Daikin VRV X Air Conditioning System

The document outlines Daikin's advanced air conditioning solutions, specifically the VRV X system, which features innovative technologies for energy efficiency and comfort. It emphasizes the importance of authorized installation and the use of specified parts to maintain warranty and safety. Additionally, it highlights Daikin's commitment to quality and environmental management through ISO certifications.

Uploaded by

PANKIJ KUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views120 pages

Daikin VRV X Air Conditioning System

The document outlines Daikin's advanced air conditioning solutions, specifically the VRV X system, which features innovative technologies for energy efficiency and comfort. It emphasizes the importance of authorized installation and the use of specified parts to maintain warranty and safety. Additionally, it highlights Daikin's commitment to quality and environmental management through ISO certifications.

Uploaded by

PANKIJ KUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

VRV X Catalogue India_A4

WORLD’S LEADING AIR CONDITIONING


Note: COMPANY FROM JAPAN

• Ask an authorised Daikin dealer to install Daikin products. Do not try to install the product yourself
or get it installed by any unauthorised dealer. Improper installation can result in water or refrigerant
leakage, electrical shock, fire or explosion. Warranty of the product shall be void if not installed by
an authorised Daikin dealer.

• Use only those parts and accessories supplied or specified by Daikin. Ask authorised Daikin dealer
for any repair or component. Warranty of the product / component shall be void if
non-specified spares are used or repaired by a non Daikin dealer.
PRESENTING THE NEW
• Please ensure to install ELCB (Earth Leakage Circuit Breaker) for outdoor units to prevent ground
fault effects.

• Read the user's manual carefully before using the product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.

For any enquiry, either call the numbers mentioned below or contact your nearest Daikin dealer.
Heat Pump | Cooling Only

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

About ISO 9001 About ISO 14001


ISO 9001 is a plant certification system ISO 14001 is the standard defined by the
defined by the International Organization for International Organization for Standardization
Standardization (ISO) relating to quality (ISO) relating to environmental management
assurance. ISO 9001 certification covers systems. Our group has been acknowledged by
quality assurance aspects related to the an internationally accredited compliance
“design, development, manufacture, organisation as having an appropriate programme
installation, and supplementary service” of of environmental protection procedures and
products manufactured at the plant. activities to meet the requirements of ISO 14001.
JMI-0107 JQA-1452

CUSTOMER CONTACT CENTRE:


011-40319300, 1860-180-3900
customerservice@[Link]

Ahmedabad-Tel: 079-40013100 Kolkata-Tel: 033-40608019/40659544 To know more, give a missed call or SMS:
Bengaluru-Tel: 080-25722336/25722337 Lucknow-Tel: 0522-4309858/59/60 <DAIKIN> to 9210188999
Bhubaneshwar-Tel: 0674-2554677 Ludhiana-Tel: 0161-5077028/29/30 Visit us at: [Link]
Chandigarh-Tel: 0172-4947200/30 Mumbai-Tel: 022-62321666
Chennai-Tel: 044-40807676 Patna-Tel: 0612-2582282 Follow us on:
Cochin-Tel: 0484-4038646 Pune-Tel: 020-25560300 [Link]/daikinindia
Delhi-Tel: 011-43834400/5500 Raipur-Tel: 0771-4911225 [Link]/daikinindia
Ghaziabad-Tel: 0120-4205851 Ranchi-Mob: 7008704566 [Link]/daikinindia
Indore-Tel: 0731-4005864 Secunderabad-Tel: 040-49134283 [Link]/daikin–airconditioning-india-pvt.-ltd.
Jaipur-Tel: 0141-2218903/04/05/06 Vijayawada-Tel: 0866-2952226/24/25 [Link]/user/DaikinACIndia

For more product information:


DAIPL-2017/23-VRVX-1A

For More information X’ TENSIVE X’ TRA X’ CELLENT X’ TENDED


'Scan Me' RANGE POWER SAVINGS TECHNOLOGY RELIABILITY
• The specifications, designs, and information in this brochure are subject to change without notice.
INDEX
WHAT DAIKIN STANDS FOR 2

SALIENT FEATURES 6

OUTDOOR UNIT LINE-UP 19

INDOOR UNIT LINE-UP 20

SPECIFICATIONS 48

OUTDOOR UNIT COMBINATIONS 70

OPTION LIST 72

CONTROL SYSTEMS 76

AIR TREATMENT EQUIPMENT LINE-UP 100


Equipped with advanced technology, that results
in high energy efficiency. This technological
innovation gives end user the advantage of better
comfort and works further towards creating a
sustainable environment.

1
WHAT DAIKIN STANDS FOR
The world leader in air conditioning

At Daikin, we are a leading innovator and provider of advanced,


high-quality air conditioning solutions for residential, commercial and
industrial applications.

As world's leading air conditioning company, we are committed to


deliver air conditioning solutions that enhance the quality of life all
around the world.

Established in 1924, Daikin Industries Ltd., is a diverse multinational


company, active in air conditioning, chemicals and oil hydraulics.
With headquarters at Osaka, Japan, our Daikin family has more than
84,870 members, working across 100+ production bases and 316
consolidated subsidiaries worldwide.

As the world's sole manufacturer that develops a long line of


products from refrigerants to air conditioners, we advocate
comfortable living on the strength of advanced technologies.

We are present in USA, Europe and Russia, The Middle East, Africa,
Asia, Oceania and Middle-South America. We aim to serve our
customers in each of these markets by providing optimal air
conditioning solutions.

EUROPE / MIDDLE EAST / AFRICA CHINA

Daikin Daikin Daikin Daikin Daikin Xi’an Daikin


Europe N.V. Air conditioning Air conditioning (China) Investment Air conditioning Qing’an
France Germany Shanghai Compressor

Daikin Daikin Daikin Hui Zhou Daikin Daikin Device Daikin Fluoro
Air conditioning Air conditioning Air conditioning Suns (Suzhou) Coating
Central Europe Spain Italy Air conditioning Shanghai

Daikin Daikin Industries Daikin Chemical Daikin


Air conditioning Czech Republic France Fluorochemicals
UK China

2
Osaka Head Office

Production Site

Tokyo Office

Overseas Affiliate

ASIA / OCEANIA NORTH AMERICA/CENTRAL


& SOUTH AMERICA

Daikin Daikin Compressor Daikin


Air conditioning Industries Air conditioning
India Singapore Daikin America Daikin AC
America

Daikin Australia Daikin Industries Daikin Industries


Thailand Head Office Japan
(Inside Umeda Daikin Holding
Centre Building) USA

3
Exploring new R&D frontiers

At Daikin, we are creating value through innovative


technologies. As a global industry front-runner, we are
carrying out research and development on the world’s
most advanced air conditioning technology.

Our strong R&D edge has helped us create futuristic


products that enrich people’s lives. As symbolised by the
VRV, Daikin has put forth a multitude of products and
varied technology that have always been and continue to
be, at the forefront of innovation.

To be able to offer such products and services that delight


and astound our customers, we have constructed an
advanced R&D architecture.

Formation of a three-division system of research, IT and


development to support our superior products.

To create more advanced functions and new value, we


have instituted specialised R&D divisions: the
‘Environmental Technology Research Laboratory’ and the
‘Solution Product Development Centre’.

In combination with the product development group,


each of the three divisions work in close co-operation to
precisely ascertain the customers’ needs and to enable
commercialisation of products, incorporating advanced
technology that take the lead over our competitors.

DEVELOPMENT
Product Development
Group

IT RESEARCH
Solution Product Environment Technology
Development Centre Research Laboratory

4
Environmental Technology Research Laboratory: Intensive
Research on Environmentally Conscious, Energy Saving
Air Conditioning Technology.

Accelerating globalisation of our air conditioning business


and varied needs of customers across geographies are
increasing our research challenges. We have established a
research laboratory devoted to the two fields of ‘air
conditioning’ and ‘the environment’. With our mission to
promote energy savings in air conditioners, we are
engaged in R&D on cutting-edge technologies. Our aim is
to create futuristic products from fundamental research on
motor inverters and other areas to support individual
product development.

Going forward, we will elevate our technology edge to


achieve further business expansion globally.

The Solutions Product Development Centre: Integrating


Air conditioners with IT.

Keeping in mind the changes in business brought in by


the computerisation and networking of society, we have
integrated IT into our airconditioners, including
communication technology, software technology and
digital control. We are initiating R&D that will offer new
system services–a comfortable environment with
superior energy savings by networking air conditioners.
Such a scenario will enable them to exchange
information with service centres.

Technology & Innovation Centre, Japan: Research & Development Centre, India:

Aiming for new value creation as a core base for Reiterating to its commitment to Indian market,
technology development. Daikin India R&D is dedicated to provide customised
solutions to its customers.

5
SALIENT FEATURES

World’s most advanced


air conditioning system with
innovative VRT technology.

First launched in Japan in 1982, the Daikin VRV system has been embraced by the world markets for over
three decades. Now, we at Daikin introduce the next generation VRV X system to reinforce our industry
leadership. The system offers an enhanced line-up to meet an ever widening variety of needs, while improving
energy savings, comfort and ease of installation.

The VRV X is the most advanced air conditioning system in the world and is ideal for small and large spaces.

Energy saving technology for VRV X System

VRT-Variable Refrigerant Temperature in Indoor Unit (IDU)


X’ TRA and Outdoor Unit (ODU)
POWER SAVINGS The new VRV X system now features VRT technology in IDU &
ODU. VRT automatically adjusts refrigerant temperature to
Next Generation
Compressor & individual building load and climate requirement, thus further
VRT Smart Control improving annual energy efficiency and maintaining comfort.
With this technology, running costs are reduced.

X’ TENDED
X’ CELLENT
X’ TENSIVE RELIABILITY
TECHNOLOGY
RANGE Auto-Optimisation
4D Inverter
Up to 60 HP Refrigerant
System
Charging

6
X’ TENSIVE RANGE UP TO 60 HP

Standard Type

New series with compact and light weight design


20 HP
t
6 HP-60 HP with 56 models line-up (For Heat Pump & Cooling Only) Compac
Design

Installation Space 0.95 m2


Product Weight* 285 kg

*For cooling only model

Line-up
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
Cooling Only/
Heat Pump

7
X’ TRA POWER SAVING

New heights in energy efficiency


during actual operation
The key to innovative energy savings is to •Correlation between the load factor for the rated capacity and operation time
*According to a survey by Daikin (based on Air Conditioning Network Service System data)
increase efficiency during low-load operation.

Using data gathered from actual


operation, Daikin discovered that air Load factor of 50% or
conditioning systems operate at a load factor less accounts for 70% of

Operation period
annual operation period.
of 50% or less for 70% of their
annual operation period.

This inspired us to develop new


technologies to enhance energy efficiency
during low loads.

Utilising these technologies, Daikin’s new


VRV X series raise the standard for
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
energy efficiency.
Load factor for the rated capacity

Hardware
New scroll compressor* technology
•Compressor efficiency*
Compressor efficiency

New compressor
Refrigerant leakage is minimised Conventional compressor
during low-load operation.
Operation loss due to refrigerant
The back pressure control mechanism increases
leakage is reduced by the proprietary the efficiency during low-load operation.
back pressure control mechanism to Load factor
*Graph shown above is for illustration purposes only.
ensure stable low-load operation. For More information
'Scan Me'

Back pressure control mechanism


Conventional mechanism New
New intermediate
The movable scroll is pressed by the pressure pressure mechanism
difference between high and low pressures. The force pressing the movable scroll is
The force pressing the movable scroll optimised according to operating
decreases during low-load operation, results conditions. The behaviour of the movable
in compression leakage from movable parts. scroll has been stabilised to increase
efficiency during low-load operation.

Intermediate pressure adjustment port


The intermediate pressure (back pressure)
optimises the force pressing the movable scroll
depending on the operating condition.

The force pressing the movable scroll The intermediate pressure


decreases during low-load operation. keeps pressing the movable
scroll during low-load operation.

8
Energy saving

For More information Uniting advanced software and hardware technologies


'Scan Me'
for greater energy savings during actual operation.
Software
Software
VRT Smart Control (F ul l y Auto ma t i c En er g y -s a v i n g R ef r i g er a n t Co n t r o l )
technology
technology
Optimally supply only for the needed capacity of indoor units
Daikin developed VRT smart control by combining air volume control (VAV: Variable Air Volume) for indoor units with
conventional VRT control, which optimises compressor speed by calculating the required load for the entire system and
optimal target refrigerant temperature based on data sent from each indoor unit. Coordination with the air volume
control reduces compressor load and minimises operation loss based on detailed control. VRT smart control ensures
energy savings and comfortable air conditioning to meet actual operating conditions.
• Overview of the control (system control flow)
Different automatic energy-saving refrigerant control applies depending on the indoor units connected.

Target indoor units Temperature data


Subject to VRT smart control Subject to VRT control 1 received from
indoor units

Coordinated control

The following items are


forcasted and calculated based The VRT smart control also controls the
on the required capacity: airflow rate of indoor units
automatically*, to attain detailed
energy-saving control.
• Indoor fan air volume Select the target
Compressor
• Target value of refrigerant
temperature
* Airflow rate should be set to “Auto”.
2 refrigerant
temperature 3 speed control

The smooth control • Changes in the air-conditioned room temperature during low-load operation*
(which keeps the Conventional air-conditioning method Fully automatic energy-saving
refrigerant control
compressor running) Changes in the room temperature: Large
The power consumption attributed to the Changes in the room temperature:
saves energy and start-stop loss also increases the load. Small wasted power consumption is
Start also minimised.
ensures comfort
Temperature
during low-load Room setting
temperature Turned off by Turned off by Turned off by
operation. the thermostat the thermostat the thermostat

*Graph shown above is for illustration purpose only.

Note:
• For the classification of indoor units (VRT smart control and VRT control), refer to page 20.
• In case system is having both VRT Control and VRT Smart Control types of Indoor units, system will operate under VRT Control.
• If a system has air handling unit or outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.

Higher efficiency is provided


during rated operation Advanced oil temperature control
COP at 100% operation load
Standby power consumption is reduced
5
The advanced oil temperature control reduces standby power
4.73
Cooling operation COP

4.33 consumption compared to conventional models. Standby


New
4 power is needed for preheating refrigerator oil, which
consumes substantial standby power and is reduced to save
3
energy when the air conditioner is stopped.
VRV
X SERIES

0
6 HP 8 HP
Cooling operation conditions: Indoor temp, of 27°CDB, 19°CWB and outdoor temp, of 35°CDB.

9
VRT - VARIABLE REFRIGERANT TEMPERATURE

State-of-the-art energy saving


technology for VRV system

Customise your VRV


system for optimal annual efficiency

The new VRV X system features VRT technology. VRT automatically adjusts refrigerant temperature to individual
building and climate requirement, thus further improving annual energy efficiency and maintaining comfort.

With this excellent technology, running costs are reduced.

How is energy reduced?


Refrigerant cycle
During cooling, the refrigerant evaporating temperature (During cooling) (During heating)
(Te) is raised to minimise the difference with the
Condenser Condensing temperature lowered
condensing temperature. Compressor workload reduced
Indoor unit
heat exchanger
During heating, the condensing temperature (Tc) is Compressor
Condenser
Evaporator
lowered to minimise the difference to the evaporating
Indoor unit
temperature. Compressors work less and this reduces heat exchange Compressor
Evaporating temperature raised
power comsumption. Evaporator
Compressor workload reduced

Typical changes in evaporating temperature and COP depending on changing indoor load

100%
Required capacity changes
C ooling load

as air conditioning load


& capacity

Capacity
changes changes according to
to match outdoor temperature.
heat load
25%

20°C 25°C 30°C 35°C Outdoor


Temp. In case of fixed evaporating
temperature, excessive cooling,
thermo on-off loss and other
inefficiencies that occur.
Refrigerant evaporating

High

VRT
temp. / Te(°C)

Automatic control to
adjust temperature
Low

Automatic control adjusts


Without VRT evaporating temperature
to heat load change.
20°C 25°C 30°C 35°C Outdoor
Temp.

VRT
Energy efficiency is
High

improved without
COP

sacrificing comfort.
Lo w

Without VRT

20°C 25°C 30°C 35°C Outdoor


Temp.

10
Fine control to match user preference
available through mode selection
Basic mode is selected to maintain optimal comfort.

VRT is selected to save energy and prevent excessive cooling or heating.


Capacity priority Energy saving priority

Fixed Refrigerant Variable Refrigerant Temperature


Temperature

Basic Mode Auto Mode High Sensible Mode


Fixed Te/Tc - Standard control Floating target Te/Tc depending on heat load Fixed target Te

Selecting VRT enables operation to be optimised


for either energy efficiency or rapid
cooling/heating.

Floating Te/Tc Fixed Te

Powerful Mode Quick Mode Mild Mode Eco Mode


(default setting on VRV X)
Reaction speed Very Fast Reaction speed Fast Reaction speed Medium Unable to change Te

VRT offers quicker cool down


to shorten uncomfortable pull down time. • Can boost capacity above 100% if needed.
The refrigerant temperature can go low in cooling (high in heating)
Powerful than the set minimum (maximum in heating).
30 Gives priority to very fast reaction speed.
Powerful mode
The refrigerant temperature goes down (or up in heating) fast to keep
Indoor Temp. (°C)

Quick the room setpoint stable.


Start of Mild
cooling • Gives priority to fast reaction speed.
Quick
The refrigerant temperature goes down (or up in heating) fast to keep the room
mode setpoint stable.
Set temperatur e
25 • Gives priority to efficiency.
Time
Mild
Very Fast
mode The refrigerant temperature goes down (or up in heating) gradually, giving
Fast priority to the efficiency of the system instead of the reaction speed.
Medium

Recommended for use in these situations


Cooling only regions having differences Cooling/heating regions having periods
in daily temperature. of mild outdoor temperatures.
40 40 Heating Intermediate Intermediate Heating
Av. max. temp. Av. daily temp. difference period period Cooling period period period
Outdoor Temp. (°C )

Outdoor Temp. (°C )

35 35
30 30
Av. max. temp.
25 25
20 20
Av. min. temp.
15 15
(Typical example) Av. min. temp. (Typical example)
0 0
Mar. J un. Sep. Dec. Mar. Jun. Sep. Dec.

VRT is particularly effective at VRT is particularly effective during the


night when temperatures are low. intermediate periods.

11
X’ CELLENT TECHNOLOGY

Large capacity all DC inverter


compressor in compact casing

Large capacity inverter compressor using high tensile strength material,


realise 12 HP compressor using 8 HP casing.

Compact & high efficiency concentrated winding motor

Distributed winding motor Concentrated winding motor


(Current 8 HP compressor) (New 12 HP compressor)

Coil
end

Small size coil end using concentrated winding, reduces copper loss(winding resistance).
Improves motor efficiency in low rpm range (improves intermediate efficiency).

Highly integrated heat exchanger

Improves performance by increasing heat exchanger area while maintaining the same installation space.

Realises highly integrated heat exchanger performance by


Conventional employing 3 rows and reduced fin pitch coil as well as reduction
in airflow resistance by adopting small pipe size design.

20 HP
3 rows with small pipe design,
increase heat transfer efficiency

Fine Louvre Fin Waffle Fin

12
4D Inverter Technology
Improved reliability by introducing Daikin 3-phase capacitor-less 4D Inverter technology

Conventional inverter New inverter PC board


4Ds mean…
• Direct Inverter
• Dynamic
• Drive
• High Energy Density

• Direct conversion circuit which eliminates the


electrolytic capacitor and minimise the reactor size

• Dynamic waveform control that suppresses the


resonance phenomenon generated by
Electrolytic capacitors Film capacitor
miniaturizing parts

• Drive technology

• High Density integration of parts on small printed


circuit board

New Inverter PC Board


The control functions of inverter technology have been integrated on printed circuit boards. As well as improving
reliability, this has reduced the number of parts and enabled downsizing.
• New waveform control improves tolerance of variations in power supply voltage. Even if the power supply has
irregularities, rises in current are suppressed and operation continues.
• Durability of the inverter printed circuit board improved by changing the electrolylic capacitors for the compressor
to film capacitors.

Excellent Performance

Various advanced control main PC board


SMT* packaging technology
Computer control board surface
SMT packaging technology adopted adopting SMT packaging
by the whole computer control panel SMT packaging material
technology
improve the anti-clutter performance.

Protects your computer board from


adverse effect of sandy and Computer control board
humid weather.
*SMT: Surface mounted technology

*SMT: Surface mounted technology


Improved inner design to increase smooth airflow
Bell mouth
Downsizes electric component, relocates to dead

space of bell mouth side to decrease airflow resistance.

Electric Component Space

13
ADVANCE TECHNOLOGY ACHIEVED

Excellent Performance

Refrigerant cooling technology,


ensures stability of PCB temperature
Improves reliability at high ambient temperature
It is possible to cool the inverter power module
stability even at high ambient temperature. This helps
to keep air conditioning capacity and also ensures
efficient and reliable operation.

Comfort
Sound level (dBA)
Lower operation sound 6 HP 8 HP 10 HP 12 HP
Improves heat exchanger efficiency, helps VRV X 56 56 5
57 59
to reduce operation sound.
Quiet night-time operation function
Large airflow, high static pressure and quiet technology.
Outdoor PCB automatically memorises the time when the
Without increasing operation sound, advanced analytic peak outdoor temperature appears. It enables quiet
technologies are utilised to optimise fan design, operation mode after 8 h*1 and returns to normal mode
increase airflow rate and external static pressure. after it keeps this on for 9 h*2.

*1 8 h is the initial setting with 6 h or 10 h also available.


*2 9 h is the initial setting with 8 h or 10 h also available.
Streamlined air grille
e
It promotes the
Capacity

Night mode
(%)

100
discharge of
swirling airflow,
further reducing 50

the pressure loss.


Load
(% )

0 8 hrs 9 hrs
60
Streamlined scroll fan 57
Operating
sound (dB)

The sharp edge of each fan blade 50 min. 40 dBA


has a certain curvature, reducing 40
both the vibration and the 8:00 12:00 16:00 20:00 0:00 4:00 8:00
pressure loss. Notes:
Streamlined • This function is available in field setting.
scroll fan
• The operating sound in quiet operation mode is the actual value
measured by Daikin.
Illustrated • The relationship of outdoor temperature (load) and time shown above
fan
is just an example.
• For 10 HP ODU.

Ease of Maintenance
VRV X series provides a maintenance feature* which allows the shut down of indoor unit without shutting down the whole
VRV system. This feature comes in handy during maintenance period as the remaining indoor units continue to operate.

* Field setting is required.


This feature does not apply
to residential indoor unit
connection.
For more information,
please contact Daikin
Area A Area B Area C sales office.

14
X’ TENDED RELIABILITY

Automatic Refrigerant Charge Function


Contribute to optimised operation efficiency,
higher quality and easier installation
For More information Optimised Operation
'Scan Me'

Optimised operation efficiency Efficiency


Cooling
capacity

The automatic refrigerant charge function automatically


determines the optimal amount of refrigerant to be charged.
Insufficient Excessive
refrigerant charge refrigerant charge
This function prevents a capacity shortage or energy loss
due to excessive or insufficient refrigerant.
Optimal refrigerant Refrigerant
amount charge amount

Higher quality and easier installation


The automatic refrigerant charge function automates the charging of the proper refrigerant amount and the closing of
shut-off valves with just one press of the switch after pre-charging. Simplified installation eliminates excessive and
insufficient refrigerant charge amounts due to calculation mistakes and this has led to higher installation quality.

Conventional

1 2 3 4 5
Calculate necessary Recalculate refrigerant Charge refrigerant Regularly check Complete by
refrigerant amount amount from final refrigerant weight on manually closing
from design drawing installation drawing weighing scale valves when proper
weight is reached

1 2 3 Automatic completion with


Calculation of necessary Pre-charge of refrigerant* Start of automatic optimal refrigerant amount
refrigerant amount from refrigerant charge operation
design drawing
Monitoring refrigerant charging is
not required

No recalculation of charge amounts


due to minor design changes at site
*Pre-charge amount changes according to conditions,
and there are cases when pre-charging is unnecessary.

Multiple advanced features ensuring more


accurate test operation and stable system
Automatic check
Efficient automatic test operation
Wiring
Automatically checks the wirings between outdoor units and indoor units to check
confirm whether there is a defective wiring.

Confirms and corrects the actual piping length. Piping


check
Automatically checks whether the stop valve in each outdoor unit is in normal
status to ensure the smooth operation of air conditioning system.
Stop valve
check
Free phase technology
Phase reversal occurs in areas where power supply is frequent. At the time of power recovery, phase reversal may take
place due to AC source and device may stop for PCB protection. By employing Free Phase technology, continued
operation is achieved.

15
X’ TENDED RELIABILITY

Simplified commissioning
and after-sales service
Function of information display 7-segment digital display Conventional LED display
by luminous digital tube Figures out
system
VRV X system utilises the 7-segment luminous operation
Displays information by
digital tubes to display system operation system reading light
operation emitting state
information, enabling the operational state to be information of different
directly. diodes, which
visually displayed whilst facilitating simplified
is both
commissioning and after-sales service. inefficient and
fallible.

VRV configurator
• The VRV configurator is an advanced solution that allows Simplified
for easy system configuration and commissioning. commissioning
• Less time is required on the roof configuring the
outdoor unit.
• Multiple system at different sites can be managed in exactly
the same way, thus offering simplified commissioning for
key accounts. Retrieve initial
• Initial setting on the outdoor unit can be easily retrieved. system settings

Outdoor unit sequencing technology


Automatic sequencing operation
During start-up, the Daikin VRV X unit sequencing operation will be automatically enabled to ensure balanced
operation of each outdoor unit to improve longevity of equipment and stable operation.

Stage 1 Stage 2 Stage 3


Automatic Automatic
sequencing sequencing

Priority: Priority: Priority:

Double back-up operation functions responding


resiliently to various unexpected situations
Double back-up operation functions
Daikin VRV X system boasts double back-up operation functions, which can secure the use of air conditioners in this area to the
greatest extent by emergently enabling double back-up operation functions even if failure occurs in a set of air conditioning
equipment. In the event of a failure, emergency operation can be enabled conveniently to allow the remaining system to operate in a
limited fashion.
Compressor back-up Operation Function
If malfunction occurs in a compressor...
Emergency
Emergency operation can be easily set and enabled by the outdoor unit operation Malfunction
(for a single outdoor unit system RXQ16-20ARY6 : for Cooling only model
RXYQ14-20ARY6: for Heat Pump model).

Unit back-up operation function


If malfunction occurs in an outdoor unit, emergency operation can be conveniently set and enabled
by the remote controller for indoor unit (for systems composed of two or more outdoor units).

16
MORE FLEXIBLE SYSTEM DESIGN

More options for


installation location
Long piping length
The long piping length provides more design flexibility, which can match even large-sized buildings.

Between the outdoor


branch and the last
outdoor unit
Max. 13m
Max. total piping length 1000m
Between the
outdoor units
Max. 5m

Max. level difference


between the outdoor units
and the indoor units
Max. equivalent
piping length
90m*2
190m
Max. level
difference between
Between the first indoor the indoor units
branch and the farthest
indoor unit 30m

Max. 90m*1

Note: The above is just a schematic diagram.

Actual piping length (Equivalent) 165 m (190 m)


Total piping length 1000 m
Maximum allowable piping length
Between the first indoor branch and the farthest indoor unit 90 m*1
Between the outdoor branch and the last outdoor unit (Equivalent) 10 m (13 m)
Between the outdoor units (Multiple use) 5m
Maximum allowable level difference Between the indoor units 30 m
Between the outdoor units and the indoor units 90m*2

1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and
requirements have to be met to allow utilisation of 90 m piping length.
2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased. If the outdoor unit is above the indoor unit,
a dedicated setting on the outdoor unit is required.

Connection ratio
Conditions of VRV indoor unit connection capacity
Connection capacity
at maximum is 200%. Applicable Other VRV indoor
VRV indoor units unit models*1
Connection ratio FXDQ, FXMQ-PB, FXAQ, models

50%–200% Single outdoor units

200%
200%
Double outdoor units 160%
Connection ratio = Triple outdoor units 130%
Total capacity index of the indoor units *
1 For the FXFQ25 and FXVQ models, maximum connection ratio is 130% for the entire range of outdoor units.
Capacity index of the outdoor units Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the
indoor units.
*Refer to page 65 for outdoor unit combination details.

17
High external static pressure
VRV X outdoor unit has achieved
high external static pressure up to 78.4 Pa
78.4 Pa, ensuring the efficient heat More options in the
More options in the
opening/angle of louvre
dissipation and stable operation of Outstanding heat dissipation
equipment in either hierarchical or effect in both hierarchical and
intensive arrangement
intensive arrangement.

18
OUTDOOR UNIT LINE-UP

Outdoor Units

The outdoor unit capacity is up to 60 HP in increment of 2 HP.


• VRV X outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized buildings.

• The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but
also bringing the system flexibility to a new level.

• With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.

Standard Type

• Single Outdoor Units • Double Outdoor Units


6, 8, 10, 12 HP 14, 16 HP 18, 20 HP 22, 24 HP 26, 28, 30 HP

RX(Y)Q6ARY6 RX(Y)Q14ARY6 RX(Y)Q18ARY6 RX(Y)Q22ARY6 RX(Y)Q26ARY6


RX(Y)Q8ARY6 RX(Y)Q16ARY6 RX(Y)Q20ARY6 RX(Y)Q24ARY6 RX(Y)Q28ARY6
RX(Y)Q10ARY6 RX(Y)Q30ARY6
RX(Y)Q12ARY6

• Double Outdoor Units • Triple Outdoor Units

32, 34, 36, 38, 40 HP 42, 44, 46, 48, 50, 52 HP 54, 56, 58, 60 HP

RX(Y)Q32ARY6 RX(Y)Q42ARY6 RX(Y)Q54ARY6


RX(Y)Q34ARY6 RX(Y)Q44ARY6 RX(Y)Q56ARY6
RX(Y)Q36ARY6 RX(Y)Q46ARY6 RX(Y)Q58ARY6
RX(Y)Q38ARY6 RX(Y)Q48ARY6 RX(Y)Q60ARY6
RX(Y)Q40ARY6 RX(Y)Q50ARY6
RX(Y)Q52ARY6

Line-up
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
Cooling Only/
Heat Pump

19
INDOOR UNIT LINE-UP

Enhanced Range Of Choices


A variety of VRV indoor units is enabled in one system, opening the door to stylish and quiet indoor units.

VRV Indoor Units 17 types 76 models

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 7 HP 8 HP 10 HP 16 HP 20 HP
Capacity Index 20 25 32 40 50 63 71 80 100 125 140 170 200 250 400 500
Ceiling Mounted
Cassette Round FXFSQ-ARV16
Flow & Round Flow VRT
with Sensing (Optional) VRT Smart Control

Ceiling Mounted
Cassette VRT FXZQ-AVM
(Compact Multi Flow) VRT Smart Control
Ceiling Mounted
Cassette VRT FXCQ-AVM
(Double Flow)

Ceiling Mounted FXKQ-AV


Cassette Corner New

FXDQ-PDV36
VRT (with drain pump)
VRT Smart Control (700mm width type)
Slim Ceiling
Mounted Duct FXDQ-NDV36
VRT (with drain pump)
VRT Smart Control (900/1,100mm width type)

FXMQ-PAVE/PBV36
VRT
VRT Smart Control
Ceiling Mounted Duct
VRT FXMQ-NVE

Mid Static Ceilling VRT


Mounted Duct FXMQ-ARV16
VRT

Ceiling Suspended VRT FXHQ-MAVE

4-Way Flow VRT FXUQ-AVEB


Ceiling Suspended

Wall Mounted VRT FXAQ-ARVE6


VRT Smart Control

Floor Standing VRT FXLQ-MAVE

Concealed
Floor Standing VRT FXNQ-MAVE

Multi Cube/Spot New FXPQ-AVM

Floor Standing
Duct VRT FXVQ-NY1(6)

VRT
FXBQ-PVE
VRT
Clean Room
Air Conditioner
VRT FXBPQ-PVE

20
At Daikin, we offer a wide range of indoor units, including both VRV and residential models, responding to a
variety of needs of our customers that require air conditioning solutions.

VRV Indoor Units

Ceiling Mounted Cassette Ceiling Mounted Cassette


Round Flow & Round Flow (Compact Multi Flow) Type
with Sensing (Optional)
FXFSQ-ARV16 FXZQ-AVM

Presence of people and floor


temperature can be detected to Quiet, compact and designed for
provide comfort and energy savings. users comfort.

Ceiling Mounted Cassette Ceiling Mounted Cassette


(Double Flow) Type Corner Type
FXCQ-AVM
FXKQ-AV

New

Add finishing touch to your ceiling, Slim design for flexible


with enhancing function and design. installation.

Slim Ceiling Mounted Ceiling Mounted Duct Type


Duct Type

FXDQ-PDV36 FXMQ-PBV36

FXMQ-ARV16

FXDQ-NDV36 FXMQ-NVE

Slim design, quietness and High/Mid external static pressure


static pressure switching. allows flexible installations.

4-Way Flow Ceiling Ceiling Suspended Type


Suspended Type

FXUQ-AVEB FXHQ-MAVE

This slim and stylish indoor unit Slim body with quiet and
achieves optimum air distribution, wide airflow.
and can be installed without the
need for ceiling cavity.

21
INDOOR UNIT LINE-UP

Floor Standing Duct Type Floor Standing Type


FXLQ-MAVE

FXVQ-NY16
(High static pressure type) Concealed Floor Standing
Type
FXNQ-MAVE

Large airflow type for large spaces. Suitable for perimeter zone air
Flexible interior design for each tenant. conditioning.

Wall Mounted Type Clean Room Air Conditioner

FXAQ-ARVE6
FXBQ-PVE

FXBPQ-PVE

Stylish flat panel design harmonised Suitable for hospitals and other clean
with your interior décor. spaces.

Multi Cube (Spot AC) Type

FXPQ-AVM

New

New solution in large


space comfort.

22
VRV Indoor Units
Ceiling Mounted Cassette Round Flow & Round Flow with Sensing (Optional)

VRT Smart Control


FXFSQ25A / FXFSQ32A / FXFSQ40A /
FXFSQ50A / FXFSQ63A / FXFSQ80A /
FXFSQ100A / FXFSQ125A /
(Optional)
FXFSQ140A

Presence of people and floor temperature can be


detected to provide comfort and energy savings.
Dual sensors*1

Infrared presence sensor

The 4 sensors detect human presence.


Ceiling height 2.7m 3.5m 4.0m
Round
R ou
und flow
flow
flo Detection range approx. approx. approx.
with sensing (diameter)*3 8.5m 11.5m 13.5m
Detecting the
presence of people *3. The infrared presence sensor detects 80 cm above the floor.
in 4 areas

C
B D
Infrared floor sensor
A
The sensor detects the floor temperature and
Detecting the
average temperature
automatically adjusts operation of the indoor
of indoor floor unit to reduce the temperature difference
between the ceiling and the floor.
Ceiling height 2.7m 3.5m 4.0m
Detection range approx. approx. approx.
(diameter)*4 11m 14m 16m

Various sensing functions *4. The infrared floor sensor detects at the floor surface.

Sensing sensor mode*5*6


Operation is reduced in places
Sensing sensor low mode (default: OFF) where there are no people.

When there are no people in a room, the set temperature is shifted automatically.

The system automatically saves energy by detecting whether or not the room is
occupied. The set temperature is shifted automatically if the room is unoccupied.
• Cooling setpoint: 26°C • Shift temperature: 1.0°C
Example
• Shift time:30 min. • Limit cooling temperature:30°C
28 28°C
27 27°C If people do not
26 26°C 26°C return, the air
Setpoint (°C)

Automatically conditioner will


Occupied reverts when raise the
people return. WHPSHUDWXUHʝ
Unoccupied
every 30 minutes
and then operate
DWʝ
Time
After 30 min After another 30 min

6KLIWWHPSHUDWXUHDQGWLPHFDQEHVHOHFWHGIURPWRʝLQʝLQFUHPHQWVDQGRU For More information


120 minutes respectively with remote controller. 'Scan Me'

*1.
Applicable when sensing panel (BYCQ140EEF6/BYCQ125EEK) is installed.
*5.
These functions are not available when using the group control system.
*6.
User can set these functions with remote controller.

23
INDOOR UNIT LINE-UP

VRV Indoor Units

Sensing sensor stop mode (default: OFF)


When there are no people in a room, the system stops automatically.*7
The system automatically saves energy by detecting whether or
not the room is occupied.
Based on preset user conditions, the system automatically stops
operation if the room is unoccupied.

Absent stop time can be selected from 1 to 24 hrs in 1 hr increments with remote controller.
*7.
3OHDVHQRWHWKDWXSRQUHHQWHULQJWKHURRPDLUFRQGLWLRQHUZLOOQRWVZLWFKRQDXWRPDWLFDOO\

Auto airflow function*8


*[Link] direction shoud be set to “Auto”.

New Direct Airflow (default: OFF) Cooling Dry

When human presence is not detected When human presence is detected

Optimal air direction by “Auto”

Optimal air direction by “Auto” Swing (narrow)

• With Auto airflow direction mode, flaps • When human is detected, air direction is
are controlled to deliver optimal airflow set to “Swing (narrow)” to deliver cool air
when the room is unoccupied. to users.

24
Comfort and energy saving preventing over cooling*9

$LUIORZGLUHFWLRQDQGDLUIORZUDWHVKRXOGEHVHWWR´$XWRµ

Floor temperature is detected and over cooling prevented. Cooling


Without sensing function With sensing function

30°C near ceiling 30°C near ceiling

Room 2 Room temperature is


temperature is calculated as 27°C in the area which
detected as LVLQWKHYLFLQLW\RIWKHSHUVRQ
ƒ&
1 24°C near floor
20°C near floor

Area around feet gets too cold because air conditioner The floor temperature, Automatic control using
which is lower than near the temperature near the
continues until the temperature near the ceiling reaches
the ceiling, is detected. person as the room
the set temperature. temperature.

(QHUJ\ The temperature near the person is automatically calculated by detecting the temperature of the
savings IORRU(QHUJ\LVVDYHGEHFDXVHWKHDUHDDURXQGWKHIHHWGRHVQRWJHWWRRFROG

New Circulation Airflow

1. Blows horizontally

2. Strikes the wall

3. Reaches every The illustration shows typical airflow.


corner of the room Effectiveness may differ according to room
conditions, room size and distance to walls.

Individual Airflow
New Direct Airflow Direction Control

The illustration shows


Optimal air direction Swing typical airflow.
by “Auto” (narrow)

25
INDOOR UNIT LINE-UP

Circulation Air Flow *1. Applicable when wired remote controller BRC1E62 is used.
*2. Not applicable when using individual airflow direction control.

Circulation airflow cools the entire room to deliver comfort that never feels cold
During 2-way horizontal flow
Hot
outdoor air

Airflow effectively avoids


blowing air directly on people.

Cool air moves down along Comfort without Cools by airflow blocking
the walls and to every cold air pockets at out hot air near windows
corner of the room. floor level. and walls.

Comfort to the entire room with even temperatures and no cold air pockets at floor level
30.0 Comparison Conditions
4-way cassette (Swing) 29.0
Room size:
28.0
27.0 Width 7.5m x depth 7.5m
26.0 x height 2.6m
25.0 Indoor unit capacity:71 class
24.0
23.0 Outdoor air temperature:35ʝ
22.0 Airflow rate and air direction:
21.0 high / swing
20.0

Areas at floor level are


cold while areas
around walls are hot.

%KRETĚCěKON#KRĝOV(2-way horizontal + 4-way swing) Approx. 5% energy *3


savings by reducing
uneven temperatures
*[Link] under the following
comparison conditions:
When the average temperature at a
height of 0.6m above the floor
o
reaches set temperature. (26 C)

Full comfort is
provided with no
cold feet.

Configurations of Circulation Airflow


Operation Performs repeatedly
(at start) Airflow
direction When the target
changes temperature is reached,
normal operation
(all-round flow) begins.

Cools areas around Cools entire room Cools areas around Cools entire room Note: Results may vary depending on
equipment conditions, room size
walls using using 4-way walls using using 4-way and distance from indoor unit to walls.
2-way horizontal flow swing flow 2-way horizontal flow swing flow

26
Three technologies that achieved circulation airflow
Flow-out is straight, horizontally and strong, so the air travels far and even reaches the wall from which it falls to the floor. This
approach and technology makes circulation airflow possible.
1
1 Use of new wide flaps (Straight)
Compared to conventional models, the new Conventional flap*4 New wide flap
wide flap increases straightness of the airflow,
so coverage is approximately doubled.

Approx.
doubled

*4. FXFQ-S model

New wide flap construction inhibits


ceiling dirt and grime

By tapering both flap ends, the airflow that causes dirty


ceilings is directed downward.

22 Optimising airflow angle (Horizontally)


Even with the flap angle raised, a sufficient airflow route is
maintained to realize a more horizontal airflow angle.

Conventional flap*4 New wide flap


*4. FXFQ-S model
20°
horizontal
flow

30° air direction 20° air direction

When set to 20°


the airflow route A more horizontal 20°
Cannot blow more gets narrow. flow is realized. Even at 20°, the airflow
than 30° horizontal. route is sufficiently
maintained.

23 Increased velocity in 2-way flow (Strongly)


Velocity increased by making 2-way flow. Powerful airflow was realized.

All-round flow Two-way flow

Velocity
*5
10%
increase

*5

*[Link] 2 outlets are controlled by changing the flap direction (angle) to suppress airflow volume.

27
INDOOR UNIT LINE-UP

*1. Applicable when wired remote controller BRC1E63 is used.

Comfortable air conditioning for all room layouts and conditions

Airflow direction can be Easy setting is possible with a wired remote controller.
individually adjusted for each air
discharge outlet to deliver optimal
air distribution.

There are
identification
marks near
the air outlets.
Position 0 Remote controller
((KWGFCKRĝOVěO BRC1E63 screen
highest position)

Individual airflow settings


No individual • No individual setting (Auto airflow)
setting • Position 0 (Highest point)
(#TěOCKRĝOV) • Position 1
• Position 2
• Position 3
Swing Position 4
(Up/down) ((KWGFCKRĝOVěOěJG • Position 4 (Lowest point)
lowest position) • Swing

Individual settings are possible as stated above.

When individual airflow is selected, airflow direction can be adjusted to room layout.

Position
Position Position
0 0
For offices The airflow is at the
highest setting (Position 0)
for people who
Swing dislike air blowing
Discussions near Swing is set for directly on them.
a hot window meetings near
quickly heat up. the windows.

It’s quite pleasant


It is very cold here, when cold air isn’t
isn’t it?… Discussions
scu
cussions also
als blowing on us.
go smoothly.

For shops and restaurant

Swing
Swing is
selected for
areas near No individual (Auto)
the windows.
Auto is set for people
sitting farthest from
Sitting here is hot The seats here the entrance.
because of the hot air are comfortable
from outside. though…

28
New
Wide variety of decoration panels (Option)
• Designer choice has been given a boost with the increase in number of new types of decoration panels.

- Fresh White - - Black - - Fresh White - - Fresh White - - Black -

Standard panel with sensing Designer panel *2 Standard panel *2

New
Designer panel (Option)

Close to ideal styling


New designer panel

FLAT C L E AN ROUND

Flatter styling: Clean-cut form: Subtle distinction:


Suction panel grid Soiling is hard to see Around suction inlets
texture smoothed. on smart-looking panel. silvering is a tasteful touch.

Decoration
coration Panel Line
Line-up
u (Option)

Standard panel*1 Standard panel*1 Designer panel*1 *1. Sensing function is applicable
when sensing panel is installed.
BYCQ125EAF6
YCQ125EAF6 (Fresh White
White) BYCQ125EAK (Black) BYCQ125EAPF (Fresh White)

Sensing panel Sensing panel


BYCQ140EEF6 (Fresh White) BYCQ125EEK (Black)

New
Auto grille panel (Option)*1

• Clogged filters strain performance of the indoor unit and may


For these situations recommended
result in breakdowns. Impeded airflow through the filter also • Where the air is dusty and likely to
lowers operational efficiency, which increases electricity bills. soil the air conditioner.
• Where simple and quick filter and
With the auto grille, anyone can easily clean the filter, which grille cleaning is a worthwhile benefit.

translates to lower maintenance cost and longer life of the


air conditioner.
• With the auto grille panel, motorised raising and lowering allows
suction panel and air filter cleaning to be carried out without the Auto grille panel*1
need for a step ladder. BYCQ125EASF (Fresh White)
A dedicated wireless remote controller is supplied with the auto grille panel.

29
INDOOR UNIT LINE-UP

Comfortable airflow Easy installation


• Indoor unit offers 360° airflow discharges air • Drain pump is equipped as a standard accessory
in all directions with more uniform with a 850mm lift.
temperature distribution.

Dead spot of airflow


850mm

Easy maintenance
There are areas of
uneven temperature.
• Internal hygiene can be easily checked without
removing the whole panel. Simply opening the suction
panel allows the internal drain pan to be checked.

New
New
• 24mm diameter drain outlet

The drain outlet allows insertion of a finger


There are much fewer or dental mirror for inspection of the internal
areas of uneven cleanliness of the drain pan. Removal of the
temperature. suction panel enables access.

30
Example of airflow patterns

All-round flow is available, as well as 2-way to 4-way flows, so you can choose the most suitable airflow pattern depending
on location or room layout.

All-round flow 4-way flow

3-way flow L-shaped 2-way flow

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing
material (option) must be used to close each unused outlet.

All-round flow is available, as well as 2-way to 4-way flows, so you can choose the most
suitable airflow pattern depending on location or room layout.

• An antibacterial treatment that uses silver ions has been applied to the drain pan,
preventing the growth of slime, mould and bacteria that cause blockages and odours.
(The lifespan of a silver ion cartridge depends on the usage environment, but should be
changed once every two to three years.)

• The air filter has an anti-mould and antibacterial treatment that prevents the growth
of mould generated from dust or moisture that may adhere to the filter.

New

• Control of the airflow rate can be selected from 5-step control and auto.

31
INDOOR UNIT LINE-UP

VRV Indoor Units

Ceiling Mounted Cassette (Compact Multi Flow Cassette) Type

FXZQ20AVM / FXZQ25AVM / FXZQ32AVM


VRT Smart Control
/ FXZQ40AVM / FXZQ50AVM
*FXZQ-A FXZQ-A

VRT Smart

Quiet, Compact, Designed for


user comfort 8mm

Compact & Elegant Design


• Fully-flat integration in standard architectural ceiling tiles, leaving only 8mm.
• Remarkable blend of iconic design and engineering excellence with an
elegant finish in white.
• The newly designed panel integrates fully within one ceiling tile enabling
lights, speakers and sprinklers to be installed in the adjoining ceiling tiles.

Efficiency & Comfort


• Two optional intelligent sensors improve energy efficiency and comfort.
• An optional presence and floor sensor kit can be fitted to the cassette for
draught prevention, energy-saving operation and to provide optimal control
of airflow.

Individual airflow direction control: Flexibility to suit every room layout without changing the location of the unit.

Auto swing (up/down)


Possibility to select automatic vertical moving of the air discharge flaps for efficient air and temperature distribution
throughout the room.

Ceiling soiling prevention


• Prevents air from blowing against the ceiling to prevent ceiling stains.
• Reduced energy consumption, thanks to the specially developed small tube heat exchanger, DC fan motor, and drain
pump optional fresh air intake kit.

32
Ceiling Mounted Cassette (Double Flow) Type

FXCQ25AVM / FXCQ32AVM / FXCQ40AVM /


FXCQ50AVM / FXCQ63AVM / FXCQ80AVM /
FXCQ125AVM

Add finishing touch to your ceiling, with


enhancing function and design.
Stylish unit blends easily with any interior. Integrated
ceiling surface with sophisticated panel design with the
adoption of flat flap. Add finishing touch to your ceiling,
with enhancing function and design.
• Individual airflow direction control (Unavailable
during automatic airflow mode, airflow angle:
configurable from 0 to 4 swing positions.)

Individual flap control

The flat flaps close


entirely when the
unit is not operating
and there are no
air intake grilles
visible.

• Reduced energy consumption thanks to specially developed


small tube heat exchanger, DC fan motor and drain pump. 850mm

Enhanced functions from various aspects such as


maintenance
• An antibacterial treatment that
• Check contamination in drain pan by simply removing
uses silver ions has been applied
suction grille and panel.
to the drain pan, preventing the
• The flap parts are easy to clean because it is hard to growth of slime, mould and
condensate and get dirty. bacteria that cause blockages
• Equipped with long life filter which requires only 1-year and odours.
maintenance interval. (The lifespan of a silver ion cartridge
• Adjuster pockets mount at four corners of the unit enable depends on the usage environment,
to adjust the main unit without removing the panel. but should be changed once
• Drain pump is equipped as standard accessory with every two to three years.)
850mm lift.

Drain socket part

• Easy visual inspection of drainage through the


Adjuster Pocket transparent body drain socket.

33
INDOOR UNIT LINE-UP

VRV Indoor Units

Ceiling Mounted Cassette Corner Type

New

FXKQ32AV / FXKQ40AV
FXKQ50AV / FXKQ63AV

This new Indoor unit has been awarded with Good Design Award

• Very Compact & Elegant Design


• Sleek panel with dual tone styling that give rational choice of elegancy
• Flexibility to install on several height false ceiling minimum up to 3.9 inches (100mm)
with the help of multiple spacers (Optional).

White Color Panel Silver Color Panel

Base Color: Black Base Color: White Base Color: Black


Surface color: White Surface color: White Surface color: Silver

34
Installation with Panel Spacers

It has the flexibility to install on several height false ceiling i.e its ceiling height can be minimize with multiple optional by spacers
(25mm each) from 25mm to 75mm
Note- Spacer colour- Dark gray

Further Further
Standard Ceiling Height Reduced by 25mm Reduced by 25mm Reduced by 25mm
175mm (6.88 Inches) 150mm (5.9 Inches) 125mm (4.9 Inches) 100mm (3.9 Inches)
145mm IDU height + 30mm clearance

<Full Covered) <Half Covered)

Celling Surface 25mm Spacer 50mm Spacer 75mm Spacer

Optional List Spacer Kit Detail:


Space Kit-Model Name
Item Name Required Height (mm) BKF25A6 BKF25CA6 BKF50CA6 BKF75SA6
Spacers (Nos): 2 + 2 Comers 4 Nos + Screws 4 Nos Comers 4 Nos + Screws 4 Nos Installation Hook: 6 Nos
App. Model/Qty. 1 1 X X

25
(mm) Item/Images NA NA

App. Model/Qty. 2 2 1 X

Spacer 50
Assembly (mm) Item/Images NA

App. Model/Qty. 3 3 1 1

75
(mm) Item/Images

BKF25CA6 BKF50CA6
75mm Spacer

Detail View

BKF25A6 BKF75SA6

35
INDOOR UNIT LINE-UP

VRV Indoor Units


Slim Ceiling Mounted Duct Type
VRT Smart Control
FXDQ20PD / FXDQ25PD / FXDQ32PD
FXDQ40ND / FXDQ50ND / FXDQ63ND

Slim design, quietness and static pressure switching

• Only 200mm in height, this model can be installed in


Suited to use in drop-ceilings rooms with as little as 240mm depth between the
drop-ceiling and ceiling slab.
• Only 700mm in width and 23 kg in weight,
this model is suitable for installation in limited
spaces like drop-ceilings in hotels.

Great for
hotel use

200mm
900mm
200mm
Only 700mm * 1,100mm in width for the FXDQ63ND model.

Suspension bolt* Air filter

AIR 240mm
Discharge grille *
Suction grille *
AIR
* To be obtained locally

• External static pressure selectable by remote controller


switching makes this indoor unit a very comfortable and
flexible model.

10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PD models.


15 Pa-44 Pa/factory set: 15 Pa for FXDQ-ND models.

• FXDQ-PD and FXDQ-ND models are available with a


• Control of the airflow rate has been improved from drain pump as a standard accessory.
2-step to 3-step control. FXDQ-PD/NDVE: with a drain pump (750mm lift) as a standard
accessory
Low operation sound level (dBA)

FXDQ-PD/ND 20/25/32 40 50 63
Sound level
33/31/29 34/32/30 35/33/31 36/34/32 750mm
(HH/H/L)

* The values of operation sound level represent those for rear-suction


operation. Sound level values for bottom-suction operation can be Ceiling

obtained by adding 5 dBA.


* Values are based on the following conditions:
FXDQ-PD: external static pressure of 10 Pa; FXDQ-ND: external static
pressure of 15 Pa.

36
High Static Pressure Ceiling Mounted Duct Type

FXMQ20P / FXMQ25P / FXMQ32P VRT Smart Control


FXMQ40P / FXMQ50P / FXMQ63P
FXMQ80P / FXMQ100P / FXMQ125P
FXMQ140P

High static pressure allows for flexible duct design

• A DC fan motor increases the external static pressure


capacity range to include middle to high static pressures,
increasing design flexibility.

30 Pa-100 Pa for FXMQ20P-32P

30 Pa-160 Pa for FXMQ40P

50 Pa-200 Pa for FXMQ50P-125P

50 Pa-140 Pa for FXMQ140P


All models are only 300mm in height, an improvement over
the 390mm height of conventional models. The weight of the
FXMQ40P has been reduced from 44 kg to 28 kg.

Drain pump is equipped as standard 700mm Improved ease of installation


accessory with 700mm lift. • Airflow rate can be controlled using a remote
Ceiling
controller during test operations. With the
Control of the airflow rate has been improved from 2-step to conventional model, the airflow rate was controlled
3-step control. from the PC board. It is automatically adjusted to the
range between approximately ±10% of the rated HH
Low operation sound level (dBA)
tap airflow for FXMQ20P–125P.
FXMQ-P 20/25 32 40 50 63 80/100 125 140
Sound
level
(HH/H/L)
33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43 Improved ease of maintenance
• The drain pan can be detached for easy cleaning.
Energy-efficient An antibacterial treatment that uses silver ions has
• The adopted DC fan motor is much more efficient than been applied to the drain pan, preventing the growth
the conventional AC motor, yielding an approximate of slime, mould and bacteria that cause blockages
20% decrease in energy consumption (FXMQ125P). and odours.

FXMQ170N/FXMQ200N
FXMQ250N

Simplified Static Pressure Control


External static pressure can be easily adjusted using a
change-over switch inside the electrical box to meet the
resistance in the duct system.

37
INDOOR UNIT LINE-UP

VRV Indoor Units


Mid Static Pressure Ceiling Mounted Duct Type

FXMQ40A / FXMQ50A / FXMQ63A


FXMQ80A / FXMQ100A

Mid static pressure allows for flexible duct design


• AC fan motor is installed to suit applications where High airflow rate
external static pressure is required at nominal capacity. Airflow rate is optimised to meet wider spectrum of
30 Pa-50 Pa for FXMQ40-80ARV16 airflow requirements.

30 Pa-60 Pa for FXMQ100ARV16 Low operation sound level (dBA)


FXMQ-A 40 50 63 80 100
Sound level
All models are only 300mm in height, an improvement over (H/L) 39/37 41/39 42/40 43/41 44/42

the 390mm height of conventional models. The weight of the


FXMQ40P has been reduced from 44 kg to 28 kg.
Improved ease of maintenance
Drain pump is equipped as standard • The drain pan can be detached for easy cleaning.
700mm
accessory with 700mm lift. An antibacterial treatment that uses silver ions has
Ceiling been applied to the drain pan, preventing the growth
of slime, mould and bacteria that cause blockages
and odours.

38
Ceiling Suspended Type

FXHQ32 / 63 / 100MA FXHQ125 / 140A

Slim body with quiet


and wide airflow

New 125 / 140 models provide greater capacity


for large spaces
The technology of the DC fan motor, wide sirocco fan,

and quiet operation.

Sophisticated design
Flap neatly closes when
not in use.

Suitable for high ceilings


Comfort
4.3
m Auto swing (up and down) and louvers (left and right
by hand) bring comfort to the room.

Switchable fan speed: 3 steps

3-step.

Quiet operation
Drain pump kit (option) includes a silver ion antibacterial Uses quiet stream fan and other quiet technologies.
agent that assists in preventing the growth of slime, (FXHQ32-100MA)
bacteria, and mould that cause smells and clogging. Sound absorption
member

Quiet stream fan


Straightening vane

dBA
Sound level
Indoor unit
H M L
FXHQ32MA 36 ----- 31
FXHQ63MA  ----- 34
FXHQ100MA 45 ----- 37
FXHQ125A 46 41 37
FXHQ140A 48 42 37

39
INDOOR UNIT LINE-UP

VRV Indoor Units


Wall Mounted Type
VRT Smart Control

FXAQ20A / FXAQ25A
FXAQ32A / FXAQ40A
FXAQ50A / FXAQ63A

Stylish flat panel design harmonised


with your interior décor

• Stylish flat panel design creates a graceful harmony that enhances any interior space.

• Flat panel can be cleaned with only the single pass of a cloth across their smooth surface.

• Vertical auto-swing realises efficiency of air distribution. The louvre closes automatically when the unit stops.

40
Floor Standing Type

FXLQ32MA / FXLQ50MA
FXLQ63MA

Suitable for perimeter zone air conditioning


• Floor Standing types can be hung on the wall for easier cleaning.
Running the piping from the back allows the unit to be hung on walls.
Cleaning under the unit, where dust tends to accumulate, is
considerably easier.

• The adoption of a fibre-less discharge grille, featuring an original


design to prevent condensation, also helps prevent staining and makes
cleaning easier.
• A long-life filter is equipped as standard accessory.
*8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Wall hanging Floor installation

Concealed Floor Standing Type

FXNQ32MA / FXNQ50MA
FXNQ63MA

Designed to be concealed in the


perimeter skirting-wall

• The unit is concealed in the skirting-wall of the


perimeter, that creates a classy interior design.
• The connecting port faces downwards, greatly
Connecting
facilitating on-site piping work. port

Refrigerant
• A long-life filter is equipped as a standard piping
accessory.
* Applies also to Floor Standing type
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
(FXLQ-MA).

41
INDOOR UNIT LINE-UP

VRV Indoor Units


Floor Standing Duct Type

FXVQ125N / FXVQ200N
FXVQ250N / FXVQ400N
FXVQ500NY16

Large airflow type for large spaces.


Flexible interior design for each customer.
• Large airflow type that fits for spacious areas such as factories and
large stores.

• Various installations can be supported from full-scale duct connection


airflow to direct airflow that allows for easy installation.

• Full-scale duct connection airflow allows for


air conditioning evenly in spacious areas.

Duct connection airflow type


• Adding the plenum chamber (option) allows for
simple operation with direct airflow.
* Note that the operation sound increases by
approximately 5 dBA.

Direct airflow type


• The high static pressure type driven by the belt drive system
allows the usage of air discharge outlets in various shapes as
well as long ducts. Highly flexible installation is possible.
• High maintainability design that allows major services and
maintenance services to be performed at the front.
• A long-life filter is equipped as a standard accessory.
*8 hr/day, 26 day/month. For dust concentration of 0.15
mg/m3
• A wide range of optional accessories is available such as
high-efficiency filters.

• Outdoor air intake mode is


All-fresh (using outdoor air only) system Return + Outdoor air mixed system
useable as an outdoor-air Outside Outside
Circulated air

Air Air
processing airconditioner. conditioning conditioning
*When using the unit as an outdoor-air
processing unit, there are some restrictions.
Outdoor air Outdoor air
introduction introduction

* Air introduced from the outside and circulated air must be mixed in the
air conditioner primary side before introduction into the air conditioner.

42
4-Way Flow Ceiling Suspended Type

FXUQ71A / FXUQ100A

This slim and stylish indoor unit achieves


optimum air distribution and can be installed
without a ceiling cavity.
• Unit body and suction panel
adopted round shapes and realized
a slim appearance design. The unit
can be used for various locations
such as the ceilings with no cavity
and bore ceilings.

• Flaps close automatically when the


unit stops, which gives a simple
appearance.

• Unified slim height of 198mm for all


models that gives the unified
impression even when models with 198mm
different capacities are installed in
the same area.
• Control of the airflow rate has been improved
• Built-in electronic expansion valve eliminates the need for a BEV from 2-step to 3-step control. Auto airflow rate
unit, which improves flexibility of installation. control can be selected with wired remote
controller BRC1E62.
Current model New model
• Energy efficiency has been improved, thanks to
the adoption of new heat exchanger with smaller
tubes, DC fan motor and DC drain pump motor.
BEV unit is BEV unit is • Drain pump is equipped as a standard accessory
not needed
and the lift height has been improved from
500mm to 600mm.
• With adoption of the individual flap control, airflow direction • Depending on the installation site requirements or
adjustment can be individually set for each air outlet. Five room conditions, 2-way, 3-way and 4-way
directions of airflow and auto-swing can be selected with discharge patterns are available.
wired remote controller BRC1E62, which realizes the
optimum air distribution.
VCXĝOV VCXĝOV

Individual airflow direction example case


Position 0 Position 2

Position 3 Swing

.SJCPGFVCXĝOV

43
VRV INDOOR UNIT

VRV Indoor Units


Clean Room Type Air Conditioner

FXBQ40/FXBQ50
FXBQ63/FXBPQ63

Suitable for hospitals and other clean spaces


Select the air flow system and installation
Easily provides the high cleanliness environment
method to match the layout and purpose of
required by various industries
the room
Daikin’s clean room air conditioners are specially designed Two types of clean room air conditioners are
to achieve an environment cleanliness class 10,000. available – an integrated unit model and a
These air conditioners easily realize a cleanliness - class separate outlet unit model. It is also possible to
environment and help create a proper environment of configure the air flow system to ceiling intake or
hospitals, food and beverage factories, electronics factories floor-level intake according to the panel selected.
and other spaces that require clean air. This flexible design enables the air conditioner to
easily adopt to any room layout or use.

Instances of installation by type (for a hospital)

Type Ceiling intake type Floor-level intake type


(high speed contracted flow/high ceiling model) (gentle wind distribution/high cleanness class model)

Construction work is simple and a ceiling installation is possible. Easy to increase the cleanness and air-conditioning effect.
Features
Dust filtering and air-conditioning can be started immediately. A low flow speed prevents drying of the affected part and the experience of drafts.

Cleanness class*1 100,000 to 10,000 10,000

Wind speed 1.0m/s or higher Approximately 0.5m/s

• Concentrated air conditioning centered • Total air conditioning with an emphasis


directly under the unit on cleanliness
• Easy installation Intake
Integrated (sourced locally)
outlet unit
model

Applications: Surgery prep rooms, recovery rooms, nurse stations, etc. Applications: Operating theatres, delivery rooms, etc.
Blow
method
• Somewhat concentrated air conditioning • Total air conditioning with an emphasis
centered directly under the outlet on cleanliness
• Can provide air conditioning in rooms • Maintenance possible from a different
Outlet Air
Separate with irregular shapes unit conditioner room Intake
outlet unit (sourced locally)
model

Applications: CCU*2, sterile rooms, etc. Applications: Premature nurseries, newborn nurseries, ICU*3, etc.

*1. Cleanliness class. A scale expressing the cleanliness of air established by NASA (National Aeronautics and Space Administration). Class 10,000 represents a state of less than 10,000 minute particles of diameter under 0.5 μm per cubic foot.
For comparison, the cleanliness of a typical office is around class 1,000,000.
*2. CCU (Cardiac Care Unit). A ward dedicated to the admission of patients with myocardial infarctions and other heart diseases.
*3. ICU (Intensive Care Unit). A ward for the careful treatment and nursing of patients with serious illnesses, injuries, or recovering from operations.

Can be easily installed in Prevents uncomfortable drafts with a low


existing buildings flow speed of approximately 0.5m/s
A simple structure makes it easy to The floor-level intake system has a low
realize a highly clean environment with flow speed of approximately 0.5 m/s,
the same installation work as for a improving dust filtration and eliminating • Air flow distribution diagram
(operating theatre)
typical air conditioner. Can be easily the feeling of drafts. Broadly Outlet (m3/sec)
3m 0.6
installed in new buildings, existing air-conditions the room with a gentle
0.5
structures and refurbishments. air flow and creates a comfortable 0.4
environment. 0.3
0.2
Intake
0.1
*Analysis of the floor-level intake type 0 0
with the integrated outlet model. 3m 0 Operating Intake 3m
table

44
Filtration FXB(P)Q-P
Class 10,000 clean room condition achieved with a
HEPA filter (sold separately)
The low pressure-loss HEPA filter (sold separately) demonstrates superior
dust filtering performance and easily accomplishes an air cleanliness of
class 10,000.
The HEPA filter has a structure • HEPA filter
incorporating a pleated glass fibre filter
medium, making it highly efficient and
suitable for clean rooms, etc.
Installation example (in a medical facility)
*It may not be possible to maintain cleanliness in rooms with low air tightness.

Antibacterial
Suppresses the propagation of bacteria in the duct with a proprietary antibacterial coating.
The filter implements an antibacterial treatment with a new coating, combining a silver-based inorganic antibacterial material
(an organic antibacterial material that is effective against germs) that prevents mould. This enhances the antibacterial properties of the duct.
An antibacterial treatment using a silver-based organic substance reduces mould.

Antibacterial fibre used in the intake filter.


With a long-life filter employing anti-mould antibacterial fibre near the intake, cleaning performance is further enhanced.

Fan

* Please be aware that antibacterial products suppress the propagation of bacteria but do not have a sterilising
effect. Also, mould may grow in places where dust or soot accumulates.
* A material for which the registered safety was verified by Japanese chemicals and dangerous substances
regulation law
(Act on the Evaluation of Chemical Substances and Regulation of Their Manufacture, etc.) is used for the
antibacterial material.
Outlet panel HEPA filter Sheet steel Intake panel * Periodic maintenance is required (such as cleaning the air filter and washing the inside to the unit).
(punched) drain pan (punched)
(antibacterial treated)

Labour-saving
Filter maintenance unnecessary for about five years
Easy access from underneath unit provides easy maintenance.
The HEPA filter has an exceptionally long life and does not require maintenance
· HEPA filter · Fan · Drip pan inspection
for about five years. Daikin has aimed to reduce maintenance work from a variety
replacement inspection · Pre-filter replacement
of perspectives, including a service access system that eliminates the necessity for
service panels.

*The maintenance period differs significantly according to the cleanliness of the room and hours of air conditioner operation.

Quiet
All models incorporate an industry-leading quiet design, operating at under 41dB.
Operating noise is substantially reduced by employing a proprietary double-structure outlet filter chamber, sound absorbing
insulation and a low pressure-loss HEPA filter. Sound level of all models are under 41dB (38dB during low-fan speed operation).

*Operating noise may be greater than these values in highly reflective locations.

45
VRV INDOOR UNIT

VRV Indoor Units


Multi Cube (Spot AC) type for VRV system

FXPQ25AVM New

Personal air comfort delivered to large spaces


Even in large spaces, Daikin ensures individual air comfort for each person. Our compact Spot Air Conditioner was created to serve
individual air conditioning needs in large spaces. Compared to commercial buildings and offices, air conditioning factories and other
large spaces used to be extremely difficult. With this Spot Air Conditioner, temperatures can now be individually adjusted for a
comfortable work environment to suit each person.

Wind Wind  ;OPZJVTWHYLZ[OLKPZ[HUJLPU^OPJOHPYMSV^[YH]LSZMYVT[OL


travel distance velocity
HPYV\[SL[H[^PUK]LSVJP[`VMTZ^P[O[OLKPZ[HUJL[OH[HPYMSV^
30% *1 20% *2
[YH]LSZMVY[OLJVU]LU[PVUHS-?78(=5
increase increase in  ;OPZPZHJVTWHYPZVUVM^PUK]LSVJP[`
K\YPUNKPYLJ[HPYMSV^ K\YPUNK\J[JVUULJ[PVU
^P[O[OLJVUULJ[LK[VH½K\J[

Delivering greater comfort by


DGRSWLQJDKLJKHIÀFLHQF\'&PRWRU
and optimizing the shape of the air
discharge grille.

Flexible installation corresponds to


site conditions. With temperature
control available for each unit, air
conditioning adjusts to individual
preferences for personal air comfort.

Different types of installation possible

Suspended Rested
• Stand installation • Direct installation
(stand sold separately)

Installation examples at Daikin’s Sakai and Rinkai plants

Versatile installation options enable free layout

Because VRV systems allow use of long refrigerant piping, unit


layout is flexible and can be freely designed to fit large spaces.
Not only does this make ductwork unnecessary, it simplifies
installation and enables easy unit relocation in the future.
Installation costs are also greatly reduced.

Layout with new type


indoor unit

Conventional ducted Actual piping length


air conditioning system
max. 165 m
No ducts Total piping length
required! max. 1,000 m

46
Adjustable comfort for
Easy relocation/expansion individual users
Only requirement is connection to preinstalled Shut-off Valve Each Spot Air Conditioner can be controlled with a
kit for additional indoor units (Option). dedicated wired remote controller. Individual users
can set the temperature and
airflow volume.

Shut-off Valve kit for additional indoor unit (Option)  Moreover, since each unit
can be turned ON and OFF,
it is possible to reduce power
consumption resulting from
unnecessary operation and
to eliminate associated costs.
*3. Please contact your local
sales representative for
details on the Shut-off
Valve kit for additional
indoor units (Option).

Delivering comfort with a large volume of air

The large propeller fan provides a gentle, comfortable breeze and greater wind volume.
Additionally, by installing an optional air discharge adaptor and straightening plate, strong airflow can be achieved that
extends even further.


Comfort for people nearby Standard type Comfort for people far away Long-distance type

Wind velocity distribution map (horizontal section) Wind velocity distribution map (horizontal section)
 
A gentle breeze Strong airflow
T covers delivers comfort
T
the work area

 
       T        T
<Conditions> Cooling operation, high airflow volume, 60 Hz
* Distribution map for direct airflow volume Air discharge adaptor *6. Installation of the optional items "air
(KDF87C28) discharge adaptor (KDF87C28)" and
"straightening plate for air discharge adaptor
        TZ Straightening plate for (KPW87A28)" is necessary.
air discharge adaptor
(KPW87A28)

Designed for installation in any environment

Withstands oil mists Condensation suppression Fan /Motor

For the heat exchanger cooling pipe, a To minimize condensation, the air duct Air duct / Blowout tube
material with 3 to 6 times*7 the durability and blowout tubes are double Double insulation structure
of standard materials has been selected. insulated. This enables use in kitchens
and other highly humid environment.
The fan and
motor can be
replaced from
Leakage failsafe Simple maintenance the front.

An emergency reservoi Easy maintenance design


is fitted in the underframe beneath the includes front access for Bottom frame
drain pan. This provides reassuring fan motor replacement. Emergency structure
backup against drain pan overflow.
Heat exchanger
About 3 to 6 times more durable

47
SPECIFICATIONS

48
SPECIFICATIONS

VRV Indoor Units


Ceiling Mounted Cassette Round Flow & Round Flow with Sensing (Optional)

MODEL FXFSQ25ARV16 FXFSQ32ARV16 FXFSQ40ARV16 FXFSQ50ARV16 FXFSQ63ARV16 FXFSQ80ARV16 FXFSQ100ARV16 FXFSQ125ARV16 FXFSQ140ARV16
Power supply 1-phase, 220-240V, 50Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 54,600 54,600
Heating capacity
kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 16.0
Casing Galvanised steel plate
m3/min 13/12.5/11.5/11/10 17/13.5/12.5/12/11 23/20.5/19/14.5/11 23.5/21/20/16/13.5 24.5/22/20.5/20/15 33.5/30.5/27/23.5/21 34.5/31.5/28.5/25.5/23 35.5/32.5/29.5/26.5/23
Airflow rate (H/HM/M/ML/L)
cfm 459/441/406/388/353 600/477/441/424/388 812/724/671/512/388 830/742/706/565/477 865/777/724/706/530 1,183/1,077/954/830/742 1218/1112/1006/901/812 1,254/1,148/1,042/936/812
Sound level (H/HM/M/ML/L) dBA 30/29.5/28.5/28/27 35/29.5/29/28/27 38/35/34.5/29.5/27 38/36/35.5/31.5/28 39/37/36/35.5/31 44/41/38/35/33 45/42.5/39.5/37/35 46/43.5/40.5/38/35
Dimensions (H×W×D) mm 256×840×840 298×840×840
Machine weight kg 19 22 25 26
Liquid (Flare) ø 6.4 ø 9.5
Piping
Gas (Flare) mm ø 12.7 ø 15.9
connections Drain VP25 (External Dia, 32/Internal Dia, 25)
Standard Model BYCQ125EAF6 (Fresh White)
panel (Non mm
Dimensions (HxWxD) 50x950x950
sensing)
(White) Weight kg 5.5
Sensing Model BYCQ140EEF6 (Fresh White)
panel Dimensions (HxWxD) mm 50x950x950
(White) Weight kg 5.5

Note: Specifications are based on the following conditions;

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

Decoration Panel (Option) ROUND FLOW TYPE


FXFSQ-A
MODEL BYCQ125EAF6 (Fresh White ) / BYCQ125EAK (Black)
For More information
Standard
Dimensions (H×W×D) mm 50×950×950
'Scan Me'
panel
Weight kg 5.5
Model BYCQ140EEF6 (Fresh White ) / BYCQ125EEK
Sensing
panel Dimensions (H×W×D) mm 50×950×950
Weight kg 5.5
Model BYCQ125EAPF (Fresh White)
Designer
panel Dimensions (H×W×D) mm 97×950×950
Weight kg 6.5

Auto Model BYCQ125EASF (Fresh White)


grille Dimensions (H×W×D) mm 105×950×950
panel
Weight kg 8

Standard panel Standard panel Designer panel


BYCQ125EAF6 (Fresh White) BYCQ125EAK (Black) BYCQ125EAPF (Fresh White)

Sensing panel Sensing panel


Auto grille panel*2
BYCQ140EEF6 (Fresh White) BYCQ125EEK (Black)
BYCQ125EASF (Fresh White)

Note: When opting Black panel, wireless remote controller model will be BRC7M634K

49
SPECIFICATIONS

VRV Indoor Units


Ceiling Mounted Cassette (Compact Multi-Flow) Type

MODEL FXZQ20AVM FXZQ25AVM FXZQ 32AVM FXZQ40AVM FXZQ50AVM

Power supply 1-Phase, 220-240 V, 50Hz

Btu/h 7,500 9,600 12,300 15,400 19,100


Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Btu/h 8,500 10,900 13,600 17,100 21,500
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3
Casing Galvanised steel plate
m³/min 8.7/7.5/6.5 9.0/8.0/6.5 10.0/8.5/7.0 11.5/9.5/8.0 14.5/12.5/10.0
Airflow rate (H/M/L)
cfm 307/265/229 318/282/229 353/300/247 406/335/282 512/441/353

Sound level (H/M/L) dBA 32.0/29.5/25.5 33.0/30.0/25.5 33.5/30.0/26.0 37.0/32.0/28.0 43.0/40.0/33.0


Dimensions (H×W×D) mm 260×575×575 (For depth add 63mm for electrical box)
Machine weight kg 15.5 16.5 18.5
Liquid (Flare) φ6.4
Piping
Gas (Flare) mm φ12.7
connections
Drain VP20 (External Dia. 26/Internal Dia. 20)

Note: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Ceiling Mounted Cassette (Double Flow) Type

MODEL FXCQ25AVM FXCQ32AVM FXCQ40AVM FXCQ50AVM FXCQ63AVM FXCQ80AVM FXCQ125AVM


Power supply 1-phase, 220-240 V/50 Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 47,800
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 14.0
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 54,600
Heating capacity
kW 3.2 4.0 5.0 6.3 8.0 10.0 16.0
Casing Galvanised steel plate
m3/min 11.5/10.5/9.5/8.5/8 12/11/10.5/9.5/8.5 15/14/13/11.5/10.5 16/15/14/12.5/11.5 26/24/22.5/20.5/18.5 32/29.5/27.5/25/22.5
Airflow rate (HH/M/L)
cfm 406/371/335/300/282 424/388/371/335/300 530/494/459/406/371 565/530/494/441/406 918/847/794/724/653 1130/1041/971/883/794
Sound level (H/L) 220 V dBA 34/33/31/30/29 34/33/32/31/30 36/35/33/32/31 37/36/35/33/31 39/38/37/35/32 42/40/38/36/33 46/44/42/40/38
Dimensions (H×W×D) mm 305x775x620 305x990x620 305x1,445x620
Machine weight kg 19 22 25 33 38
Liquid (Flare) ø6.4 ø9.5
Piping Gas (Flare) mm ø12.7 ø15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25)
Model BYBCQ40CF BYBCQ63CF BYBCQ125CF

Panel Colour Fresh white (6.5Y 9.5/0.5)


(Option) Dimensions(H×W×D) mm 55x1,070x700 55x1,285x700 55x1,740x700
Weight kg 10 11 13

50
Ceiling Mounted Cassette Corner Type

MODEL

Fuse
BYKQ63AHW / BYKQ63AHS / BYKQ63AW
White / Silver
41 x 1390 x 595

6.6

51
SPECIFICATIONS

VRV Indoor Units


Ceiling Mounted Cassette Corner Type

MODEL

BYKQ63AHW / BYKQ63AHS / BYKQ63AW


White / Silver
41 x 1390 x 595

6.6

52
Slim Ceiling Mounted Duct Type (700 mm width type)

MODEL with drain pump FXDQ20PDV36 FXDQ25PDV36 FXDQ32PDV36


Power supply 1-phase, 220-240 V/220 V, 50 Hz
Btu/h 7,500 9,600 12,300
Cooling capacity
kW 2.2 2.8 3.6

Btu/h 8,500 10,900 13,600


Heating capacity
kW 2.5 3.2 4.0
Casing Galvanised steel plate
m3/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Airflow rate (HH/H/L)
cfm 282/254/226 282/254/226 282/254/226
External static pressure Pa 30-102
Sound level (HH/H/L) 13 dBA 33/31/29 33/31/29 33/31/29
Dimensions (H×W×D) mm 200×700×620 200×700×620 200×700×620
Machine weight kg 23.0 23.0 23.0
Liquid (Flare) ø 6.4 ø 6.4 ø 6.4
Piping
Gas (Flare) mm ø 12.7 ø 12.7 ø 12.7
connections
Drain VP20 (External Dia, 26/Internal Dia, 20)

53
SPECIFICATIONS

VRV Indoor Units

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)

MODEL with drain pump FXDQ40NDV36 FXDQ50NDV36 FXDQ63NDV36


Power supply 1-phase, 220-240 V/220 V, 50 Hz
Btu/h 15,400 19,100 24,200
Cooling capacity
kW 4.5 5.6 7.1

Btu/h 17,100 21,500 27,300


Heating capacity
kW 5.0 6.3 8.0
Casing Galvanised steel plate
m3/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L)
cfm 371/335/300 441/388/353 583/512/459
External static pressure Pa 44-152
Sound level (HH/H/L) *1*3 dBA 34/32/30 35/33/31 36/34/32
Dimensions (H×W×D) mm 200×900×620 200×900×620 200×1,100×620
Machine weight kg 27.0 28.0 31.0
Liquid (Flare) ø 6.4 ø 6.4 ø 9.5
Piping
Gas (Flare) mm ø 12.7 ø 12.7 ø 15.9
connections
Drain VP20 (External Dia, 26/Internal Dia, 20)

Note: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
* 1: Values are based on the following conditions: FXDQ-P: external static pressure of 10 Pa; FXDQ-N: external static pressure of 15 Pa.
* 2: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard".
(Factory setting is 10 Pa for FXDQ-P models and 15 Pa for FXDQ-N models.)
* 3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dBA.

Mid Static Pressure Ceiling Mounted Duct Type

MODEL with drain pump FXMQ40ARV16 FXMQ50ARV16 FXMQ63ARV16 FXMQ80ARV16 FXMQ100ARV16


Power supply 1-phase, 220-240 V, 50 Hz
Btu/h 15,400 19,100 24,200 30,700 38,200
Cooling capacity
kW 4.5 5.6 7.1 9.0 11.2
Btu/h 17,100 21,500 27,300 34,100 42,700
Heating capacity
kW 5.0 6.3 8.0 10.0 12.5
Casing Galvanized Steel Plate
m3/min 15/12 19/16 24/20 30/25 34/29
Airflow rate (HH/H/L)
cfm 530/425 671/565 848/706 1060/883 1200/1024
External static pressure Pa 30-50 30-60
Sound level (H/L) dBA 39/37 41/39 42/40 43/41 44/42
Dimensions (H×W×D) mm 300x700x700 300x1000x700
Machine weight kg 27 28 35 36

Liquid (Flare) 6.4 (Flare Connection) 9.5 (Flare Connection)


Piping 12.7 (Flare Connection) 15.9 (Flare Connection)
Gas (Flare) mm
connections
Drain VP25 (External Dia. 32, Internal Dia. 25

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

54
Ceiling Mounted Duct Type
0.8TR 1.025
1.2
MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PBV36 FXMQ50PBV36

Power supply 1-phase, 220-240 V/220 V, 50 Hz


Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Btu/h 8,500 10,900 13,600 17,100 21,500
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3
Casing Galvanised steel plate

m3/min 9/7.5/6.5 9.5/8/7 16/13/11 18/16.5/15


Airflow rate (HH/H/L)
cfm 318/265/230 335/282/247 565/459/388 635/582/530
External static pressure Pa 30-100 (50) 2 30-160 (100) 2 50-200 (100) 2
Sound level (HH/H/L) dBA 33/31/29 34/32/30 39/37/35 41/39/37
Dimensions (H×W×D) mm 300X550X700 300X700X700 300X1,000X700
Machine weight kg 25 27 35
Liquid (Flare) ø 6.4
Piping
connections
Gas (Flare) mm ø 12.7
Drain VP25 (External Dia, 32/Internal Dia, 25)

2.01 2.55 3.18 3.98 4.55


MODEL FXMQ63PBV36 FXMQ80PBV36 FXMQ100PBV36 FXMQ125PBV36 FXMQ140PBV36

Power supply 1-phase, 220-240 V/220 V, 50 Hz

Btu/h 24,200 30,700 38,200 47,800 54,600


Cooling capacity
kW 7.1 9.0 11.2 14.0 16.0
Btu/h 27,300 34,100 42,700 54,600 61,400
Heating capacity
kW 8.0 10.0 12.5 16.0 18.0
Casing Galvanised steel plate

m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32


Airflow rate (HH/H/L)
cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
External static pressure Pa 50-200 (100) 2 50-200 (100) 2 50-140 (100) 2
Sound level (HH/H/L) dBA 42/40/38 43/41/39 43/41/39 44/42/40 46/45/43
Dimensions (H×W×D) mm 300x1,000x700 300x1,400x700
Machine weight kg 35 45 46
Liquid (Flare) 9.5
Piping
Gas (Flare) mm 15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25)

Note: Specifications are based on the following condi3tions


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
 1: Power consumption values are based on conditions of rated external static pressure.
  2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50-125P) or
ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static pressure is 50 Pa
for FXMQ20-32P and 100 Pa for FXMQ40-140P

55
SPECIFICATIONS

VRV Indoor Units


Ceiling Mounted Duct Type

MODEL FXMQ170NVE6 FXMQ200NVE6 FXMQ250NVE6


Power supply 1-phase, 220, 240 V/220 V, 50 Hz
Btu/h 65,800 76,400 95,500
Cooling capacity
kW 19.3 22.4 28
Btu/h 71,600 83,300 1,07,500
Heating capacity
kW 21 25 31.5

Casing Galvanised steel plate


m3/min 58/50 68/58 80/73
Airflow rate (H/L)
cfm 2,047/1,765 2400/2,047 2,825/2,578
External static pressure Pa 100-140 2 100-200 2 190-270 2
Sound level (H/L) 220V dBA 45/42 47/45 49/47
Dimensions (H×W×D) mm 440x1,190x1,090 440x1,490x1,090
Machine weight kg 110 130
Liquid (Flare) ø 9.5
Piping Gas (Flare) mm ø 19.1 ø 22.2
connections
Drain External Dia 32

Ceiling Suspended Type

MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE FXHQ125AVM FXHQ140AVM


Power supply 1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 12,300 24,200 38,200 48,000 52,900
Cooling capacity
kW 3.6 7.1 11.2 14.1 15.5
Btu/h 13,600 27,300 42,700 54,600 58,000
Heating capacity
kW 4.0 8.0 12.5 16.0 17.0
m3/min 12/-/10 17.5/-/14 25/-/19.5 34/26/20 36/27/20
Airflow rate (H/M/L)
cfm 424/-/353 618/-/494 883/-/688 1,200/918/706 1,271/953/706
Sound level (H/M/L) dBA 36/-/31 39/-/34 45/-/37 46/41/37 48/42/37
Dimensions (H×W×D) mm 195×960×680 195×1,160×680 195×1,400×680 235×1,590×690
Machine weight kg 24 28 33 41
Liquid (Flare) 6.4 9.5
Piping mm
connections Gas (Flange) 12.7 15.9
Drain VP20 (External Dia. 26/Internal Dia. 20)

Note: Specifications are based on the following conditions


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
 1: Power consumption values are based on conditions of standard external static pressure.
 2: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure".

56
4-way Flow Ceiling Suspended Type

MODEL FXUQ71AVEB FXUQ100AVEB


Power supply 1-phase, 220-240 V/220-230V, 50 Hz
Btu/h 27,300 38,200
Cooling capacity
kW 8.0 11.2
Btu/h 30,700 42,700
Heating capacity
kW 9.0 12.5
Casing Fresh white
m3/min 22.5/19.5/16 31/26/21
Airflow rate (H/L)
cfm 794/688/565 1,094/918/741
Sound level (H/M//L) dBA 40/38/36 47/44/40
Dimensions (H×W×D) mm 198×950×950
Machine weight kg 26 27
Liquid (Flare) 9.5
Piping
Gas (Flare) mm 15.9
connections
Drain VP20 (External Dia, 26/Internal Dia, 20)

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Wall Mounted Type

MODEL FXAQ20ARVE6 FXAQ25ARVE6 FXAQ32ARVE6 FXAQ40ARVE6 FXAQ50ARVE6 FXAQ63ARVE6

Power supply 1-phase, 220 V/220 V, 50 Hz


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3 8.0
Casing White (N9.5)
m3/min 7.5/4.5 9/5 11/5.5 13/9 15/12 19/14
Airflow rate (H/L)
cfm 265/159 318/177 388/194 459/318 530/424 671/494

Sound level (H/L) dBA 35/31 36/31 38/31 39/34 42/37 47/41

Dimensions (H×W×D) mm 298×929×258


Machine weight kg 13.0
Liquid (Flare) ø 6.4 ø 9.5
Piping
connections
Gas (Flare) mm ø 12.7 ø 15.9
Drain VP13 (External Dia, 18/Internal Dia, 13)

57
SPECIFICATIONS

VRV Indoor Units

Floor Standing Type/Concealed Floor Standing Type

FXLQ32MAVE8 FXLQ50MAVE8 FXLQ63MAVE8


MODEL
FXNQ32MAVE8 FXNQ50MAVE8 FXNQ63MAVE8
Power supply 1-phase, 220-240 V/220 V, 50 Hz
FXLQ
Btu/h 12,300 19,100 24,200
Cooling capacity
kW 3.6 5.6 7.1
Btu/h 13,600 21,500 27,300
Heating capacity
kW 4.0 6.3 8.0

Casing FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate


FXNQ m3/min 8/6 14/11 16/12
Airflow rate (H/L)
cfm 282/212 494/388 565/424

Sound level (H/L) 220V dBA 35/32 39/34 40/35


FXLQ 600×1,140×222 600×1,420×222 600×1,420×222
Dimensions mm
(H×W×D) FXNQ 610×1,070×220 610×1,350×220 610×1,350×220
FXLQ 30.0 36.0 36.0
Machine weight kg
FXNQ 23.0 27.0 27.0
Liquid (Flare) ø 6.4 ø 6.4 ø 9.5
Piping mm
connections
Gas (Flare) ø 12.7 ø 12.7 ø 15.9
Drain 21O.D.

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level: (FXAQ-P) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Floor Standing Duct Type

MODEL FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY16

Power supply 3-phase 4-wire system, 380 -415 V, 50 Hz

Btu/h 47,800 76,400 95,500 1,54,000 1,91,000


Cooling capacity
kW 14.0 22.4 28.0 45.0 56.0
Btu/h 54,600 85,300 1,07,500 1,71,000 2,15,000
Heating capacity
kW 16.0 25.0 31.5 50.0 63.0
Casing colour Ivory white (5Y7.5/1)
Dimensions (HxWxD) mm 1670×750×510 1670×950×510 1670×1170×510 1900×1170×720 1900×1470×720
Machine weight kg 118 144 169 236 306
m3/min 43 69 86 134 172
Airflow rate
cfm 1,518 2,436 3,036 4,730 6,072
External static Pressure*2 Pa 152 217 281 420 390
Drive system Belt drive system
Air Filter Type Long-life filter (anti-mould resin net)

Sound level *1 dBA 52 56 60 65 66


Liquid (Flare) 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
Piping
Gas (Flare) mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)
connections
Drain Rp1 (PS 1B internal thread)

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dBA when the plenum chamber is installed to deliver direct airflow.
2: The value is the external static pressure with standard pulley.

58
Clean Room Type Air Conditioner

Type Integrated outlet unit model Separate outlet unit model


Indoor unit FXBQ40PVE FXBQ50PVE FXBQ63PVE FXBPQ63PVE
MODEL
Outlet unit Integrated with the indoor unit BAF82A63
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 15,400 19,100 24,200 24,200
Cooling capacity
kW 4.5 5.6 7.1 7.1
Power consumption kW 0.31 0.31 0.45 0.45
Intake filter efficiency *1 70% by gravimetric method
Outlet HEPA filter efficiency *2 99.97% by DOP method *5
Indoor unit weight kg 140 *3 185 *3 120 *6
Casing Galvanised steel plate
cfm 19.5/17.5 26/22.5
Airflow rate (H/L)
m3/min 688/618 918/794
Dimensions (H×W×D) mm 492×1,788×1,000 492×1,788×1,300 492×1,078×1,300
Outlet unit weight kg – 65 *3
Liquid (Flare) ø6.4 ø9.5
Piping mm ø12.7 ø15.9
Gas (Flare)
connections
Drain PT1B
Filter(Option) HEPA filter BAFH82A50 BAFH82A63
Panel Ceiling intake type Model BYB82A50C BYB82A63C BYB82A63CP
(Option) Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
*1: An intake air filter is only attached to the ceiling intake type.
*2: HEPA filter sold separately. The dust collection efficiency of HEPA filter is 99.97 %. However, air may slightly leak around the filter when installing.
*3: Weight including HEPA filter and panel.
*4: Anechoic chamber conversion value under JIS B 8616 test conditions. Value usually increases slightly in practice due to surrounding conditions.
*5 : The clean room air conditioner does not support DOP testing (leak test) based on GMP standards (Standards for Manufacturing Control and Quality Control for Medical
Devices) due to slight leakage at time of product installation.
*6: Weight including panel.

*In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build in redundancy with two or more
outdoor units.

Multi Cube (Spot AC) type)

MODEL FXPQ25AVM
Power Supply 1 Phase, 50Hz, 220-240 V
Cooling 2800
Capacity (watt)
Heating 3200
Dimension (HXWXD) mm 455X555X470
Casing Galvanised Steel plate
Type Propeller Fan

CMH 13.5 / 11.0


Airflow Rate (H/L)
Fan CFM 477 / 393
External Static Pressure PA 5
Drive Direct Drive
Sound Level dBA 51
Machine Weight Kg 30
Liquid Pipe mm 6.4mm dia (Flare Connection)
Piping Connections Gas Pipe mm 12.7mm dia (Flare Connection)
Drain Pipe mm (External dia 27.2mm, internal dia 21.6mm)
Refrigerant Control Electronic Expansion Valve
Air Filter Long Life Filter (Resin Net)

59
SPECIFICATIONS

Outdoor Units

VRV X (Cooling Only)

MODEL RXQ6ARY6(ES) RXQ8ARY6(ES) RXQ10ARY6(ES) RXQ12ARY6(ES) RXQ14ARY6(ES) RXQ16ARY6(ES)

Combination units – – – – – –

Power supply 3-phase, 380–415 V, 50 Hz


Btu/h 54,600 76,400 95,500 1,14,000 1,36,000 1,54,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 40.0 45.0
Capacity control % 25~100 20~100 13~100 12~100 11~100 10~100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
compressor 1 1 1 1 1 2

Airflow rate m³/min 119 178 191 257

Dimensions (H×W×D) mm 1,657X930X765 1,657X1,240X765

Machine weight kg 165 175 220 260


Sound level dBA 56 56 57 59 60 60

Operation
range
Cooling °CDB 10 ~ 49

Type R410A
Refrigerant
Charge kg 5.9 6.7 6.8 7.4 8.2

Liquid mm ø 9.5 ø 12.7


Piping
connections
Gas mm ø 19.1 ø 22.2 ø 28.6

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• (ES) for anticorrosion treated outdoor unit.

60
VRV X (Cooling Only)

MODEL RXQ18ARY6(ES) RXQ20ARY6(ES) RXQ22ARY6(ES) RXQ24ARY6(ES)


– – RXQ10ARY6(ES) RXQ12ARY6(ES)
Combination units – – RXQ12ARY6(ES) RXQ12ARY6(ES)
– – – –
Power supply 3-phase, 380–415 V, 50 Hz
Btu/h 1,71,000 1,91,000 2,10,000 2,29,000
Cooling capacity
kW 50.0 56.0 61.5 67.0
Capacity control % 10~100 7~100 6~100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
compressor 2 2 1+1 1+1

Airflow rate m³/min 257 297 178+191 191+191

Dimensions (H×W×D) mm 1,657X1,240X765 (1,657X930X765)+(1,657X930X765)

Machine weight kg 260 285 175+175


Sound level dBA 61 65 61 62
Operation
Cooling °CDB 10 ~ 49
range

Type R410A
Refrigerant
Charge kg 8.4 11.8 6.7+6.8 6.8+6.8

Liquid mm ø 15.9
Piping
connections
Gas mm ø 28.6 ø 34.9

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• (ES) for anticorrosion treated outdoor unit.

61
SPECIFICATIONS

Outdoor Units

VRV X (Cooling Only)

MODEL RXQ26ARY6(ES) RXQ28ARY6(ES) RXQ30ARY6(ES) RXQ32ARY6(ES) RXQ34ARY6(ES) RXQ36ARY6(ES)


RXQ12ARY6(ES) RXQ12ARY6(ES) RXQ12ARY6(ES) RXQ14ARY6(ES) RXQ16ARY6(ES) RXQ18ARY6(ES)
Combination units RXQ14ARY6(ES) RXQ16ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES)
– – – – – –
Power supply 3-phase, 380–415 V, 50 Hz
Btu/h 2,47,000 2,68,000 2,85,000 3,05,000 3,24,000 3,41,000
Cooling capacity
kW 73.5 78.5 83.5 90 95.0 100
Capacity control % 6~100 5~100 5~100 5~100 4~100 5~100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
1+1 1+2 1+2 1+2 2+2 2+2
compressors

Airflow rate m³/min 191+257 191+257 191+257 257+257 257+257 257+257

Dimensions (H×W×D) mm (1,657X1,240X765)+(1,657X1,240X765)


(1,657X930X765)+(1,657X1,240X765)

Machine weight kg 175+220 175+260 220+260 260+260


Sound level dBA 63 64

Operation
range Cooling °CDB 10 ~ 49

Type R410A
Refrigerant
Charge kg 6.8+7.4 6.8+8.2 6.8+8.4 7.4+8.4 8.2+8.4 8.4+8.4

Liquid mm ø 19.1 ø 19.1 ø 19.1 ø 19.1 ø 19.1 ø 19.1


Piping
connections
Gas mm ø 34.9 ø 34.9 ø 34.9 ø 34.9 ø 34.9 ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• (ES) for anticorrosion treated outdoor unit.

62
VRV X (Cooling Only)

RXQ38ARY6(ES) RXQ40ARY6(ES) RXQ42ARY6(ES) RXQ44ARY6(ES) RXQ46ARY6(ES) RXQ48ARY6(ES) RXQ50ARY6(ES)


RXQ18ARY6(ES) RXQ20ARY6(ES) RXQ12ARY6(ES) RXQ12ARY6(ES) RXQ14ARY6(ES) RXQ14ARY6(ES) RXQ14ARY6(ES)
RXQ20ARY6(ES) RXQ20ARY6(ES) RXQ12ARY6(ES) RXQ12ARY6(ES) RXQ14ARY6(ES) RXQ16ARY6(ES) RXQ18ARY6(ES)
– – RXQ18ARY6(ES) RXQ20ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES)
3-phase, 380–415 V, 50 Hz
3,62,000 3,82,000 3,99,000 4,20,000 4,40,000 4,57,000 4,78,000
106 112 117 123 129 134 140
4~100 3~100 4~100 3~100
Ivory white (5Y7.5/1)
Hermetically Sealed Scroll Type

2+2 1+1+2 1+2+2

257+297 297+297 191+191+257 191+191+297 257+257+257

(1,657X930X765)+ (1,657X1,240X765)+
(1,657X1,240X765)+ (1,657X930X765)+ (1,657X1,240X765)+
(1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)

260+285 285+285 175+175+260 175+175+285 220+220+260 220+260+260 220+260+260


66 68 65 67 65

10 ~ 49

R410A
8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 7.4+7.4+11.8 7.4+8.2+8.4 7.4+8.4+8.4

ø 19.1

ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• (ES) for anticorrosion treated outdoor unit.

63
SPECIFICATIONS

Outdoor Units

VRV X (Cooling Only)

MODEL RXQ52ARY6(ES) RXQ54ARY6(ES) RXQ56ARY6(ES) RXQ58ARY6(ES) RXQ60ARY6(ES)


RXQ16ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ20ARY6(ES)
Combination units RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ20ARY6(ES) RXQ20ARY6(ES)
RXQ18ARY6(ES) RXQ18ARY6(ES) RXQ20ARY6(ES) RXQ20ARY6(ES) RXQ20ARY6(ES)
Power supply 3-phase, 380–415 V, 50 Hz

Cooling capacity Btu/h 4,95,000 5,12,000 5,32,000 5,53,000 5,73,000


kW 145 150 156 162 168
Capacity control % 3~100 2~100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
compressors 2+2+2

Airflow rate m³/min 257+257+257 257+297+297

Dimensions (H×W×D) mm (1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)

Machine weight kg 260+260+260 260+260+285 260+285+285 285+285+285


Sound level dBA 65 66 68 69 70

Operation
range Cooling °CDB 10 ~ 49

Type R410A
Refrigerant
Charge kg 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8

Liquid mm ø 19.1
Piping
connections
Gas mm ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• (ES) for anticorrosion treated outdoor unit.

64
VRV X (Heat Pump)

MODEL RXYQ6ARY6 RXYQ8ARY6 RXYQ10ARY6 RXYQ12ARY6 RXYQ14ARY6 RXYQ16ARY6

Combination units – – – – – –

Power supply 3-phase, 380–415 V, 50 Hz


Btu/h 54,600 76,400 95,500 1,14,000 1,36,000 1,54,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 40.0 45.0
Btu/h 61,400 85,300 1,07,000 1,28,000 1,54,000 1,71,000
Heating capacity
kW 18.0 25.0 31.5 37.5 45.0 50.0
Capacity control % 25-100 20-100 13-100 12-100 11-100 10-100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
1 2
compressors

Airflow rate m³/min 119 178 191 257

Dimensions (H×W×D) mm 1,657X930X765 1,657X1,240X765

Machine weight kg 180 195 265


Sound level dBA 56 57 60

Operation Cooling °CDB -5 ~ 49


range Heating °CWB -20 ~ 15.5
Type R410A
Refrigerant
Charge kg 6.9 7.0 7.4 7.6 9.1 9.3

Liquid mm ø 9.5 ø 12.7


Piping
connections
Gas mm ø 19.1 ø 22.2 ø 28.6

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

65
SPECIFICATIONS

Outdoor Units

VRV X (Heat Pump)

MODEL RXYQ18ARY6 RXYQ20ARY6 RXYQ22ARY6 RXYQ24ARY6


– – RXYQ10ARY6 RXYQ12ARY6
Combination units – – RXYQ12ARY6 RXYQ12ARY6
– – – –
Power supply 3-phase, 380–415 V, 50 Hz
Btu/h 1,71,000 1,91,000 2,10,000 2,29,000
Cooling capacity
kW 50.0 56.0 61.5 67.0
Btu/h 1,91,000 2,15,000 2,35,000 2,56,000
Heating capacity
kW 56.0 63.0 69.0 75.0
Capacity control % 10-100 7-100 6-100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
compressors 2 1+1

Airflow rate m³/min 257 297 178+191 191+191

Dimensions (H×W×D) mm 1,657X1,240X765 (1,657X930X765)+(1,657X930X765)

Machine weight kg 285 305 195+195


Sound level dBA 61 65 61 62

Operation Cooling °CDB -5 ~ 49


range Heating °CWB -20 ~ 15.5
Type R410A
Refrigerant
Charge kg 11.8 7.4+7.6 7.6+7.6

Liquid mm ø 15.9
Piping
connections
Gas mm ø 28.6 ø 34.9

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

66
VRV X (Heat Pump)

MODEL RXYQ26ARY6 RXYQ28ARY6 RXYQ30ARY6 RXYQ32ARY6 RXYQ34ARY6 RXYQ36ARY6


RXYQ12ARY6 RXYQ12ARY6 RXYQ12ARY6 RXYQ16ARY6 RXYQ16ARY6 RXYQ16ARY6
Combination units RXYQ14ARY6 RXYQ16ARY6 RXYQ18ARY6 RXYQ16ARY6 RXYQ18ARY6 RXYQ20ARY6
– – – – – –
Power supply 3-phase, 380–415 V, 50 Hz
Btu/h 2,47,000 2,68,000 2,85,000 3,05,000 3,24,000 3,45,000
Cooling capacity
kW 73.5 78.5 83.5 90.0 95.0 101.0
Btu/h — 2,99,000 3,19,000 3,41,000 3,62,000 3,86,000
Heating capacity
kW 82.5 87.5 93.5 100.0 106.0 113.0
Capacity control % 5-100 4-100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor
No. of
1+2 2+2
compressors

Airflow rate m³/min 191+257 257+257 257+297

Dimensions (H×W×D) mm (1,657X1,240X765)+(1,657X1,240X765)


(1,657X930X765)+(1,657X1,240X765)

Machine weight kg 195+265 195+285 265+265 265+285 265+305


Sound level dBA 63 64 66

Operation Cooling °CDB -5 ~ 49


range
Heating °CWB -20 ~ 15.5

Type R410A
Refrigerant
Charge kg 7.6+9.1 7.6+9.3 7.6+11.8 9.3+9.3 9.3+11.8

Liquid mm ø 19.1
Piping
connections
Gas mm ø 34.9 ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

67
SPECIFICATIONS

Outdoor Units

VRV X (Heat Pump)

MODEL RXYQ38ARY6 RXYQ40ARY6 RXYQ42ARY6 RXYQ44ARY6


RXYQ18ARY6 RXYQ20ARY6 RXYQ12ARY6 RXYQ12ARY6
Combination units RXYQ20ARY6 RXYQ20ARY6 RXYQ12ARY6 RXYQ12ARY6
– – RXYQ18ARY6 RXYQ20ARY6
Power supply 3-phase, 380–415 V, 50 Hz

Btu/h 3,62,000 3,82,000 3,99,000 4,20,000


Cooling capacity
kW 106.0 112.0 117.0 123.0
Btu/h 4,06,000 4,30,000 4,47,000 4,71,000
Heating capacity
kW 119.0 126.0 131.0 138.0

Capacity control % 4 - 100 3 - 100 4 - 100 3 - 100


Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type

Compressor No. of
compressors 2+2 1+1+2

Airflow rate m³/min 257+297 297+297 191+191+257 191+191+297

(1,657X930X765)+
mm (1,657X1,240X765)+
Dimensions (H×W×D) (1,657X930X765)+
(1,657X1,240X765)
(1,657X1,240X765)

Machine weight kg 285+305 305+305 195+195+285 200+200+325


Sound level dBA 66 68 65 67

Operation Cooling °CDB -5 ~ 49


range Heating -20 ~ 15.5
°CWB
Type R410A
Refrigerant
Charge kg 11.8+11.8 7.6+7.6+11.8

Liquid mm ø 19.1
Piping
connections
Gas mm ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

68
VRV X (Heat Pump)

RXYQ46ARY6 RXYQ48ARY6 RXYQ50ARY6 RXYQ52ARY6 RXYQ54ARY6 RXYQ56ARY6 RXYQ58ARY6 RXYQ60ARY6


RXYQ14ARY6 RXYQ16ARY6 RXYQ16ARY6 RXYQ16ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ20ARY6
RXYQ16ARY6 RXYQ16ARY6 RXYQ16ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ20ARY6 RXYQ20ARY6
RXYQ16ARY6 RXYQ16ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ18ARY6 RXYQ20ARY6 RXYQ20ARY6 RXYQ20ARY6
3-phase, 380–415 V, 50 Hz

4,44,000 4,61,000 4,78,000 4,95,000 5,12,000 5,32,000 5,53,000 5,73,000


130.0 135.0 140.0 145.0 150.0 156.0 162.0 168.0
4,95,000 5,12,000 5,32,000 5,53,000 5,73,000 5,97,000 6,21,000 6,45,000
145.0 150.0 156.0 162.0 168.0 175.0 182.0 189.0

3 - 100 2 - 100
Ivory white (5Y7.5/1)
Hermetically Sealed Scroll Type

2+2+2

257+257+257 257+257+257 257+257+257 257+257+297 257+297+297 297+297+297

(1,657X1,240X765)+
(1,657X1,240X765)+ (1,657X1,240X765 + 1,657X1,240X765 + 1,657X1,240X765)
(1,657X1,240X765)

195+195+305 265+265+265 265+265+285 265+285+285 285+285+285 285+285+305 285+305+305 305+305+305


65 66 68 69 70
-5 ~ 49
-20 ~ 15.5
R410A
9.1+9.3+9.3 9.3+9.3+9.3 9.3+9.3+11.8 9.3+11.8+11.8 11.8+11.8+11.8

ø 19.1

ø 41.3

Note: Specifications are based on the following conditions:


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°WB, Equivalent piping length: 7.5m, Level difference: 0m.
• Sound level: Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

69
OUTDOOR UNIT
COMBINATIONS
& OPTIONS LIST

70
OUTDOOR UNIT COMBINATIONS

VRV X

Capacity Outdoor unit multi Total capacity index of Maximum number of


HP Model name Combination for cooling only Combination for heat pump
index connection piping kit *1 connectable indoor units*2 connectable indoor units*2

6 150 RX(Y)Q6A RXQ6A RXYQ6A — 75 to 195 (300) 9 (15)

8 200 RX(Y)Q8A RXQ8A RXYQ8A — 100 to 260 (400) 13 (20)


10 250 RX(Y)Q10A RXQ10A RXYQ10A — 125 to 325 (500) 16 (25)

12 300 RX(Y)Q12A RXQ12A RXYQ12A — 150 to 390 (600) 19 (30)


14 350 RX(Y)Q14A RXQ14A RXYQ14A — 175 to 455 (700) 22 (35)
16 400 RX(Y)Q16A RXQ16A RXYQ16A — 200 to 520 (800) 26 (40)
18 450 RX(Y)Q18A RXQ18A RXYQ18A — 225 to 585 (900) 29 (45)
20 500 RX(Y)Q20A RXQ20A RXYQ20A — 250 to 650 (1,000) 32 (50)
22 550 RX(Y)Q22A RXQ10A + RXQ12A RXYQ10A + RXYQ12A 275 to 715 (880) 35 (44)
24 600 RX(Y)Q24A RXQ12A x 2 RXYQ12A x 2 300 to 780 (960) 39 (48)
26 650 RX(Y)Q26A RXQ12A + RXQ14A RXYQ12A + RXYQ14A 325 to 845 (1,040) 42 (52)
28 700 RX(Y)Q28A RXQ12A + RXQ16A RXYQ12A + RXYQ16A 350 to 910 (1,120) 45 (56)
30 750 RX(Y)Q30A RXQ12A + RXQ18A RXYQ12A + RXYQ18A 375 to 975 (1,200) 48 (60)
BHFP22P1006
32 800 RX(Y)Q32A RXQ14A + RXQ18A RXYQ16A + RXYQ16A 400 to 1,040 (1,280) 52 (64)
34 850 RX(Y)Q34A RXQ16A + RXQ18A RXYQ16A + RXYQ18A 425 to 1,105 (1,360) 55 (64)
36 900 RX(Y)Q36A RXQ18A x 2 RXYQ16A + RXYQ20A 450 to 1,170 (1,440) 58 (64)
38 950 RX(Y)Q38A RXQ18A + RXQ20A RXYQ18A + RXYQ20A 475 to 1,235 (1,520) 61 (64)
40 1,000 RX(Y)Q40A RXQ20A x 2 RXYQ20A x 2 500 to 1,300 (1,600)
42 1,050 RX(Y)Q42A RXQ12A x 2 + RXQ18A RXYQ12A x 2 + RXYQ18A 525 to 1,365 (1,365)
44 1,100 RX(Y)Q44A RXQ12A x 2 + RXQ20A RXYQ12A x 2 + RXYQ20A 550 to 1,430 (1,430)
46 1,150 RX(Y)Q46A RXQ14A + RXQ14A + RXQ18A RXYQ14A + RXYQ16A + RXYQ16A 575 to 1,495 (1,495)
48 1,200 RX(Y)Q48A RXQ14A + RXQ16A + RXQ18A RXYQ16A x 3 600 to 1,560 (1,560)
50 1,250 RX(Y)Q50A RXQ14A + RXQ18A + RXQ18A RXYQ16A + RXYQ16A + RXYQ18A 625 to 1,625 (1,625)
BHFP22P1516 64 (64)
52 1,300 RX(Y)Q52A RXQ16A + RXQ18A × 2 RXYQ16A + RXYQ18A × 2 650 to 1,690 (1,690)
54 1,350 RX(Y)Q54A RXQ18A × 3 RXYQ18A × 3 675 to 1,755 (1,755)
56 1,400 RX(Y)Q56A RXQ18A × 2 + RXQ20A RXYQ18A × 2 + RXYQ20A 700 to 1,820 (1,820)
58 1,450 RX(Y)Q58A RXQ18A + RXQ20A × 2 RXYQ18A + RXYQ20A × 2 725 to 1,885 (1,885)
60 1,500 RX(Y)Q60A RXQ20A × 3 RXYQ20A × 3 750 to 1,950 (1,950)

Note: *1 For multiple connection of 22 HP systems and above, the outdoor unit multi connection piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double
outdoor units, and 130% for triple outdoor units. Refer to page 17 for notes on connection capacity of indoor units.

71
OPTION LIST

VRV Indoor Units


Ceiling Mounted Cassette Round Flow & Round Flow With Sensing (Optional)

FXFSQ25A FXFSQ50A FXFSQ100A


No. Item Type FXFSQ32A FXFSQ63A FXFSQ125A
FXFSQ40A FXFSQ80A FXFSQ140A
Fresh white BYCQ125EAF6 *
Standard panel
Black BYCQ125EAK *
Decoration Designer panel 1
Fresh white BYCQ125EAPF *
1
panel Auto grille panel 2,3
Fresh white BYCQ125EASF *
Fresh white BYCQ140EEF6 *
Sensing panel
Black BYCQ125EEK *
For usage of 3-4-way flow KDBH551C160
2 Sealing material of air discharge outlet 4

For usage of 2-way flow KDBH552C160


3 Panel spacer KDBP55H160FA
Chamber Without T-duct joint KDDP55B160 (Components: KDDP55C160-1, KDDP55B160-2) 8

4 Fresh air intake kit type 5,6 With T-duct joint KDDP55B160K (Components: KDDP55C160-1, KDDP55B160K2) 8

Direct installation type 7


KDDP55X160A
High-efficiency filter unit 9 (Colorimetric method 65%) KAFP556C80 KAFP556C160
5
(Including filter chamber) (Colorimetric method 90%) KAFP557C80 KAFP557C160
(Colorimetric method 65%) KAFP552B80 KAFP552B160
6 Replacement high-efficiency filter 9,10

(Colorimetric method 90%) KAFP553B80 KAFP553B160


7 Filter chamber KDDFP55C160
8 Replacement long-life filter KAFP551K160
9 Replacement long-life filter (Auto grille panel) KAFP551H160
10 Ultra long-life filter unit (Including filter chamber) 9
KAFP55C160
11 Replacement ultra long-life filter 9,10
KAFP55H160H
12 Branch duct chamber 4 KDJP55C80 KDJP55C160
13 Insulation kit for high humidity 9,11
KDTP55K80 KDTP55K160

Note:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate 2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and
may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when more fresh air is necessary.
8. Please order using the names of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
*These panels do not contain the sensing function.

Ceiling Mounted Cassette (Compact Multi Flow) Type


FOR UNIT MODEL
Grid ceiling panel BYFQ60CAW

Decoration panel BYFQ60B3W1*1

Relay wire harness adaptor for decoration panel* 1


BER01A1

Sensor kit for grid ceiling panel BRYQ60AAW

Sealing material for air discharge outlet BDBHQ44C60

Replacement long life filter KAF441C60

Fresh air intake kit KDDQ44XA60

Notes:
1. Option relay wire harness adaptor (BER01A1) is necessary when installing decoration panel (BYFQ60B3W1).
2. Installation box*2 is necessary for each adaptor marked +.
3. Up to 2 adaptors can be fixed for each installation box.
4. Only one installation box can be installed for each indoor unit.

72
Ceiling Mounted Cassette (Double Flow) Type

FXCQ32A
No. Item Type FXCQ25A FXCQ50A FXCQ63A FXCQ80A FXCQ125A
FXCQ40A

1 Decoration panel BYBCQ40CF BYBCQ63CF BYBCQ125CF


65% KAFP532B50 KAFP532B80 KAFP532B160
High efficiency filter1
90% KAFP533B50 KAFP533B80 KAFP533B160
2 Filter related
Filter chamber bottom suction KDDFP53B50 KDDFP53B80 KDDFP53B160
Long-life replacement filter KAFP531B50 KAFP531B80 KAFP531B160
3 Remote controller Wireless H/P BRC7M65
4 Navigation remote controller (Wired remote controller) BRC1E63

Note: 1 Filter chamber is required if installing high efficiency filter.

Ceiling Mounted Cassette Corner Type


MODEL
Item
FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16

BYKQ63AW (Surface Colour: White/ Base Colour: White)

Slim Ceiling Mounted Duct Type (700 mm width type)


No. Item Type FXDQ20PD FXDQ25PD FXDQ32PD

1 Insulation kit for high humidity KDT25N32

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


No. Item Type FXDQ40ND FXDQ50ND FXDQ63ND

1 Insulation kit for high humidity KDT25N50 KDT25N63

High Static Ceiling Mounted Duct Type


FXMQ20P FXMQ50PBV36 FXMQ100PBV36
No. Item Type FXMQ25P FXMQ40PBV36 FXMQ63PBV36 FXMQ125PBV36
FXMQ32P FXMQ80PBV36 FXMQ140PBV36
1 Drain pump kit —
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160
2 High efficiency filter
90% — KAF373AA56 KAF373AA80 KAF373AA160
3 Filter chamber — BDDF37A40~6 BDDF37A80~6 BDDF37A140~6
4 Long-life replacement filter — KAF371AA56 KAF371AA80 KAF371AA160
5 Long-life filter chamber kit — KAF375AA56 KAF375AA80 KAF375AA160
White — KTBJ25K56W KTBJ25K80W KTBJ25K160W
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
Brown — KTBJ25K56T KTBJ25K80T KTBJ25K160T
7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A

8 Suction flange — BDF37A40~6 BDF37A80~6 BDF37A140~6

73
OPTION LIST

VRV Indoor Units


Ceiling Suspended Type
No. Item Type FXHQ32MA FXHQ63MA FXHQ100MA

1 Drain pump kit KDU50N60VE KDU50N125VE


2 Replacement long-life filter (Resin net) KAF501DA56 KAF501DA80 KAF501DA112
3 L-type piping kit (for upward direction) KHFP5MA63 KHFP5MA160

Floor Standing Type/Concealed Floor Standing Type


No. Item Type FXLQ32MA/FXNQ32MA FXLQ50MA/FXNQ50MA FXLQ63MA/FXNQ63MA

1 Long-life replacement filter KAFJ361K45 KAFJ361K71

Mid Static Ceiling Mounted Duct Type


Duct Type
No. Item Type
FXMQ40ARV16, FXMQ50ARV16 FXMQ63ARV16, FXMQ80ARV16, FXMQ100ARV16
1 High efficiency filter 65% Type KAF372AA56 KAF372AA80
2 Filter chamber Type BDDF37A40~6 BDDF37A80~6
3 Long-life replacement filter Type KAF371AA56 KAF371AA80
BDF37A40~6 BDF37A80~6
4 Suction flange
KTBJ25K56W KTBJ25K80W
KTBJ25K56F KTBJ25K80F
5 Service panel
KTBJ25K56T KTBJ25K80T
6 Air discharge adaptor KDAJ25K56A KDAJ25K71A

Floor Standing Duct Type


No. Item Type FXVQ125N FXVQ200N FXVQ250N FXVQ400N FXVQ500N
1 Replacement long life filter KAFJ261M140 KAFJ261M224 KAFJ261M280 KAFJ261N450 KAFJ261N560
2 Ultra long-life filter — KAFSJ9A400 KAFSJ9A560
3 Filter chamber for high 65% KDDF-92A140 KDDF-92A200 KDDF-92A280 KDDF-92A400 KDDF-92A560
4 efficiency filter *1 90% KDDF-93A140 KDDF-93A200 KDDF-93A280 KDDF-93A400 KDDF-93A560
Discharge and Suction

5 Front suction filter Front suction base flange KD-9A140 KD-9A200 KD-9A280 KD-9A400 KD-9A560
6 chamber for high Suction grille KDGF-9A140 KDGF-9A200 KDGF-9A280 KDGF-9A400 KDGF-9A560
7 efficiency filter Replacement Long-life filter *3 KAF-91B140 KAF-91B200 KAF-91B280 KAF-91B400 KAF-91B560
8 filter *2 High efficiency 65% KAF-92B140 KAF-92B200 KAF-92B280 KAF-92B400 KAF-92B560
9 filter 90% KAF-93B140 KAF-93B200 KAF-93B280 KAF-93B400 KAF-93B560
10 Plenum chamber *4 KPCJ140A KPC5J KPC8J KPCJ400A KPC15JA
11 Pulley for plenum chamber *4 KPP8JA KPP9JA KPP10JA —
12 Fresh air intake kit KD106D10 KDFJ906A560
13 Rear suction kit KDFJ905A140 KDFJ905A200 KDFJ905A280 KDFJ905A400 KDFJ905A560
14 Discharge grille for plenum side KD101A10 KD101A20
15 Wood base KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15
16 Vibration isolating frame K-ABSG1406A K-ABSG1407A K-ABSG1408A K-ABSG1409A K-ABSG1410A

*1 A front suction base flange and suction grille are required (option). *2 A filter chamber for high efficiency is required (option).
*3 Different from the filter attached as standard. *4 Use the plenum chamber and pulley for plenum chamber in combination.

Clean Room Air Conditioner


No. Item Type FXBQ40PVE FXBQ50PVE FXBQ63PVE FXBPQ63PVE
1 Outlet unit – BAF82A63
2 Filter HEPA filter BAFH82A50 BAFH82A63
3 Ceiling intake type BYB82A50C BYB82A63C BYB82A63CP
Panel
4 Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP
5 Outside air intake duct flange KDFJ82A80

74
VRV X
RX(Y)Q6ARY6
RX(Y)Q14ARY6
Optional Accessories RX(Y)Q8ARY6 RX(Y)Q12ARY6
RX(Y)Q16ARY6
RX(Y)Q10ARY6

KHRP26M22H,
Distributive (Max. 4 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H
REFNET header
piping KHRP26M33H (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
(Max. 8 branch)

REFNET joint KHRP26A22T KHRP26A22T, KHRP26A33T, KHRP26A72T


KHRP26A33T

RX(Y)Q18ARY6
Optional Accessories
RX(Y)Q20ARY6

KHRP26M22H, KHRP26M33H, KHRP26M72H


Distributive REFNET header
(Max.4 branch) (Max.8 branch) (Max.8 branch)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T

RX(Y)Q26ARY6 RX(Y)Q34ARY6
RX(Y)Q28ARY6 RX(Y)Q36ARY6
Optional Accessories RX(Y)Q22ARY6 RX(Y)Q24ARY6 RX(Y)Q30ARY6 RX(Y)Q38ARY6
RX(Y)Q32ARY6 RX(Y)Q40ARY6

KHRP26M22H
(Max.4 branch),
KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header
(Max.8 branch), (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Distributive KHRP26M72H
piping (Max.8 branch),

KHRP26A22T,
REFNET joint KHRP26M33T, KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26M72T,

Pipe size reducer — KHRP26M73TP, KHRP26M73HP


Outdoor unit connection piping kit BHFP22P1006

RX(Y)Q46ARY6
RX(Y)Q48ARY6
RX(Y)Q50ARY6
RX(Y)Q42ARY6 RX(Y)Q52ARY6
Optional Accessories
RX(Y)Q44ARY6 RX(Y)Q54ARY6
RX(Y)Q56ARY6
RX(Y)Q58ARY6
RX(Y)Q60ARY6

KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H


Distributive REFNET header
(Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit connection piping kit BHFP22P1516

75
CONTROL
SYSTEMS

76
OFFICE | HOME | HOTEL

Reiri for Office is the ideal building management solution for all sizes of commercial
[nbe]bg`l%^li^\bZeer_hklfZeemhf^]bnf&lbs^][nbe]bg`l%k^`Zk]e^llh_eh\Zmbhg'Mabl
smart building solution provides affordable and scalable building control and energy
management, allowing users greater control and automation of building utilities such as
Zbk&\hg]bmbhgbg`Zg]eb`ambg`%Zg]mhfhgbmhkZg]fZgZ`^^g^k`ri^k_hkfZg\^Zg]
indoor air quality.

Expanded Features

Reiri for Office Reiri for Office Reiri for Office


DCPF01 Controller Extension Multisite Extension
DCPF05 DCPF10

Reiri for Home is the complete smart home solution with seamless integration
capabilities, allowing users to control and monitor all smart home devices
conveniently from just a single mobile app. From security and safety
enhancements to indoor air quality and energy management, Reiri for Home is the
ideal home automation system for every homeowner.

R i i for
Reiri f Home
H Reiri for Home
DCPH01 Lite Version
DCPH02

K^bkb_hkAhm^e^__^\mbo^erlZo^l^g^k`rZg]\hlmpabe^ikbhkbmbsbg``n^lml\hf_hkmZg]
satisfaction. With this smart hotel solution, energy consumption is optimised without
\hfikhfblbg`hgma^`n^lmlbg&khhf\hf_hkm'Ahm^efZgZ`^klZg]lmZ__Zk^ZelhZ[e^
to conveniently monitor the status and manage the settings of every room.

Reiri for Hotel Reiri for Resort


DCPL01 DCPR01

77
CONNECTABLE
Various types of equipment in a building
can be controlled by a single controller.

Individual Air-conditioning Control


From VRV to SkyAir to Split Units, conveniently
manage all air-conditioning needs with flexible and
precise control when connected to Reiri.

Lighting Control DALI Compatible


Monitor and control DALI-compatible LED lighting systems
from a single controller with enhanced automation through
interlocking functions with air-conditioners and other
connectable devices.

Smart Devices
Connect to a wide variety of smart devices,
ranging from IP cameras to locks and sensors,
and access all of them from just one Reiri app.

78
BENEFITS OF REIRI
Energy Saving
By automating air-conditioning and
lighting controls through available functions such
as scheduling and interlocking, energy consumption
is greatly minimized while maximising
comfort and efficiency.

Energy and Cost Management


Easily monitor and analyse energy consumption
with data trend graphs, reports and even real-time
energy monitoring display. Tenant billing management
is also available for effective cost management.

Integration Capabilities
Reiri is able to integrate and connect to various sensors
and smart devices, thus making it the ideal all-in-one
platform to monitor and control every room's indoor
environment, such as temperature, humidity, indoor air
quality and illuminance.

and lighting is the key to cutting energy costs.


Electricity consumption ratio
in typical office buildings.

Other
12%
Office
Devices HVAC
16%
48%
Lighting
24%

HVAC and lighting


account for 72%
Source: Agency for Natural Resources
and Energy, Government of Japan

79
CONTROL SYSTEMS

Individual Control Systems for VRV Indoor Units


Navigation remote controller (Wired remote controller) (Optional)

Clear display
• Dot matrix display
A combination of fine dots enables various
icons. Large text display is easy to see.

• Backlight display
Backlight display helps operating in dark rooms.

Simple operation
BRC1E63 &
BRC1F61 (Only for FXEQ Series) • Large buttons and arrow keys
Large buttons and arrow keys enable easy
operation. Basic setting such as fan speed
and temperature can be intuitively operated.
For other settings, just select the function
from the menu list.

• Guide on display
The display gives an explanation of each setting for easy operation.

Energy saving

• Set point range set


• Saves energy by limiting the min. and max. set temperature.
• Avoids excessive cooling or heating.
• This function is convenient when the remote controller is installed at a place where
any number of people may operate it.

• Set point auto-reset


• Even if the set temperature is changed, it returns to the preset temperature after
a preset period of time.
• Period selectable from 30 min/60 min/90 min/120 min.

• Off timer Restaurant sample


• Turns off the air conditioner after a preset
Restaurant opened Full tables at lunchtime After 30 minutes*
period of time.
Temperature is set to 27°C Then is lowered to 24°C Automatically returns to preset
• Period can be preset from 30 to 180 for crowded room temperature (27°C)
Returns to
minutes in 10-minute increments.
27 °C 24 °C 27°C
automatically

*Setting possible for after 30, 60, 90,


and 120 minutes.

80
Convenience

• Setback (default: OFF)


Setback Recovery
Maintains the room temperature in a specific range during an unoccupied period
temperature differential
by temporarily starting air conditioner that was turned OFF.
Ex) Setback temperature Cooling : 35°C Recovery differential Cooling : -2°C Cooling 33 37°C -2 -8°C
When the room temperature goes above 35°C, the air conditioner starts operating in Cooling automatically.
When room temprature reaches 33°C, the air conditioner turns OFF.

• Weekly schedule
• Five actions per day can be scheduled for each day of the week.
• The holiday function will disable schedule timer for the days that have been set as holiday.
• Three independent schedules can be set (e.g. summer, winter, mid-season).

College classroom sample (a summer Monday case)


1) 8:30 ON 2) 10:00 OFF 3) 13:00 ON 4) 15:00 OFF
The first period starts and the In the second period, the classroom When the third period starts, After the third period, the classroom
air conditioner starts the cooling is unoccupied and the air conditioner operation starts again. becomes vacant again and the
operation. stops. air conditioner stops.
ON OFF ON OFF

Comfort
• Individual airflow direction (*1)
Airflow direction of each of the four air outlets can be controlled individually.
(Positions 0 to 4, Swing, and No individual settings are selectable).

1 2

Outlet mark

1
3
3 4

• Auto airflow rate (*2)


Airflow rate is automatically controlled in accordance with the
*1 Only available for VRV 4-Way Flow Ceiling Suspended type FXUQ-A series.
difference between room temperature and set temperature. *2 Only available for VRV 4-Way Flow Ceiling Suspended type FXUQ-A series.

81
CONTROL SYSTEMS

Individual Control Systems for VRV Systems

Stylish remote controller (Option) - Madoka

A complete redesigned
controller focused to
enhance user experience For More information
'Scan Me'

BRC1H61W (White) BRC1H61K (Black)

Product Features User-friendly interface


• Combines refinement and simplicity. • Just three buttons and a large-figure display.
• Echoes the distinct blue circle and simplicity of design. • Customisable display.
• Two attractive colours to match any interior. • Direct access to basic functions (ON/OFF,
• Compact, measures only 85 x 85 mm. Operation mode, temperature setting, Airflow
rate, Airflow direction).

SIMPLE VIEW ON/OFF Customisable example

Easy and direct access


to main functions

Fan speed Louvre setting


Mode selection
(cooling, fan only, etc.)

Easy setting via Bluetooth App with smartphone (for Installer/Facility Manager)
Keep hotel room comfortable
• Improved setback function by setting the lower
temperature limit in cooling mode.

Shorter installation time


• Easy to create multiple remote control and field
settings via App.
• Prepare a setting in advance at the office and
immediately send it to the on-site remote controller.
• Save and reuse settings. App screen image

82
Stylish remote controller (Option)

Easy operation with new intuitive design


Simple operation BRC2E61
Using only six buttons, users have direct access to basic functions. This enables them to
easily set comfort to their preference.
• ON/OFF • Airflow rate (5-step & Auto)*
• Operation mode • Up and down airflow direction (5-step & Swing)*
• Temperature setting • ON/OFF timer

Intuitive design
• By using pictograms, the user- friendly interface enables convenient and easy operation.

Compact size
• Measuring only 85 x 85 mm, the new remote controller is extremely compact and
complements any interior design.

Wireless remote controller (Option)

• The same operation mode and setting as with wired remote controllers are possible.
*Individual airflow direction, auto air-flow rate and sensor control can be set only via
wired remote controller BRC1E62. They cannot be set via other remote controllers.
• A compact signal receiver unit (separate type) to be mounted into wall or ceiling is
included.
• A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Signal receiver unit Compact Multi Flow, Double Flow) type, Ceiling Suspended Type and Wall Mounted
(Installed type)
type is mounted into the Indoor unit.

Signal receiver unit can be


installed on the panel.
Ex. Ceiling Mounted Cassette (Round Flow) type

*Wireless remote controller and signal receiver unit are sold as a set.
*Refer to page 90 for the name of each model. Signal receiver unit
(Installed type)

Wide variation of remote controller for VRV indoor unit


FXFQ-AVM FXVQ
FXFQ-S FXZQ FXCQ FXUQ FXEQ FXDQ FXMQ FXHQ FXAQ FXL(N)Q

Navigation remote controller


(Wired remote controller)
BRC1E63

Wired remote controller


(BRC2E61)

Wireless remote controller*

83
CONTROL SYSTEMS

Centralised Control Systems for VRV Indoor Units


• Up to 64 groups of indoor units (128 units) can be centrally • System integrated with various air conditioning peripheral
controlled. equipment such as Heat Reclaim Ventilator is easy.
• Optional controllers for centralised control can be combined • Wiring can be run up to a length of 2km, and adapts
freely, and system can be designed in accordance with easily to large-scale system expansion.
building scale and purpose.

Unified on/off
controller
(DCS301BA61).
Connection of
up to 8 units Independent
possible. and centralised
Address setting of central control can be control of Heat
performed from the remote controller. Reclaim
Ventilator is
possible.

Connectable number
of centralised control
equipment
Central remote Group control of up to 16 units is possible
controller 2 units (group control via automatic address setting)
Unified remote
controller 8 units

Schedule timer 1 units

System without remote control is also available.

Forced
shut-down
input Central control Wiring
adaptor kit Adaptor for Outdoor air
(DTA107A55) other air- processing
conditioners unit can be
(DTA103A51) connected.
Central remote
controller Interface adaptor for Sky Air
(DCS302CA61) Series
(DTA112BA51)
Up to 2 unit
connectable

6 crores 7 crores max. Interlink Building Management system


(host computer monitor panel) also
Schedule Timer (DST301BA61) possible.
1 unit connectable possible Unification adaptor for
8 weekly schedule control patterns possible computerised control (DCS302A52)

• Certain indoor units limit the functions of some control systems.

84
Residential remote controller (Optional)

Max. 16 groups of indoor units can be easily controlled


with the large LCD Panel.
• Max. 16 group (128 indoor units) are controllable.
• Backlight and large LCD panel for easy readability.
• ON/OFF, temperature setting and scheduling can be controlled individually for indoor units.
• All indoor units can be turned on or off at once with “ALL” button.
• Outside temperature display.
*For residential use only. Cannot be used with other centralised control equipment.
DCS303A51

Central remote controller (Optional)

Max. 64 groups (zones) of indoor units can be controlled individually same as


LCD remote controller.
• Max. 64 group (128 indoor units) are controllable.
• Max. 128 group (128 indoor units) are controllable by using 2 central remote controllers, which can be
controlled from 2 different places.
• Zone control.
• Malfunction code display.
DCS302CA61 • Max. wiring length of 1,000m (Total: 2,000m).
• Airflow volume and direction can be controlled individually for indoor units in each group operation.
• Ventilation volume and mode can be controlled for Heat Reclaim Ventilator.
• Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.

Unified ON/OFF controller (Optional)


Max. 16 groups of indoor units can be operated
simultaneously/individually.
• Max. 16 group (128 indoor units) are controllable.
• 2 remote controllers can be used to control 2 different places.
• Operating status indication (Normal Operation, Alarm).
• Centralised control indication.
• Max. wiring length of 1,000m (Total: 2,000m).
• Compact size casing (Thickness: 16mm).

DCS301BA61

Schedule timer (Optional)


Max. 128 indoor units can be operated as programmed schedule.
• Max. 128 indoor units are controllable.
• When used in combination with a central remote controller, a maximum of 8 weekly schedule
patterns can be set, while the central controller can be used to select desired zones. Up to 2
ON/OFF pairs can be set per day.
• Max. 8 hours back-up power supply.
• Max. wiring length of 1,000m (Total: 2,000m).
• Compact size casing (Thickness: 16mm).
DST301BA61

85
CONTROL SYSTEMS

Advanced Control Systems for VRV Indoor Units

One touch selection enables flexible control of


equipment in a building.

For More information


'Scan Me'

DCM601A51

Various types of equipment in a building


can be controlled by a single controller.

Individual air-conditioning control


The flexible control achieved by the VRV system precisely
meets different air conditioning needs in each room (e.g.
offices, conference rooms, hotel rooms).

Lighting control DALI-compatible


DALI-compatible
DALI-compatible LED lighting systems can be
controlled and monitored. Lighting control is
enhanced through an interlock function with air
conditioners and other functions.

Air conditioning control for large spaces Building equipment control


Air handling units can also be controlled. Large spaces, Various types of equipment other than air conditioners,
such as entrance halls and shopping malls, can be easily including ventilators, fans, and pumps, can also be
controlled to ensure comfort. controlled.

Pump Fan

86
For Energy Saving & Comfort

Intelligent Touch Manager maximises


the advantages of VRV features
Intelligent Touch Manager is an advanced multi-zone controller that provides the most cost-effective way to control and
monitor the Daikin VRV system.

The 10.4" LCD touch screen is easy to use with three different screen views to include the floor plan layout view, icon
view and list view and menus for system configurations.

It is also easy to use with standardised remote Web Access from your PC.

It can manage a total of 650 management points consisting of up to 512 Daikin indoor unit groups

(up to 1024 indoor units) along with building equipment control / monitoring with Digital Inputs / Output

(Di/Dio), Analog Inputs / Output (Ai/Ao) and Pulse input (Pi) optional devices.

Schedule the operation time for each application. Define the set point range that users can change.
With Remote controller
This heat is killing me.

Reception: Very cold.


Office: 9:00-17:00
8:00-18:00
Admin: 16°C
8:30-17:00
Machine room:
24 hours

With Control System


Manager room:
Set point range 22°C - 28°C
8:00-20:00

It can not
Why? be set
Common area: below this Oh! Cool.
Meeting room: 9:00-17:00
No schedule

22°C

Turn the unit OFF, if a user didn’t. Reset set point regularly.

Change to 20°C
Stop Start

Working hours Turn ON again by remote controller, 24ºC


(Scheduled) forgot to turn OFF, and left. Saved power consumption
by control system
20ºC
Saved power consumption
by control system
8:00 17:00 18:30 8:00 8:00 10:00 18:00 8:00

Turn OFF Automatically turn OFF


Set at 24°C Reset to 24°C
as scheduled to cut wasteful operation

87
CONTROL SYSTEMS

Advanced Control Systems for VRV Indoor Units

In addition to switching lights on and off, advanced lighting control,


such as illuminance adjustment, can be achieved.

Lighting control (Optional)


Connection to DALI - compatible lighting control system
DALI-compatible
DALI-compatible
Simple wiring (daisy chain) enables management of LED lighting by the
Please contact your local sales office for details.
Intelligent Touch Manager.
Various air conditioning and lighting control is enabled through the interlock
with occupancy sensors and illuminance sensors.
Air conditioning and lighting for which power consumption is high can be
efficiently controlled to promote energy conservation and cost reduction!
Lighting control achieved by
the Intelligent Touch Manager.
System
[Operation]
• Switch-on/switch-off operation.
• Illuminance (1–100%) control.
• Various illuminance patterns can be registered. DCM009A51
• Registered pattern can be selected from Intelligent (BACnet ® Client option) LAN
Touch Manager.

WAGO I/O system


[Monitoring] DALI BUS
BACnet ® DALI module
• Switch-on/switch-off status monitoring. controller 753-647
• Lighting abnormality monitoring. 750-831
DALI LED driver
• Illuminance monitoring.
Sensor
• DALI occupancy sensor monitoring. LED light (occupancy /
• DALI illuminance sensor monitoring. illuminance)

[Overview of control]
• Up to 5 DALI modules can be connected to a (Each group corresponds to a management point • DALI BAS simplifies wiring and setting work by
single BACnet® controller. of the Intelligent Touch Manager.) daisy chain wiring and automatic address setting.
• Up to 64 DALI LED drivers (64 addresses) can • Up to 16 scenes can be set to a single DALI
be connected to a single DALI module. module.
• 64 DALI addresses can be freely assigned to up • Up to 12 sensors (occupancy, illuminance) can be
to 16 groups using a single DALI module. connected to a single DALI module.

Easy maintenance and energy saving by lighting control.


Case 1 Case 2 Case 3
Switch-on / switch-off and illuminance Occupancy sensors are used to eliminate Lighting abnormalities (e.g. burned-out
are controlled based on a schedule to both wasteful lighting and air bulbs) can be checked on
cut wasteful power consumption. conditioning. the Intelligent Touch Manager screen.
When a room is unoccupied,
• Failing to switch the air conditioning stops and the Lighting maintenance becomes easier and
off lights is prevented. quicker.
lighting is switched off.

OFF OFF

The layout screen enables quick


identification of specific locations.
• Optimal illuminance reduces energy.

88
Tenant Management (PPD Option)

Reporting the power consumption of VRV system for each tenant.

With the PPD function, power consumption can be calculated for each indoor unit (Optional)
The energy consumption is proportionally
calculated for each indoor unit. The data can be Operational information
of individual indoor units
used for energy management and calculation of air Tenant A
conditioning usage fees for respective tenants. HIGH
Operation duration
Room temperature
Expansion valve
Operational information of individual indoor units opening ratio
Tenant B
are monitored, based on distribution of power LOW
consumption of outdoor units. Automatic calculation of

me om
total power consumption of

h l fr
ter
individual indoor units
Daikin’s PPD keeps track of power distribution for

kW igna
the se s
Tenant C
each indoor unit. It performs air conditioning

l
MEDIUM

Pu
Tenant B
billing calculations quickly and automatically. Tenant A
Tenant C
It is easy to output PPD data.
PPD data is output in CSV format to a PC or USB memory device
kWh meter Total power consumption
and can be freely processed and managed.

*PPD (Power Proportional Distribution) is Daikin’s proprietary calculation method.

Air conditioning bills can be issued by one click.

Electricity bills can be easily calculated for each tenant (Optional)

The power consumption of VRV controlled by the


Intelligent Touch Manager can be easily managed Internet / Ethernet

for each tenant using a PC. The electricity bill HUB


Invoice

settings facilitate billing work through easy SVMPS1 Invoice Invoice

User’s PC
calculation and issuance of VRV electricity bills.

[ Main functions ]
• Register tenants.
• Set the electricity unit price for 5 time zones.
• Calculate power consumption and electricity charge for each tenant.
• Show aggregation results in the specified period for each tenant.
• Output the results (Printout and CSV file).

Tenant registration screen Set-up screen VRV electricity bill screen

89
CONTROL SYSTEMS

Advanced Control Systems for VRV Indoor Units

System Structure
Up to 512 groups
Intelligent Touch Manager System Overview (1024 indoor units)

Air Conditioning Up to 650


Network Service System
management points

One D -NET system


Max. 64 indoor unit groups (128 indoor units)
iTM Plus Adaptor
100Mbps Max. 64 indoor unit groups
Ethernet

USB Di/Pi port


Flash drive
Max. 64 indoor unit groups
Di/Pi Line

Web Access
via Internet

Max. 64 indoor unit groups


KRP
928BB2S

Web Access
via LAN Up to 7 Adaptors

Fire alarm kWh meter Residential A/C


WAGO I/O up to 30 nodes

BACnet® / IP

Air Handling Unit Pump Fan Sensor Keycard switch


3rd party
BACnet® controller

WAGO I / O system
BACnet® controller DALI module
750-831 753-647

DALI BUS

DALI LED driver


Sensor
LED light (occupancy / illuminance)

DALI BUS

DALI LED driver


Sensor
LED light (occupancy / illuminance)

DALI BUS

DALI LED driver


Sensor
LED light (occupancy / illuminance)

90
Air Conditioning Network Service System
Preventive Maintenance
The Intelligent Touch Manager can be connected to Daikin’s own Air Conditioning Network Service System for remote monitoring
and verification of operation status for VRV system. By its ability to predict malfunctions, this service provides customers with
additional peace of mind.

Enhanced convenience with link to the Air Conditioning Network Service System
The Intelligent Touch Manager connects seamlessly to Daikin’s 24-hour Air Conditioning Network Service System.

ACC centre
Personnel at the centre monitor the
occurrence of malfunctions and track their
Trouble
cause via the Internet.
Advance malfunction warnings help prevent
the sudden occurrence of problems later.
Even malfunctions difficult to identify
Air Conditioning Network Service System*
can be monitored remotely.
Repair *Because of restrictions
Allows dispatching of Enable prompt repairs as in applicable areas and
service engineers without service engineers know the release times, please consult
cause of the problem a Daikin representative
a call from customers. separately for details.
beforehand.

Daikin Offers a Variety of Control Systems

Convenient controllers that offer more freedom to administrators

Ease of use and expanded control functions


The user-friendly controller features colours, multilingual function, and icons in the display for ease
of understanding. A wide variety of control methods can be accommodated, permitting
administrators to monitor and operate the system even when they are away from the controller.
DCS601C51

Connect VRV system to your BMS via BACnet® or LONWORKS®


Compatible with BACnet® and
BACnet® LONWORKS ®
LONWORKS ®, the two leading open
Seamless connection Facilitating the network
network comunication protocols,
between VRV system integration of
Daikin offers interfaces that provide a
and BACnet® open VRV system
seamless connection between VRV network protocol. and LONWORKS ®
system and your BMS.
DMS502B51 DMS504B51
(Interface for use in BACnet ® ) (Interface for use in LONWORKS ® )
Dedicated interfaces make
Daikin air conditioners freely Notes: 1. BACnet ® is a registered trademark of American Society of Heating, Refrigerating and
compatible with open networks Air-Conditioning Engineers (ASHRAE).
2. LONWORKS ® is a trademark of Echelon Corporation registered in the United States and other countries.

Modbus Interface Adaptor


Up to 16 indoor units can be individually controlled.

Other Home
VRV Indoor unit Appliances

Home Automation
Use of Modbus protocol Master Controller Television

RS485 Mod
Modbus
dbus Protocol
Wire length is up to 500m Electric curtains

VRV Outdoor unit


Simple installation
Lighting
The VRV outdoor unit and home automation system can be equipment
Up to 2 units can be DTA116A51*
connected simply by using this dedicated adaptor.
connected One Adaptor
requires for a house Compatible with
*A separate power supply for Home Automation Interface Adaptor is necessary. an existing unit.
It may not be installed inside some outdoor unit models.

91
CONTROL SYSTEMS

Integrated Building Monitoring System

The high speed transmission of DIII-NET enables more advanced control of the VRV system, providing you
with enhanced comfort.

Controllers for Centralised Control

(DCS601C51)

(DCM601B51)

Central Remote Unified ON/OFF Schedule Timer


Via internet Controller Controller (DST301BA61)
(DCS302CA61) (DCS301BA61)

Via internet

ACC Centre Control /Connection Interface


Air conditioning Network Service System
(There are restrictions in applicable areas and release Unification adaptor
times, therefore please consult us separately for for computerised control
details.) (DCS302A52)
(Optional Maintenance Service)

Home Automation
Master Controller
Home Automation
Interface Adaptor
(DTA116A51)
BMS
(Obtain locally)

Interface for use in BACnet®


(DMS502B51)

Interface for use in LONWORKS®


(DMS504B51)

Wiring adaptor
for electrical appendices
(KRP2A61/62/53)

92
Integrated Building Monitoring System
DIII-NET Line
The DIII-NET system provides for:
BACnet®/Ethernet or LONWORKS®
Network Communication Line • Close control and monitoring by integrating a wide variety of air conditioners in the
entire building.
Contact Signal Line • Saving the in-building cabling using non-polar, two-wire cables. Easier wiring work with
tremendously fewer wiring errors.
RS485 Modbus Line • Additional set-ups readily up and running. An extendable cabling up to 2 km in total.
• Different control equipment flexibly joined in the system for hierarchical risk
WAGO Connection diversification.
• Daikin's total heat exchangers and other devices all under integral control.

VRV

D -NET Heat Reclaim Ventilator

(High Speed Multiple


Transmission)

Interface Adaptor for SkyAir Series


(DTA112BA51) SkyAir
Our unique high speed
multiple transmission system
links air conditioners and
* No adaptor is required for the
various other building FCQ-B and FHQ-BV.
equipment in accordance
with applications, scale and
Central Control Adaptor Kit Packaged
conditions and transmits vast (DTA107A55)
amounts of information Airconditioner
between them.

Interface Adaptor for DIII-NET use


(KRP928BB2S)
Residential Airconditioner

WAGO Building services equipment


• Electrical equipment
• Supply water and drainage equipment
• Automatic fire alarm
• Parking equipment
• Lift
• Ventilation equipment
• Lighting
• Crime and fire prevention equipment

VRV
Caution:
Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.

Note: BACnet® is a registered trademark of American Society of Heating, Refrigerating and


Air-Conditioning Engineers (ASHRAE). LONWORKS® is a trademark of Echelon Corporation
registered in the United States and other countries.

93
CONTROL SYSTEMS

Option List
Operation Control System Optional Accessories

For VRV indoor unit use


Type FXFSQ-A FXDQ-PD
No.
(For Black FXFSQ-A FXZQ-M FXUQ-A FXCQ-M FXKQ-AV
Item Panel) FXDQ-ND
Receiver BRC7M632F-6 BRC7M630W-6 BRC63AV BRC4M61-6
Wireless BRC7M634K BRC7CB58 BRC7M65
1 Remote controller Handset BRC4M150W16 BRC4M150W16
Wired BRC2E61
BRC1E63
2 Navigation remote controller (Wired remote controller) BRC1E63 Note 7
3 Simplified remote controller (Exposed type) — BRC2C51
4 Remote controller for hotel use (Concealed type) — BRC3A61
5 Adaptor for wiring ÌKRP1C63 ÌKRP1BA57 — ÌKRP1B61 KRP1B61 ÌKRP1B56
6-1 Wiring adaptor for electrical appendices (1) ÌKRP2A62 ÌKRP2A62 — ÌKRP2A61 KRP2A61 ÌKRP2A53
6-2 Wiring adaptor for electrical appendices (2) ÌKRP4AA53 ÌKRP4AA53 ÌKRP4AA53 ÌKRP4AA51 KRP4AA51 ÌKRP4A54
7 Remote sensor (for indoor temperature) KRCS01-4B KRCS01-1B
Note 2, 3 Note 4, 6 Note 2, 3 Note 4, 6
8 Installation box for adaptor PCB KRP1BA97 —
KRP1H98 KRP1BA101 KRP1B96 KRP1BA101
9 External control adaptor for outdoor unit ÌDTA104A62 ÌDTA104A62 — ÌDTA104A61 DTA104A61 ÌDTA104A53
10 Adaptor for multi tenant ÌDTA114A61 —

Type FXMQ-P/ FXLQ-MA


No. Item FXMQ-NVE FXHQ-MA/AVM FXAQ-A FXVQ-N
FXMQ-ARV FXNQ-MA
Receiver BRC4M61-6 BRC7EA63W9 BRC7N618-6 BRC4M61-6 —
Wireless
1 Remote controller Handset BRC4M150W16 /BRC7M53 BRC4M150W16 —
Wired BRC2E61 BRC2E61 Note 8
2 Navigation remote controller (Wired remote controller) BRC1E63 Note 7 BRC1E63 Note 9
3 Wired remote controller with weekly schedule timer BRC1D61 —
4 Simplified remote controller (Exposed type) BRC2C51 BRC2C51 — BRC2C51 —
5 Remote controller for hotel use (Concealed type) BRC3A61 BRC3A61 — BRC3A61 —
6 Adaptor for wiring ÌKRP1C64 KRP1B61 KRP1BA54 — KRP1B61 KRP1C67
7-1 Wiring adaptor for electrical appendices (1) ÌKRP2A61 KRP2A61 ÌKRP2A61 ÌKRP2A61 KRP2A61 —
7-2 Wiring adaptor for electrical appendices (2) ÌKRP4AA51 KRP4AA51 ÌKRP4AA52 ÌKRP4AA52 KRP4AA51 KRP2A62
8 Remote sensor (for indoor temperature) KRCS01-4B — — KRCS01-1B — —
Note 1 Note 3 Note 1
9 Installation box for adaptor PCB KRP4A96 — KRP1CA93 KRP4AA93 —

10 External control adaptor for outdoor unit ÌDTA104A61 DTA104A61 ÌDTA104A62 ÌDTA104A61 DTA104A61 DTA104A62
11 Adaptor for multi tenant ÌDTA114A61 — — ÌDTA114A61 —
12 External control adaptor for cooling / heating — KRP6A1
13 Remote controller with key — KRCB37-1

Function List Round Flow with Sensing Type For Control Model
FXFSQ-A
Remote controller
Wired BRC1E63 Wireless Heat Pump BRC7M530W
(for grid ceiling panel)
Remote controller
Wireless —
Remote controller
Dual sensors *1 Wireless Heat Pump BRC7E530W
(for decoration panel)
Direct airflow *1
Sensing sensor low mode *1 Navigation remote controller BRC1E63

Sensing sensor stop mode *1 Simplified remote controller BRC2E61


Circulation airflow Adaptor for wiring (operation status output) ÌBRP11B62
Individual airflow direction control Wiring adaptor for electrical appendices (1) ÌKRP2A62
Switchable 5 step fan speed
Wiring adaptor for electrical appendices (2) ÌKRP4AA53
Auto-airflow rate
Remote sensor (for indoor temperature) BRCS01A-5
Auto-swing
Installation box for adaptor printed circuit board*2 KRP1BB101 (Note 3, 4)
Swing pattern selection
High ceiling application External control adaptor for outdoor unit ÌDTA104A62

Notes: Multi tenant unit (24V free type) for indoor ÌBRP114A61
1. Installation box is necessary for each adaptor marked Ì.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
7. Individual airflow direction, auto airflow rate and sensing sensor control can be set only via
wired remote controller BRC1E63. Cannot be set via other remote controllers.
8. Since the control panel is equipped as standerd, use the option for 2 remote control system.
9. When using BRC1E63, be sure to remove the control panel and since BRC1E63 cannot be
stored inside the indoor unit, please place it separately.

94
6\VWHP&RQÀJXUDWLRQ
Type
No. Item Model No. Function

Note 2 • Up to 16 groups of indoor units (128 units) can be easily controlled using the
1 Residential central remote controller DCS303A51 large LCD panel. ON/OFF, temperature settings and scheduling can be
controlled individually for indoor units.
2 Central remote controller DCS302CA61 • Up to 64 groups of indoor units (128 units) can be connected, and ON/OFF,
temperature setting and monitoring can be accomplished individually or
2-1 Electrical box with earth terminal (3 blocks) KJB311AA simultaneously. Connectable up to 2 controllers in one system.
3 Unified ON/OFF controller DCS301BA61 • Up to 16 groups of indoor units (128 units) can be turned, ON/OFF individually or
3-1 Electrical box with earth terminal (2 blocks) KJB212AA simultaneously, and operation and malfunction can be displayed. Can be used in
3-2 Noise filter (for electromagnetic interface use only) KEK26-1A combination with up to 8 controllers.
• Programmed time weekly schedule can be controlled by unified control for up to
4 Schedule timer DST301BA61
64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.
5-room centralised For CDXS, FDK(X)S, Note 3 • Up to 5 indoor units can be controlled. This is a low cost system which can only
5 controller for residential
FTK(X)S KRC72A control ON/OFF.
indoor units
Interface adaptor for For CDXS, FDK(X)S, • Adaptors required to connect products other than those of the VRV System to the
6 KRP928BB2S
residential indoor units FTK(X)S high-speed DIII-NET communication system adopted for the VRV System.
Interface adaptor for For FCQ-B, FFQ-B,
7 ÌDTA112BA51
SkyAir-series FHQ-BV, FBQ-B
* To use any of the above optional controllers, an appropriate adaptor must be
8 Central control adaptor kit For UAT(Y)-K(A), FD-K ÌDTA107A55
installed on the product unit to be controlled.
9 Wiring adaptor for other air-conditioner ÌDTA103A51

DIII-NET • Up to 1024 units can be centrally controlled in 64 different groups.


10 DTA109A51
Expander Adaptor • Wiring restrictions (max. length: 1,000m, total wiring length: 2,000m, max.
number of branches: 16) apply to each adaptor.
10-1 Mounting plate KRP4A92 • Fixing plate for DTA109A51
Note: 1. Installation box for Ì adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralised control equipment.
3. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.

Building Management System


No. Item Model No. Function

Intelligent Touch • Air conditioning management system that can be controlled by a


1 Basic Hardware Controller DCS601C51
Intelligent Touch compact all-in-one unit.
Controller
1-1 Option Hardware DIII-NET plus DCS601A52 • Additional 64 groups (10 outdoor units) is possible.
adaptor
1-2 Electrical box with earth terminal (4 blocks) KJB411A • Wall embedded switch box.
• Air conditioning management system that can be controlled by touch
2 Basic Hardware Intelligent Touch DCM601B51
Manager screen.
2-1 • Additional 64 groups (10 outdoor units) is possible. Max. 7 iTM plus
Hardware iTM plus adaptor DCM601A52
2-2 adaptors can be connected to Intelligent Touch Manager.
Intelligent Touch
Manager Option iTM power • Power consumption of indoor units are calculated based on operation
2-3 proportional DCM002A51 status of the indoor unit and outdoor unit power consumption measured
Software distribution by kWh metre.
2-4 iTM energy • Building energy consumption is visualised. Wasted air conditioning
navigator DCM008A51 energy can be found out.
2-5 Di unit DEC101A51 • 8 pairs based on a pair of ON/OFF input and abnormality input.
2-6 Dio unit DEC102A51 • 4 pairs based on a pair of ON/OFF input and abnormality input.
• Interface unit to allow communications between VRV and BMS.
3 *1 Interface for use in BACnet ® DMS502B51 Operation and monitoring of air conditioning systems through BACnet®
communication.
• Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET
3-1 Optional DIII board DAM411B51 communication ports. Not usable independently.
• Expansion kit, installed on DMS502B51, to provide 16 more wattmeter
3-2 Communication Optional Di board DAM412B51
pulse input points. Not usable independently.
interface
• Interface unit to allow communications between VRV and BMS.
4 *2 Interface for use in LONWORKS ® DMS504B51 Operation and monitoring of air conditioning systems through
LonWorks® communication.

• Use of the Modbus protocol enables the connection of the VRV system
5 Home Automation Interface Adaptor DTA116A51
with a variety of home automation systems from other manufacturers.

Notes:
*1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
®

*2. LonWorks is a trademark of Echelon Corporation registered in the United States and other countries.
®

*3. Installation box for Ì adaptor must be obtained locally.

95
AIR HANDLING UNIT

Integrate your air handling unit for large size spaces


such as factories and for fresh air solutions.

Capacity range : 6 - 60 HP

• Easy design and installation.


• The system is easy to design and install since no additional
water systems such as boilers, tanks, gas connections, etc.
are required.
• Inverter controlled units.
• Control of air temperature via standard Daikin wired
remote control.

System overview

Air handling unit

Daikin communication wire (F1, F2 communication) Liquid pipe


Other communication wire Gas pipe
Air handling units can be connected to VRV systems.
This combination can be built to order as a system. Outdoor air series is also possible. Please contact your local sales office for details.
*Control box and expansion valve kit are necessary for integration of AHU and VRV system.

96
HEADER PACK

The Innovative Refrigerant Piping of next generation.


Daikin innovated next generation of quality and efficiency for VRV installation. It offers differentiated soulutions in installation.
It ensures quality installation with reduction of site work.

Advantage
• Installation time saving: Up to 1/3 of conventional method.
• Easy to Install: Hanging points available.
• Safety: Consists of faring method, no brazing required*.
• Space saving: Head pack to Indoor unit soft drawn pipe, top side of
refrigerant pipe doesn’t need space for brazing torch movement.
Header Pack • Quality Installation: Elimination of difficult process, enhancing quality
installation.

Quick, flare
nut connection

No need of
brazing

Easy,
soft copper
tube piping

Compact design to fit into narrow attic space


Light weight and the compact body give minimum damage on the building structure.

Header Pack Line-up


Piping connections (Liquid/Gas mm)
Model Name HP Indoor unit total capacity index
Outdoor unit side Indoor unit side

BHF6RHP6 6 Φ9.5/Φ15.9 (Φ9.5/Φ15.9)×1 (Φ6.4/Φ12.7)×3 <150

BHF8RHP6 8 Φ9.5/Φ19.1 150 <


= X < 200
(Φ9.5/Φ15.9)×3
BHF10RHP6 10 Φ9.5/Φ22.2 200 <
= X < 290
(Φ6.4/Φ12.7)×3
BHF16RHP6 16 Φ12.7/Φ28.6 290 <
= X < 420

For More information


'Scan Me'

97
DAIKIN GAS TIGHT JOINT (DGT)

Non-brazed connection for Refrigerant piping

Evolutionally - Advanced Feature


A combination of rubber packing and screwed metal body
offers gas-tight and rigid connection without brazing.
Patented "Leverage Method" mechanically holds the pipe
and prevents it from pull-out.

Size φ 6.4 - φ 41.3


Mechanism
Daikin DGT is a non-brazed connection suitable for piping. Pipes can be joined easily and quickly without brazing or using any
special tools. It meets stringent safety requirements and provides leak-free tightness among various substantial benefits.

• Double edged claw catches the pipe to form tight mechanical sealing.
• 3 types of connectors suitable for most pipe sizes and applications.
• Unique mechanical and resin sealing prevent gas leak completely.
• It is durable up to 4 times (17.2MPa) of max. operating pressure.

For More information


'Scan Me'

System Reliability Safety First


• No risk of copper oxide or soot in pipes • As no brazing is required, fire hazards
due to no brazing. are completely eliminated during
• Prevents early compressor failure and installation on site.
prolongs the lifespan of air-conditioners. • No risk of handling high pressure and
flammable gas.
Time & Costs Savings
• No need to apply for hot work permit or station fire safety
watchers onsite, thus saving time and cost with less
administrative work.
• Simple installation process also reduces installation time.

98
Daikin Gas Tight Joint Line up
(Matching for various piping sizes)

Standard Joints (Connecting the same pipes)

Dimension (mm)
Figure Model Name Weight /pc (g)
ND AF L
SDGTB06 φ 6.4 19.0 50.4 43
SDGTB09 φ 9.5 22.2 55 79
SDGTB12 φ 12.7 23.8 59 113
SDGTB15 φ 15.9 29.7 74 210
SDGTB19 φ 19.1 35.0 76.8 273
SDGTB22 φ 22.2 38.0 83.4 292
SDGTB28 φ 22.6 45.0 88 515
BDGTA34 φ 34.9 51.1 101.5 686
BDGTA41 φ 41.3 58.3 103.5 881

Asymmetry Joints (Connecting different size pipes)


Dimension (mm)
Figure Model Name Weight /pc (g)
ND AF L
SDGTB0906 φ 9.5-6.4 22.2 19 52.7 67
SDGTB1209 φ 12.7-9.5 23.8 22.2 57.5 101
SDGTB1512 φ 15.9-12.7 29.7 23.8 65 164
SDGTB1915 φ 19.1-15.9 35 29.7 76.8 244
SDGTB2219 φ 22.2-19.1 38 35 81.5 358
SDGTB2522 φ 25.2-22.2 41.8 38 85.8 444
SDGTB2825 φ 28.6-25.4 45 41.8 88.1 505
SDGTB3428 φ 34.9-28.6 51.1 45 101.5 645

99
AIR TREATMENT EQUIPMENT LINE-UP

Our air treatment systems


create a higher air quality
environment

Components
of Indoor Air Quality

Ventilation *TMKFKĂECěKON

Air Processing*

*Refers to bringing outdoor air to near indoor


temperature and delivering to a room.

A recent trend rapidly gaining popularity is the need for air treatment along with air
conditioning. Our Outdoor Air Processing Unit can combine fresh air treatment and air
conditioning, supplied from a single system. It adjusts the temperature of air from outdoors using
a fixed discharge temperature control. Along with Outdoor Air Processing Units, we also offer
Heat Reclaim Ventilator systems. The Heat Reclaim Ventilator VAM-GJ series units in particular
have been praised for their compactness, energy conservation and extensive operation range
of outdoor temperatures. This series provides higher enthalpy efficiency due to the greatly
enhanced performance of the thin film element. Furthermore, improved external static pressure
offers more flexibility for installation. The Heat Reclaim Ventilator VKM-GAM series units,
equipped with a DX-coil and a humidifier, provide further advanced features, such as
temperature adjustment to suit conditions indoors and to prevent cold air from blowing on
people directly during heating operation. The series also realises significant energy savings by
exercising heat recovery.

100
Outdoor Air Heat Reclaim Ventilator
Processing Unit VKM-GAM Type VKM-GA Type VAM-GJ Type

Ventilation *TMKFKĂECěKON Ventilation *TMKFKĂECěKON Ventilation *TMKFKĂECěKON

Air Processing* Air Processing* Air Processing*

Refrigerant Piping Connectable Connectable Not connectable

Connections Wiring Connectable Connectable Connectable


with VRV X
After-Cool &
Available Available Not available
After-Heat Control

Heat Exchange Element — Energy savings obtained Energy savings obtained

Humidifier — Fitted — —
High Efficiency Filter Option Option Option
Ventilation System Air supply only Air supply & air exhaust Air supply & air exhaust
Power Supply 220-240 V, 50 Hz 220-240 V, 50 Hz 220-240 V/220 V, 50 Hz

250 m3/h

500 m3/h 500 m3/h


Airflow Rate 650 m3/h
800 m3/h 800 m3/h
1260 m /h 3 1000 m3/h 1000 m3/h
1500 m3/h
1740 m3/h
2000 m3/h
2340 m3/h
*Refers to bringing outdoor air to near indoor temperature and delivering to a room.

101
AIR TREATMENT EQUIPMENT LINE-UP

Outdoor Air Processing Unit


Combination of fresh air treatment and air conditioning,
supplied from a single system.

Lineup
Model Name FXMQ125NFRV16 FXMQ200NFRV16 FXMQ250NFRV16
Capacity Index 125 200 250

Fresh air treatment and air conditioning can be


achieved with a single system by using the heat
pump technology - without the usual troublesome
air supply and air discharge balance design.
Fan coil units for air conditioning and an
outdoor-air processing unit can be connected to the
same refrigerant line. The results are enhanced
design flexibility and a significant reduction in total
system costs.
Combination with VRV X

Air conditioning and outdoor air processing can be


accomplished using a single system.

VRV X Outdoor Units

Outdoor-Air Processing Unit

Indoor Unit Indoor Unit

Air Outdoor
Conditioning Air Supply

Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
• When outdoor-air processing units are connected, the total connection capacity index must be 50% to 100% of the capacity index of the outdoor units.
• When outdoor air processing units and standard indoor units are connected, the total connection capacity index of the outdoor air processing units must not exceed 30% of the
capacity index of the outdoor units.
• Outdoor air processing units can be used without indoor units.

102
Standard Specifications
Indoor unit
Type Ceiling Mounted Duct Type
Model FXMQ125NFRV16 FXMQ200NFRV16 FXMQ250NFRV16
Power supply 1-phase 220- 240 V (also required for indoor units), 50 Hz
kcal/h 12,000 19,300 24,100
Cooling capacity *1 Btu/h 47,800 76,400 95,500
kW 14.0 22.4 28.0
kcal/h 7,700 12,000 15,000
Heating capacity *1 Btu/h 30,400 47,400 59,400
kW 8.9 13.9 17.4

Casing Galvanised steel plate


Dimensions (HXWXD) mm 440 x 1190 x 1090 440 x 1190 x 1090
Motor output kW 0.75
m3/min 21 29 39
Fan Airflow rate
cfm 741 1,024 1,377
External Static Pressure
220 V/240 V Pa 300 260 240
with Filter (PM10+PM50)
Liquid mm ø9.5 (flare)
Refrigerant ø22.2 (brazing)
Gas mm ø15.9 (flare) ø19.1 (brazing)
piping
Drain mm PS1B female thread
Machine weight kg 115
Sound level *3 220 V/240 V dBA 48 50 52
Connectable outdoor units *4 *5 6 HP and above 10 HP and above

Notes: *1. Specifications are based on the following conditions;


• Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
*2 An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter. Please mount it in the duct system of the
suction side. Select a dust collection efficiency (gravity method) of 50% or more.
*3 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
*4. It is possible to connect to the outdoor unit if the total capacity of the indoor units is 50% to 100% of the capacity index of the outdoor units.
*5 Local setting mode. Not displayed on the remote controller.
• This equipment cannot be incorporated into the remote group control of the VRV X system.

103
AIR TREATMENT EQUIPMENT LINE-UP

Heat Reclaim Ventilator with


DX-Coil and Humidifier-VKM Series

The Heat Reclaim Ventilator lineup features the DX-coil in response


to recently diversifying outdoor air introduction requirements.

Line-up
With DX Coil & Humidifier Type
Model Name VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
Capacity Index 31.25 50 62.5
For More information
'Scan Me' With DX Coil Type
Model Name VKM50GAV1 VKM80GAV1 VKM100GAV1
Capacity Index 31.25 50 62.5

VKM80GAV1

Humidifier
The line-up includes models with a humidifier, in
response to diversifying customer requirements.
(VKM50/80/100GAMV1 only)

DX-coil
The Heat Reclaim Ventilator features DX-coil that
contributes to the prevention of cold airflow hitting
people directly during heating operation, due to the
after-cool, after-heat operations done beforehand.
Efficient outdoor air introduction is possible
The Heat Reclaim Ventilator (VKM series) series introduces fresh High static pressure
outdoor air with minimum heat losses, while a wide variety of High external static pressure means enhanced
features responds to customer requirements. design flexibility.

Air conditioning and outdoor air processing can be


accomplished using a single system.

VRV X Outdoor Units

Heat Reclaim Ventilator with


DX Coil & Humidifier

Outdoor Air

Exhaust Air Indoor Unit Indoor Unit

Return
Air Air
Air Conditioning Air Supply

Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
• When the Heat Reclaim Ventilator VKM series units are connected, the total connection capacity index must be 50% to 130% of the capacity index of the outdoor units.

104
A compact unit packed with our cutting-edge technology

Exhaust Fan
Heat Exchanger Elements
EA Damper Motor
(Exhaust air to outdoors) Damper

For More information


'Scan Me'
OA
(Fresh air from outdoors)
RA
(Return air
HEP Element from room)
(Anti-mould)
Air Supply Fan
SA
(Supply air to room)
Operation of the heat exchanger element Electronics Box
(Control box)
DX-coil
Outdoor Indoor Humidifier element
30.6°C SA
62% RH 27.4°C
63% RH

SA
Temperature Integrally-
and humidity formed liner
RA
26°C RA
50% RH

32°C DX-coil (Direct expansion coil) *TMKFKĂGR'ĚGMGNě


70% RH Integrally-formed liner

*GCěKNICNFJTMKFKĂECěKONPROEGSS

Structure of
VKM series Outdoor Indoor
Humidification Humidification: 5.4kg/h (VKM100GAMV1)
Heating
Natural Evaporating
by DX-Coil Pan Type Humidifier
The outdoor air is heated from 16.6°C to 36.5°C with DX-coil,
Heat exchange Natural Evaporating Pan Type Humidifier is passed and
humidification capacity is improved.
16.6°C 36.5°C
Exhaust Air Supply Air
To the Outdoor 10.4°C
To the Indoor 24.5°C

DX-Coil: Heat Exchanger which heats or cools the air by VRV


Return Air outdoor unit’s refrigerant.
Outdoor Air From the Indoor 20°C
From the Outdoor 7°C

Efficient outdoor air introduction with heat exchanger


and cooling/heating operations
100 80
60

Indoor unit with outdoor air treatment Outdoor air temperature


Heat recovery in summer
'ėGEěOHHTĚĚJGCěGWEJCNIG
Using outdoor air, the temperature can be brought near room temperature +
Relative humidity (%)

'ėGEěOHEOOĚKNI 40
with minimal cooling capacity through the use of outdoor air. Heating and cooling
+
Humidifying Indoor temperature during cooling
'ėGEěOH
Indoor temperature during heating JTMKFKĂECěKON
20

Outdoor air temperature


in winter Effect of heating
'ėGEěOHJGCěKNI
Other features Effect of full heat exchange
'ėGEěOHHTĚĚJGCěGWEJCNIG
• Integrated system includes ventilation and humidifying operations.
• Ventilation, cooling/heating and humidifying are possible with one –5 0 5 10 15 20 25 30 35 40
remote controller. Dry bulb temperature (°CDB)

105
AIR TREATMENT EQUIPMENT LINE-UP

Specifications
MODEL VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 VKM50GAV1 VKM80GAV1 VKM100GAV1
Refrigerant R-410A
Power Supply 1-phase, 220–240 V, 50 Hz
Airflow rate m3/h 500 750 950 500 750 950
Ultra-high
Static pressure Pa 160 140 110 180 170 150
Airflow Rate & Static Airflow rate m3/h 500 750 950 500 750 950
Pressure (Note 7) High
Static pressure Pa 120 90 70 150 120 100
Airflow rate m3/h 440 640 820 440 640 820
Low
Static pressure Pa 100 70 60 110 80 70

Heat Ultra-high 560 620 670 560 620 670


exchange High W 490 560 570 490 560 570
mode Low 420 470 480 420 470 480
Power Consumption
Ultra-high 560 620 670 560 620 670
Bypass
High W 490 560 570 490 560 570
mode
Low 420 470 480 420 470 480
Fan Type Sirocco Fan
Motor Output kW 0.280 x 2 0.280 x 2 0.280 x 2 0.280 x 2 0.280 x 2 0.280 x 2
Ultra-high 37/37.5/38 38.5/39/40 39/39.5/40 38/38.5/39 40/41/41.5 40/40.5/41
Heat
exchange High dBA 35/35.5/36 36/37/37.5 37/37.5/38 36/36.5/37 37.5/38/39 38/38.5/39
mode Low 32/33/34 33/34/35.5 34/34.5/35.5 33.5/34.5/35.5 34.5/36/37 35/36/36.5
Sound Level (Note 5)
(220/230/240 V) Ultra-high 37/37.5/38 38.5/39/40 39/39.5/40 38/38.5/39 40/41/41.5 40/40.5/41
Bypass
High dBA 35/35.5/36 36/37/37.5 37/37.5/38 36/36.5/37 37.5/38/39 38/38.5/39
mode
Low 32/33/34 33/34/35.5 34/34.5/35.5 33.5/34.5/35.5 34.5/36/37 35/36/36.5
Humidification Capacity (Note 4) kg/h 2.7 4.0 5.4 —
Ultra-high 76 78 74 76 78 74
Temp. Exchange High % 76 78 74 76 78 74
Efficiency
Low 77.5 79 76.5 77.5 79 76.5
Ultra-high 64 66 62 64 66 62
Enthalpy Exchange High % 64 66 62 64 66 62
Efficiency (Cooling)
Low 67 68 66 67 68 66
Ultra-high 67 71 65 67 71 65
Enthalpy Exchange High % 67 71 65 67 71 65
Efficiency (Heating)
Low 69 73 69 69 73 69
Casing Galvanised Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Non-flammable Paper
Air Filter Multidirectional Fibrous Fleeces
DX-coil Cooling (Note 2) 2.8 4.5 5.6 2.8 4.5 5.6
kW
Capacity Heating (Note 3) 3.2 5.0 6.4 3.2 5.0 6.4
Height 387 387 387 387 387 387
Dimensions Width mm 1,764 1,764 1,764 1,764 1,764 1,764
Depth 832 1,214 1,214 832 1,214 1,214
Connection Duct Diameter mm 200 250 200 250
Net 102 120 125 96 109 114
Machine Weight kg
Gross (Note 8) 107 129 134 —
Around Unit 0°C–40°C DB, 80%RH or less
Unit Ambient Condition OA (Note 9) -15°C–40°C DB, 80%RH or less
RA (Note 9) 0°C–40°C DB, 80%RH or less

Notes: 1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. When 11. Power consumption and efficiency depend on the above value of airflow rate.
calculating the capacity as indoor units, use the following figures: VKM50GAMV1/GV1: 3.5 kW, 12. Temperature exchange efficiency is the mean value for Cooling and Heating. Efficiency is measured under the following
VKM80GAMV1/GV1: 5.6 kW, VKM100GAMV1/GV1: 7.0 kW. condition: Ratio of rated external static pressure outdoor to indoor is kept constant at 7 to 1.
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB. 13. In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the system goes into
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB. defrost operation. During defrost operation, the fans of the unit continue driving (factory setting). The purpose of this is to
4. Humidifying capacity is based on the following conditions: Indoor temperature: 20°C DB, 15°C WB, Outdoor maintain the amount of ventilation and humidifying.
temperature: 7°C DB, 6°C WB. 14. When connecting with a VRV system heat recovery outdoor unit and bringing the RA (exhaust gas intake) of this unit
5. The operating sound measured at the point 1.5 m below the centre of the unit is converted to that measured in an directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit (master unit), and use group-linked
anechoic chambar built in accordance with the JIS C 1502 conditions. The actual operating sound varies operation. (See the Engineering Data for details).
depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally 15. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor
higher than this value. unit, perform group-linked operation, and make the direct duct connection settings from the remote controller. (Mode No.
For operation in a quiet room, it is required to take measures to lower the sound. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the indoor unit.
For details, refer to the Engineering Data. Depending on the fan strength and static pressure, the unit might back up.
6. The noise level at the air discharge port is about 8–11 dBA or higher than the unit’s operating sound.  Feed clean water (city water, tap water or equivalent). Dirty water may clog the valve or cause dirt deposits in the water
For operation in a quiet room, it is required to take measures to lower the sound. container, resulting in poor humidifier performance. (Never use any cooling tower water and heating-purpose water.)
7. Airflow rate can be changed over to Low mode or High mode. Also, if the supply water is hard water, use a water softener because of short life.
8. In case of holding full water in humidifier. * Life of humidifying element is about 3 years (4,000 hours) under the supply water conditions of hardness: 150 mg/l. (Life
of humidifying element is about 1 year (1,500 hours) under the supply water conditions of hardness: 400 mg/l.)
9. OA: fresh air from outdoor. RA: return air from room.
Annual operating hours: 10 hours/day x 26 days/month x 5 months = 1,300 hours.
10. Specifications, design and information here are subject to change without notice.

106
Heat Reclaim Ventilator - VAM Series
Good quality air for every day

Controlling the necessary elements will improve the quality of ventilation.

In case of natural ventilation (Class 3) Conditioned air will be


2
Air Conditioner
released through windows
and exhaust fan.
3
Insects, dust and noise
enter from outside.

Room temperature
1 increases due to
unconditioned outside air.

In case of install Heat Reclaim Heat Reclaim Ventilator (VAM)


Ventilator (VAM) (Class 1)
2
Reduces energy loss by
Air Conditioner
heat recovery.
Prevent insects, dust and
3 noise entering into room
from outside.

Maintain stable room


1 temperature while
ventilation is being done.

Air conditioning load is reduced by heat recovery

EA
(Exhaust air to outdoors)
Total heat exchange ventilation RA
OA (Return air
This unit recovers heat energy lost through ventilation and (Fresh air from from room)
curbs room temperature changes caused by ventilation, thereby outdoors)
conserving energy and reducing the load on the air conditioning system.

Indoor Outdoor SA
(Supply air
to room)
EA
(Exhaust air to Sheet structure
outdoors) Exhaust air
High-humidity air

SA Molecule of water
(Supply air Miscellaneous gas
CO2 molecule, etc.
to room)

material

OA
RA (Fresh air from Supply air Low-humidity air
(Return air outdoors)
from room)
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.

107
AIR TREATMENT EQUIPMENT LINE-UP

Airflow Control

Class 1 Ventilation Class 2 Ventilation Class 3 Ventilation


Both supply air and exhaust System that uses mechanical System that uses natural ventilation
air are controlled by mechanical ventilation for supply air and for supply air and mechanical
ventilation in order to achieve natural ventilation for exhaust air. ventilation for exhaust air.
stable ventilation when required.
Class 2 ventilation is often used for Class 3 ventilation often being used
For common ventilation usage, specific purpose such as positively at area with high odor generation
Class 1 ventilation is able to meet pressured room (Hospital Clean Room, such as kitchen and toilet.
the requirement. Factory Clean Room).

“For example: “For


For example: “For example:
Heat Reclaim Ventilator” Mechanical Ventilation (Supply)” Mechanical Ventilation (Exhaust)”

EA SA kitchen

Positive Negative
pressure(+) pressure(-)
Dust

Fresh Up Operation

By changing the airflow balance, positive pressure or


negative pressure in a room can be achieved in order Exhaust fresh up operation will increase
to prevent pollutants from entering or flowing out. exhaust air volume to prevent pollutants from
flowing to other area.
For example, to prevent dirty air generated indoors from flowing out in
Supply fresh up operation increases the supply air volume through windows and doors, the indoor air is kept under negative
to prevent pollutants from entering into the room. pressure and discharged.
For example, it keeps outdoor pollen and dust from entering when
doors are opened or closed, or through gaps in windows.

Example: Convenience Stores Example: Conference Room

By positive pressure in the room, the entering of dirty outside air, odors By negative pressure in the room, contaminated air and moisture from the
and moisture when opening and closing of doorway is prevented. room is prevented from leaking into other areas.

EA SA EA SA

Dust Negative
Positive pressure(-)
pressure(+) hallway

Doorway

108
Ventilation volume control with CO2 sensor interlocking

&TRKNIKNERGCSGKN%12ĚGUGĚKNěJGROOMUGNěKĚCěKONCKRUOĚTMGVKĚĚDGKNERGCSGFěOJCUGJKIJGRCKRGWEJCNIGKN
ORFGRěORGFTEGěJG%12 level in room.
*TMCNOEETPCNEXKSRGĝGEěGFCS%12 concentration

Change in CO 2 concentration in conference room


(ppm) Meeting room size: 40m2
1600
Even if the number of
1400ppm people decreases, if
1400 ventilation is off, high
CO2 concentration
will not reduce much.
1200
Ventilation Ventilation Ventilation
ON OFF ON
1000
CO2 concentration

Gradual decrease

image: [Link]
in CO2 as
800
ventilation is
550ppm turned on
Experimental data: CO 2 concentration in the conference room.
600
Closed conference rooms often tend to have stagnant air
Number of people Number of people Number of people flow. In long meeting duration or meeting with full occupancy,
400 in the room in the room in the room the concentration of CO 2 increases due to the exhaled CO 2
from human and causes decrease in mind concentration. In

200
4 Person 13 Person 4 Person order to achieve effective ventilation in short period,
mechanical ventilation and natural ventilation should be
combined to replace the air.

0
9 10 11 12 13 14 15 16 17 18 Image is for illustrative purpose.
Times of Day

Equipped with a CO2 sensor to automatically control the ventilation volume


according to the CO2 concentration
Low airflow when there is low occupancy.

Air Conditioner
Heat Reclaim Ventilator

Air Supply Exhaust

New Wired Controller


(BRC1H62W/K)

High airflow when there is an increase in occupancy.

With the new wired controller, BRC1H62W/K,


Air Conditioner the airflow is able to be automatically controlled
Heat Reclaim Ventilator based on CO 2 concentration and CO2 concentration
is able to be visualized on the screen*.
Air Supply Exhaust
*Optional accessory CO 2 sensor is required for this
function.

This CO 2 sensor cannot be used as CO 2


measurement tool. CO2 concentration value will be
subject to change depending on the room
condition and environment.

109
AIR TREATMENT EQUIPMENT LINE-UP

Energy Saving Ventilation (interlocked with air conditioner)

#KREONFKěKONGRCNFUGNěKĚCěKONSXSěGMECNDGKNěGRĚOELGFěOPROUKFGGUGNIRGCěGREOMHORěCNFGNGRIXSCUKNI

The system can be interlocked with Daikin air conditioners to provide energy saving ventilation solution for various situation.

Ve n t i l a t i o n Air conditioning

Interlocking control

Heat Reclaim Ventilator Daikin air conditioner unit

Sensing Sensor Stop Mode

+NSKěTCěKONOHNOJTMCNOEETPCNEXFGěGEěKONěJGOPGRCěKONKSěTRNGFOė

When the "Sensing sensor" installed on the air conditioner detects no occupancy in the room, the ventilation system and air
conditioner system is turned off automatically to reduce energy wastage.

• During group controlling of air


Operation ON Operation OFF conditioner, no occupancy stop
Air conditioner Air conditioner
mode cannot be used. Please
Operation ON Operation OFF
refer to VRV general catalogue
Total heat exchanger for the target indoor units.
Air Supply Exhaust Air Supply Exhaust • When 24-hours ventilation mode is
turned on, the normal operation
mode is changed to 24-hours
With occupants Without occupants ventilation mode.
• Once the absence is detected and
the operation stopped, i t will not
be performed automatically again.

Pre-Cooling/Pre-Heating Control

6JGOPGRCěKONOHUGNěKĚCěKONSXSěGMKSFGĚCXGFFTRKNIěJKSMOFG

During first start up of the air conditioner, the start up operation of ventilation system is delayed in order to reduce additional heat
load from outside air. This will reduce power consumption for the air conditioner as well.

8:00 9:00

• Delay timer settings can


Operation OFF Operation ON be adjusted.

Operation ON Operation ON

Air Supply Exhaust Air Supply Exhaust

110
Auto-Ventilation Mode Changeover Switching

Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating status of the
air conditioner.
When the cooling operation is required in winter, use of heat recovery ventilation is not efficient because the outdoor air
temperature is normally lower than that of the indoor. Thus, the proper use of ventilation mode enhances the heating / cooling
efficiency.
In addition, by installing a humidity sensor (optional), automatic switching by heat (energy) or discomfort index is possible
which further improves energy efficiency and comfort.

Total Heat Exchange Mode


(Cooling operation in summer/Heating operation in winter)
Heat exchange element Indoor air temperature sensor

Exhaust air Return air


Air exhaust fan

Outdoor air intake Air supply fan


Supply air

Outdoor air temperature sensor

Bypass Mode (“Intermediate” season)

Heat exchange element Indoor air temperature sensor

Exhaust air Return air


Air exhaust fan

Outdoor air intake Air supply fan

*Supply air
(Intermediate season)
*atThetheairsame
cannot be supplied
temperature
as the outdoor air because
Outdoor air temperature sensor it is partly heat-exchanged.

111
AIR TREATMENT EQUIPMENT LINE-UP

Night time free cooling operation

Night time free cooling operation is an energy-conserving function that works at night when air conditioners are off. By
ventilating rooms containing office equipment that raises the room temperature, night time free cooling operation reduce
the cooling load when air conditioners are turned on in the morning. It also alleviates feelings of discomfort in the morning
caused by heat accumulated during the night.
The indoor accumulated heat is discharged at night.
- When connected to air conditioners, operation of This reduces the air conditioning load the next day, thereby increasing
heat reclaim ventilator is controlled according to the efficiency.
set temperature, outside air temperature and room
temperature.
- When using only ventilation unit, operation of heat
reclaim ventilator is controlled according to the set
temperature on remote controller.
- Night time free cooling operation is possible during
air conditioners linked operation by centralized
control. Heat is discharged. The load is small so the temperature is
rapidly reduced to a comfortable level.
- Night time free cooling operation is set to “off” in the *Interlocked operation with an air conditioner.
factory settings, so if there is a need to turn on, please
contact Daikin dealer.

Improved Installation Method

1. Improved installation process by changing the dimension and shape


of hanging bracket.
- The nut dropout prevention structure eliminates the need to
replace the hanging bracket even when mounting upside down.
- It also prevents the anti-vibration hanging bracket from interfering
with the equipment.

2. Improved duct installation process with new duct connector location.


- The duct connector is adjusted to be parallel to each other in order
to ease duct installation process.

3. Improves controllability by input / output signals and simplifies


various wiring work.
- Operation, ventilation volume, and ventilation mode can be
switched by external contact input.
- Output signal terminal for external dampers.
- Output signal terminal for abnormal signals and filter signs.

112
Application Example

8GNěKĚCěKONRGĚCěGFPOKNěSěODGěCLGNKNěONOěGFTRKNIFGSKINKNISěCIG

Restaurant
Regardless of the industry,

Problem t he c a us e of d i ffi c ul t y i n
op e ni ng d oor s m a y b e d ue
• The entrance door is difficult to open.
t o i ns uffi c i e nt a i r s up p l y

• The food smell leaks to dining area. (ventilation).

• Hot outside air is coming in when the

entrance door is opened.

The restaurant has negative room pressure due Negative


to insufficient supply air. When the entrance pressure(-)
door is opened, outside air enters into the Dining area kitchen restroom
Entrance
restaurant bringing warm air and pollutants.

3 2
Countermeasure plan

1. Separate ventilation for kitchen and customer dining


area.
2. Provide an air supply vent in the kitchen.
Negative pressure(-)
3. Install a Heat Reclaim Ventilator in the dining area. 1
resolved
Dining area kitchen restroom
Entrance

Office & Shoplot

Problem

• Ventilation cannot be achieved by


opening windows or doors.
• No large windows or doors at the area.

No air movement due to low airflow.


Cannot move the
In the case of windows and doors are located at the front Lack of airflow Shop
air around here.
only, there will be no air movement at the back of the
shop. Air will be stagnant and not well ventilated.

Countermeasure plan

Heat Reclaim Ventilator must be installed


to provide effective mechanical ventilation.

As a result, airflow is able to ventilate all areas of Shop


the shop.

113
AIR TREATMENT EQUIPMENT LINE-UP

Remote Controller & Option List


Standard remote controller: - BRC1H62W/BRC1H62K
Optional remote controller: - Navigation remote controller-BRC1E63, Simplified remote controller-BRC2E61
(Optional controller are connectable with some function limitation.)
BRC1H62W(K) BRC1E63 BRC2E61

Function Detail

A ir co nditioner interlock Interlo ck Heat Reclaim Ventilato r with air conditioner by one
remo te co ntroller.
Ventilation mode Switch the ventilation mode (A utomatic, Heat exchange, Bypass). -

Ventilation airflow rate When using CO 2 sensor, ventilation volume can be changed.
Fresh up indicatio n Indicates that fresh up operatio n is being carried o ut. - -

CO2 indicatio n Indicates value o f CO 2 senso r. - -

Outdoor temperature indication Indicates outdoor air temperature (OA ). - -

Night time free cooling indication Show the night purge icon when is set. - -

24 hours ventilating indication Show the icon when 24hrs operation is set. - -

Indicates that ventilating operation is being carried out even when


Ventilating operation indication night purge operation and 24 hour ventilating operatio n is -
being carried out.
Ventilating standby indication Indicates that ventilating operatio n has been sto pped temporarily - -
during pre-cool / pre-heat control.
Sharing CO2 data Share the CO 2 data to submit from main unit within the group. - -

Additional functions: Installed functions Additional Installation function

Option List:
Type Item VAM250HVE VAM500HVE VAM650HVE
Silencer – KDDM24B100
Additional
Function

Nominal Pipe mm – φ200


High efficiency filter KAF242J25M KAF242J65M
Air filter for replacement KAF241J25M KAF241J65M
Flexible duct (1m) K-FDS151E K-FDS201E
Flexible duct (2m) K-FDS152E K-FDS202E
CO2 sensor BRYC24A25M BRYC24A65M
Humidity sensor BRYH241A100 (for RA) / BRYH242A100 (for OA)
PM2.5 filtration unit BAF249A300 BAF249A500 –
PM2.5 with activated carbon filtration unit BAF249A300C BAF249A500C –
Wired remote controller BRC1H62W (White) / BRC1H62K (Black) / BRC1E63 / BRC2E61
Residential central remote controller DCS303A51*1
Controlling device

Central remote controller DCS302CA61


Centralised controlling device
Unified ON/OFF controller DCS301BA61
Schedule Timer DST301BA61
Wiring adaptor for electrical appendices KRP2A62
Installation box for adaptor KRP1C18A90
PCB adaptor
For heater control kit BRP4A50A
PCB adaptor for wiring KRP1C18

Type Item VAM800HVE VAM1000HVE VAM1500HVE VAM2000HVE

KDDDM24B100 KDDDM24B100 x 2
Additional

Silencer
function

Nominal pipe mm ij250


High efficiency filter KAF242K100M KAF242K100M x 2
Air filter for replacement KAF241K100M KAF241K100M x 2
Flexible duct (1m) K-FDS251E
Flexible duct (2m) K-FDS252E
CO2 sensor BRYC24A100M
Humidity sensor BRYH241A100 (for RA) / BRYH242A100 (for OA)
PM2.5 filtration unit BAF429A20A
PM2.5 with activated carbon filtration unit BAF429A20AC
Wired remote controller BRC1H62W (White) / BRC1H62K (Black) / BRC1E63 / BRC2E61
Centralised

DCS303A51* 1
controlling

Residential central remote controller


device

Central remote controller DCS302CA61


Controlling device

Unified ON/OFF controller DCS301BA61


Schedule Timer DST301BA61
Wiring adaptor for electrical appendices KRP2A62
adaptor

Installation box for adaptor KRP1C18A90


PCB

For heater control kit BRP4A50A


PCB adaptor for wiring KRP1C18
* 1 For residential only. When connect with a Heat Reclaim Ventilator (VAM), you can only switch the power ON/OFF. It cannot be used with other central control equipment.

114
Air Treatment Equipment
Airflow rate control with CO2 sensor

The CO2 sensor controls airflow rate so that it best matches the changes of CO2 level in the room. This prevents
energy losses from over-ventilation while maintaining indoor air quality with optional CO2 sensor.

Example of CO2 sensor operation in an office room:


7- stage control with different airflow levels CO2 level
Airflow rate for ventilation
If airflow rate
were constant
Airflow rate down

Airflow rate for ventilation


Reference
value
Airflow rate down
CO2 level

Airflow rate up

indicates energy savings!


Airflow rate up Energy wastage for ventilation is reduced.
Air conditioning load for ventilation is reduced.

9 10 11 12 13 14 15 16 17 18 19 20 21 Hours

Sales Sales
Morning Lunch Overtime
personnel leave personnel
meetings Time work
office return

Heat Reclaim Ventilator

Air conditioner

Many people increase CO2 level: Fewer people decrease CO2 level:
Airflow rate up Airflow rate down

Automatic Ventilation Mode Switching (Bypass control) with Humidity sensor

Suitable ventilation mode depending on condition will be switched automatically.


The ventilation unit detects room temperature and outside air temperature, then automatically switches to suitable ventilation mode to
provide higher energy-savings. By installing humidity sensor (optional item), the mode will be switched automatically based on the
amount of heat (energy) and discomfort index to further improve energy saving and comfort. *1

Free cooling after comparing temperature Free cooling


*1 “Energy saving ventilation
Energy saving Energy saving mode” or “Comfortable
Operation Operation ventilation mode” can be
selected by local setting.
Air Supply Exhaust Air Supply Exhaust
Indoor Indoor
Outdoor temperature is
Outdoor temperature is

temperature is temperature is
lower than indoor
lower than indoor

higher lower

115
TECHNICAL SPECIFICATIONS

Unit

MODEL VAM250HVE VAM500HVE VAM650HVE


Power Supply 1-phase, 220-240 V/220V, 50/60 Hz
Ultra-High 60.5 / 60.5 61.5 / 61.5 59.5 / 59.5
For
High % 60.5 / 60.5 61.5 / 61.5 59.5 / 59.5
Temp. Cooling
Exchange Low 65.0 / 65.5 63.0 / 64.0 62.5 / 63.0
Efficiency Ultra-High 76.5 / 76.5 80.0 / 80.0 74.5 / 74.5
(50/60 Hz)
For
High % 76.5 / 76.5 80.0 / 80.0 74.5 / 74.5
Heating
Low 78.5 / 79.0 81.5 / 82.5 76.5 / 77.0
Ultra-High 60.0 / 60.0 62.5 / 62.5 60.0 / 60.0
For
High % 60.0 / 60.0 62.5 / 62.5 60.0 / 60.0
Enthalpy Cooling
Exchange Low 61.5 / 62.0 64.0 / 65.0 62.5 / 63.0
Efficiency Ultra-High 69.5 / 69.5 71.0 / 71.0 68.0 / 68.0
(50/60 Hz) For
High % 69.5 / 69.5 71.0 / 71.0 68.0 / 68.0
Heating
Low 73.0 / 73.5 72.5 / 73.5 69.5 / 71.5
Ultra-High 126-141 / 172 296-326 / 390 381-426 / 472
Heat
Exchange High W 114-123 / 144 248-261 / 329 307-319 / 413
Power Mode
Low 75-83 / 79 223-233 / 268 264-276 / 332
Consumption
(50/60 Hz) Ultra-High 126-141 / 172 296-326 / 390 381-426 / 472
Bypass Mode High W 114-123 / 144 248-261 / 329 307-319 / 413
Low 75-83 / 79 223-233 / 268 264-276 / 332
Ultra-High 33.0-34.0 / 33.5 36.0-37.0 / 38.5 37.5-38.0 / 38.0
Heat
Exchange High dBA 31.0-32.5 /28.0 35.0-36.0 / 35.0 36.0-36.5 / 37.0
Mode
Sound Level Low 23.0-25.5 / 21.0 32.0-34.0 / 31.0 34.0-35.0 / 32.5
(50/60 Hz) Ultra-High 33.0-34.0 / 34.5 36.0-37.0 / 38.5 39.5-40.0 / 42.0
Bypass Mode High dBA 31.5-32.5 / 29.0 35.0-36.0 / 35.0 38.0-38.5 / 39.0
Low 23.5-25.5 / 21.5 32.0-34.0 / 31.0 35.5-36.5 / 33.5
Casing Galvanised steel plate
Insulation Material Self-extinguishable polyurethane foam
Dimensions (HxWxD) mm 278 x 551 x 810 338 x 832 x 973
Machine Weight kg 22 41 43

Air to air cross flow total heat


Heat Exchange System
(Sensible heat + latent heat) exchange

Heat Exchange Element Material Specially processed nonflammable paper


Air Filter Multidirectional fibrous fleeces
Type Sirocco fan
Ultra- High 250 / 250 500 / 500 650 / 650
Airflow
Rate High m3/h 250 / 250 500 / 500 650 / 650
(50/60 Hz)
Low 165 / 145 470 / 420 570 / 495
Fan
Ultra- High 115-130 / 135 165-190 / 245 185-190 / 260
External Static
Pressure High Pa 80-90 / 60 140-175 / 180 140-155 / 210
(50/60 Hz)
Low 35-75 / 20 124-155 / 127 108-119 / 122
Motor Output kW 0.030 x 2 0.100 x 2 0.170 x 2
Net Supply Airflow Ratio Ultra-High % 90
Indoor side mm
Connection Duct Diameter φ150 φ200 φ200
Outdoor side mm
Unit Ambient Condition -15ºC–50ºC DB, 80%RH or less

* Values for electrical current, power consumption, and efficiency are at the above above-stated airflow.
* Exchange efficiencies are values based on performance codes and air conditions that comply with JIS B8628:2017.
* Temperature exchange efficiency and enthalpy exchange efficiency vary according to the ratio of supply air and exhaust air and air conditions.
* Operation sound is an anechoic chamber conversion that complies with JISB8628:2017. When measured under actual installation conditions, the operation sound is usually greater due to
ambient noise and reverberation.

116
Unit

Model VAM800HVE VAM1000HVE VAM1500HVE VAM2000HVE


Power Supply 1-phase, 220-240 V / 220 V, 50/60 Hz
Ultra-High 61.5 / 61.5 58.0 / 58.0 61.5 / 61.5 58.5 / 58.5
For
High 㸣 61.5 / 61.5 58.0 / 58.0 61.5 / 61.5 58.5 / 58.5
Temp. Cooling
Exchange Low 64.0 / 65.0 61.5 / 62.0 65.5 / 66.0 65.5 / 65.5
Efficiency
Ultra-High 77.5 / 77.5 74.0 / 74.0 77.5 / 77.5 73.5 / 73.5
(50/60 Hz) For
Heating High 㸣 77.5 / 77.5 74.0 / 74.0 77.5 / 77.5 73.5 / 73.5
Low 78.5 / 79.5 76.0 / 76.5 79.5 / 80.0 76.5 / 77.0
Ultra-High 63.0 / 63.0 60.0 / 60.0 63.0 / 63.0 60.0 / 60.0
For
High 㸣 63.0 / 63.0 60.0 / 60.0 63.0 / 63.0 60.0 / 60.0
Enthalpy Cooling
Exchange Low 64.5 / 65.5 62.0 / 62.5 65.5 / 66.0 64.5 / 64.5
Efficiency Ultra-High 72.0 / 72.0 68.5 / 68.5 72.0 / 72.0 68.0 / 68.0
(50/60 Hz) For
High 㸣 72.0 / 72.0 68.5 / 68.5 72.0 / 72.0 68.0 / 68.0
Heating
Low 74.0 / 75.0 72.0 / 72.5 74.0 / 75.0 71.0 / 71.5
Ultra-High 644-684 / 829 683-736 / 883 1,274-1,353 / 1,645 1,365-1,471 / 1,763
Heat
Exchange High W 603-612 / 712 621-656 / 763 1,207-1,225 / 1,423 1,241-1,311 / 1,526
Power Mode
Low 504-544 / 562 539-569 / 594 1,008-1,089 / 1,125 1,079-1,138 / 1,188
Consumption
(50/60 Hz) Ultra-High 644-684 / 829 683-736 / 883 1,274-1,353 / 1,645 1,365-1,471 / 1,763
Bypass High W 603-612 / 712 621-656 / 763 1,207-1,225 / 1,423 1,241-1,311 / 1,526
Mode
Low 504-544 / 562 539-569 / 594 1,008-1,089 / 1,125 1,079-1,138 / 1,188
Ultra-High 41.5-42.5 / 41.0 42.0-43.0 / 42.5 43.0-44.0/ 44.0 43.5-44.0 / 44.5
Heat
Exchange High dBA 39.5-41.0 / 37.0 40.0-41.0 / 38.0 41.0-42.5 / 39.0 41.5-43.0 / 40.0
Mode 36.0-38.5 / 33.0 38.0-39.5 / 34.5 38.0-40.5 / 35.0 39.0-41.0 / 36.5
Sound Level Low
(50/60 Hz) Ultra-High 41.5-42.5 / 41.0 42.0-43.0 / 42.5 43.0-44.0 / 44.0 43.5-44.0 / 44.5
Bypass High dBA 39.5-41.0 / 37.0 40.0-41.0 / 38.0 41.0-42.5 / 39.0 41.5-43.0 / 40.0
Mode
Low 36.0-38.5 / 33.0 38.0-39.5 / 34.5 38.0-40.5 / 35.0 39.0-41.0 / 36.5
Casing Galvanised steel plate
Insulation Material Self-extinguishable polyurethane foam
Dimensions (H x W x D) mm 387 x 1,012 x 1,110 785 x 1,012 x 1,110
Machine Weight kg 63 63 138 138
Heat Exchange System Air to air cross flow total heat (Sensible heat + latent heat) exchange
Heat Exchange Element Material Specially processed nonflammable paper
Air Filter Multidirectional fibrous fleeces
Type Sirocco fan
Ultra-High 800 / 800 1,000 / 1,000 1,500 / 1,500 2,000 / 2,000
Airflow
Rate High m3/h 800 / 800 1,000 / 1,000 1,500 / 1,500 2,000 / 2,000
(50/60 Hz) Low 720 /610 880 / 835 1,350 / 1,250 1,650 / 1,580
Fan
External Ultra-High 210-235 / 250 205-225 / 220 195-215 / 235 190-210 / 210
Static
High Pa 170-215 / 140 155-195 / 100 150-180 / 125 140-180 / 85
Pressure
(50/60 Hz) Low 138-174 / 81 115-150 / 70 123-146 / 88 96-123 / 53
Motor Output kW 0.190 x 2 0.190 x 4
Net Supply Airflow Ratio Ultra-High 㸣 90 90 90 90
Indoor side mm ij250㽢4 ij250㽢4
Connection Duct Diameter ij250 ij250
Outdoor side mm 䕕䠄680㽢290䠅㽢2 䕕䠄680㽢290䠅㽢2
Unit Ambient Condition -15ºC–50ºC DB, 80%RH or less
* Values for electrical current, power consumption, and efficiency are at the above above-stated airflow.
* Exchange efficiencies are values based on performance codes and air conditions that comply with JIS B8628:2017.
* Temperature exchange efficiency and enthalpy exchange efficiency vary according to the ratio of supply air and exhaust air and air conditions.
* Operation sound is an anechoic chamber conversion that complies with JISB8628:2017. When measured under actual installation conditions, the operation sound is usually greater
due to ambient noise and reverberation.

117
VRV X Catalogue India_A4

WORLD’S LEADING AIR CONDITIONING


Note: COMPANY FROM JAPAN

• Ask an authorised Daikin dealer to install Daikin products. Do not try to install the product yourself
or get it installed by any unauthorised dealer. Improper installation can result in water or refrigerant
leakage, electrical shock, fire or explosion. Warranty of the product shall be void if not installed by
an authorised Daikin dealer.

• Use only those parts and accessories supplied or specified by Daikin. Ask authorised Daikin dealer
for any repair or component. Warranty of the product / component shall be void if
non-specified spares are used or repaired by a non Daikin dealer.
PRESENTING THE NEW
• Please ensure to install ELCB (Earth Leakage Circuit Breaker) for outdoor units to prevent ground
fault effects.

• Read the user's manual carefully before using the product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.

For any enquiry, either call the numbers mentioned below or contact your nearest Daikin dealer.
Heat Pump | Cooling Only

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

About ISO 9001 About ISO 14001


ISO 9001 is a plant certification system ISO 14001 is the standard defined by the
defined by the International Organization for International Organization for Standardization
Standardization (ISO) relating to quality (ISO) relating to environmental management
assurance. ISO 9001 certification covers systems. Our group has been acknowledged by
quality assurance aspects related to the an internationally accredited compliance
“design, development, manufacture, organisation as having an appropriate programme
installation, and supplementary service” of of environmental protection procedures and
products manufactured at the plant. activities to meet the requirements of ISO 14001.
JMI-0107 JQA-1452

CUSTOMER CONTACT CENTRE:


011-40319300, 1860-180-3900
customerservice@[Link]

Ahmedabad-Tel: 079-40013100 Kolkata-Tel: 033-40608019/40659544 To know more, give a missed call or SMS:
Bengaluru-Tel: 080-25722336/25722337 Lucknow-Tel: 0522-4309858/59/60 <DAIKIN> to 9210188999
Bhubaneshwar-Tel: 0674-2554677 Ludhiana-Tel: 0161-5077028/29/30 Visit us at: [Link]
Chandigarh-Tel: 0172-4947200/30 Mumbai-Tel: 022-62321666
Chennai-Tel: 044-40807676 Patna-Tel: 0612-2582282 Follow us on:
Cochin-Tel: 0484-4038646 Pune-Tel: 020-25560300 [Link]/daikinindia
Delhi-Tel: 011-43834400/5500 Raipur-Tel: 0771-4911225 [Link]/daikinindia
Ghaziabad-Tel: 0120-4205851 Ranchi-Mob: 7008704566 [Link]/daikinindia
Indore-Tel: 0731-4005864 Secunderabad-Tel: 040-49134283 [Link]/daikin–airconditioning-india-pvt.-ltd.
Jaipur-Tel: 0141-2218903/04/05/06 Vijayawada-Tel: 0866-2952226/24/25 [Link]/user/DaikinACIndia

For more product information:


DAIPL-2017/23-VRVX-1A

For More information X’ TENSIVE X’ TRA X’ CELLENT X’ TENDED