
This unit recovers heat energy lost through ventilation and (Fresh air from from room)
curbs room temperature changes caused by ventilation, thereby outdoors)
conserving energy and reducing the load on the air conditioning system.
Indoor Outdoor SA
(Supply air
to room)
EA
(Exhaust air to Sheet structure
outdoors) Exhaust air
High-humidity air
SA Molecule of water
(Supply air Miscellaneous gas
CO2 molecule, etc.
to room)
material
OA
RA (Fresh air from Supply air Low-humidity air
(Return air outdoors)
from room)
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.
107
AIR TREATMENT EQUIPMENT LINE-UP
Airflow Control
EA SA kitchen
Positive Negative
pressure(+) pressure(-)
Dust
Fresh Up Operation
By positive pressure in the room, the entering of dirty outside air, odors By negative pressure in the room, contaminated air and moisture from the
and moisture when opening and closing of doorway is prevented. room is prevented from leaking into other areas.
EA SA EA SA
Dust Negative
Positive pressure(-)
pressure(+) hallway
Doorway
108
Ventilation volume control with CO2 sensor interlocking
&TRKNIKNERGCSGKN%12ĚGUGĚKNěJGROOMUGNěKĚCěKONCKRUOĚTMGVKĚĚDGKNERGCSGFěOJCUGJKIJGRCKRGWEJCNIGKN
ORFGRěORGFTEGěJG%12 level in room.
*TMCNOEETPCNEXKSRGĝGEěGFCS%12 concentration
Gradual decrease
image: [Link]
in CO2 as
800
ventilation is
550ppm turned on
Experimental data: CO 2 concentration in the conference room.
600
Closed conference rooms often tend to have stagnant air
Number of people Number of people Number of people flow. In long meeting duration or meeting with full occupancy,
400 in the room in the room in the room the concentration of CO 2 increases due to the exhaled CO 2
from human and causes decrease in mind concentration. In
200
4 Person 13 Person 4 Person order to achieve effective ventilation in short period,
mechanical ventilation and natural ventilation should be
combined to replace the air.
0
9 10 11 12 13 14 15 16 17 18 Image is for illustrative purpose.
Times of Day
Air Conditioner
Heat Reclaim Ventilator
109
AIR TREATMENT EQUIPMENT LINE-UP
#KREONFKěKONGRCNFUGNěKĚCěKONSXSěGMECNDGKNěGRĚOELGFěOPROUKFGGUGNIRGCěGREOMHORěCNFGNGRIXSCUKNI
The system can be interlocked with Daikin air conditioners to provide energy saving ventilation solution for various situation.
Ve n t i l a t i o n Air conditioning
Interlocking control
+NSKěTCěKONOHNOJTMCNOEETPCNEXFGěGEěKONěJGOPGRCěKONKSěTRNGFOė
When the "Sensing sensor" installed on the air conditioner detects no occupancy in the room, the ventilation system and air
conditioner system is turned off automatically to reduce energy wastage.
Pre-Cooling/Pre-Heating Control
6JGOPGRCěKONOHUGNěKĚCěKONSXSěGMKSFGĚCXGFFTRKNIěJKSMOFG
During first start up of the air conditioner, the start up operation of ventilation system is delayed in order to reduce additional heat
load from outside air. This will reduce power consumption for the air conditioner as well.
8:00 9:00
Operation ON Operation ON
110
Auto-Ventilation Mode Changeover Switching
Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating status of the
air conditioner.
When the cooling operation is required in winter, use of heat recovery ventilation is not efficient because the outdoor air
temperature is normally lower than that of the indoor. Thus, the proper use of ventilation mode enhances the heating / cooling
efficiency.
In addition, by installing a humidity sensor (optional), automatic switching by heat (energy) or discomfort index is possible
which further improves energy efficiency and comfort.
*Supply air
(Intermediate season)
*atThetheairsame
cannot be supplied
temperature
as the outdoor air because
Outdoor air temperature sensor it is partly heat-exchanged.
111
AIR TREATMENT EQUIPMENT LINE-UP
Night time free cooling operation is an energy-conserving function that works at night when air conditioners are off. By
ventilating rooms containing office equipment that raises the room temperature, night time free cooling operation reduce
the cooling load when air conditioners are turned on in the morning. It also alleviates feelings of discomfort in the morning
caused by heat accumulated during the night.
The indoor accumulated heat is discharged at night.
- When connected to air conditioners, operation of This reduces the air conditioning load the next day, thereby increasing
heat reclaim ventilator is controlled according to the efficiency.
set temperature, outside air temperature and room
temperature.
- When using only ventilation unit, operation of heat
reclaim ventilator is controlled according to the set
temperature on remote controller.
- Night time free cooling operation is possible during
air conditioners linked operation by centralized
control. Heat is discharged. The load is small so the temperature is
rapidly reduced to a comfortable level.
- Night time free cooling operation is set to “off” in the *Interlocked operation with an air conditioner.
factory settings, so if there is a need to turn on, please
contact Daikin dealer.
112
Application Example
8GNěKĚCěKONRGĚCěGFPOKNěSěODGěCLGNKNěONOěGFTRKNIFGSKINKNISěCIG
Restaurant
Regardless of the industry,
Problem t he c a us e of d i ffi c ul t y i n
op e ni ng d oor s m a y b e d ue
• The entrance door is difficult to open.
t o i ns uffi c i e nt a i r s up p l y
3 2
Countermeasure plan
Problem
Countermeasure plan
113
AIR TREATMENT EQUIPMENT LINE-UP
Function Detail
A ir co nditioner interlock Interlo ck Heat Reclaim Ventilato r with air conditioner by one
remo te co ntroller.
Ventilation mode Switch the ventilation mode (A utomatic, Heat exchange, Bypass). -
Ventilation airflow rate When using CO 2 sensor, ventilation volume can be changed.
Fresh up indicatio n Indicates that fresh up operatio n is being carried o ut. - -
Night time free cooling indication Show the night purge icon when is set. - -
24 hours ventilating indication Show the icon when 24hrs operation is set. - -
Option List:
Type Item VAM250HVE VAM500HVE VAM650HVE
Silencer – KDDM24B100
Additional
Function
KDDDM24B100 KDDDM24B100 x 2
Additional
Silencer
function
DCS303A51* 1
controlling
114
Air Treatment Equipment
Airflow rate control with CO2 sensor
The CO2 sensor controls airflow rate so that it best matches the changes of CO2 level in the room. This prevents
energy losses from over-ventilation while maintaining indoor air quality with optional CO2 sensor.
Airflow rate up
9 10 11 12 13 14 15 16 17 18 19 20 21 Hours
Sales Sales
Morning Lunch Overtime
personnel leave personnel
meetings Time work
office return
Air conditioner
Many people increase CO2 level: Fewer people decrease CO2 level:
Airflow rate up Airflow rate down
temperature is temperature is
lower than indoor
lower than indoor
higher lower
115
TECHNICAL SPECIFICATIONS
Unit
* Values for electrical current, power consumption, and efficiency are at the above above-stated airflow.
* Exchange efficiencies are values based on performance codes and air conditions that comply with JIS B8628:2017.
* Temperature exchange efficiency and enthalpy exchange efficiency vary according to the ratio of supply air and exhaust air and air conditions.
* Operation sound is an anechoic chamber conversion that complies with JISB8628:2017. When measured under actual installation conditions, the operation sound is usually greater due to
ambient noise and reverberation.
116
Unit
117
VRV X Catalogue India_A4
• Ask an authorised Daikin dealer to install Daikin products. Do not try to install the product yourself
or get it installed by any unauthorised dealer. Improper installation can result in water or refrigerant
leakage, electrical shock, fire or explosion. Warranty of the product shall be void if not installed by
an authorised Daikin dealer.
• Use only those parts and accessories supplied or specified by Daikin. Ask authorised Daikin dealer
for any repair or component. Warranty of the product / component shall be void if
non-specified spares are used or repaired by a non Daikin dealer.
PRESENTING THE NEW
• Please ensure to install ELCB (Earth Leakage Circuit Breaker) for outdoor units to prevent ground
fault effects.
• Read the user's manual carefully before using the product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
For any enquiry, either call the numbers mentioned below or contact your nearest Daikin dealer.
Heat Pump | Cooling Only
Ahmedabad-Tel: 079-40013100 Kolkata-Tel: 033-40608019/40659544 To know more, give a missed call or SMS:
Bengaluru-Tel: 080-25722336/25722337 Lucknow-Tel: 0522-4309858/59/60 <DAIKIN> to 9210188999
Bhubaneshwar-Tel: 0674-2554677 Ludhiana-Tel: 0161-5077028/29/30 Visit us at: [Link]
Chandigarh-Tel: 0172-4947200/30 Mumbai-Tel: 022-62321666
Chennai-Tel: 044-40807676 Patna-Tel: 0612-2582282 Follow us on:
Cochin-Tel: 0484-4038646 Pune-Tel: 020-25560300 [Link]/daikinindia
Delhi-Tel: 011-43834400/5500 Raipur-Tel: 0771-4911225 [Link]/daikinindia
Ghaziabad-Tel: 0120-4205851 Ranchi-Mob: 7008704566 [Link]/daikinindia
Indore-Tel: 0731-4005864 Secunderabad-Tel: 040-49134283 [Link]/daikin–airconditioning-india-pvt.-ltd.
Jaipur-Tel: 0141-2218903/04/05/06 Vijayawada-Tel: 0866-2952226/24/25 [Link]/user/DaikinACIndia