IEC 61850 - Communication Networks and Systems in Substations: An Overview of Computer Science
Jianqing Zhang and Carl A. Gunter University of Illinois at Urbana-Champaign
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
2
Background I: Power Substation
Intelligent Electronic Device
Microprocessor-based controllers of power system equipment
e.g. circuit breaker, protective relay
Receive digitalized data from sensors and power equipment Issue control commands in case of anomalies to maintain the desired status of power grid
e.g. tripping circuit breakers
4
Why Standards Are Needed
Interoperability and Integration
No standard for data representation or how devices should look and behave to network applications
Intuitive device and data modeling and naming
Hierarchical and structured, rather than plain formatted
Fast and convenient communication
Lower cost for installation, configuration and maintenance
Wire connected legacy devices
5
History of IEC 61850
UCA: Utility Communication Architecture Protocols Data models Abstract service definitions
GOAL: One International Standard
IEC 61850
IEC 60870-5 A communication profile for sending basic telecontrol messages between two systems Based on permanent directly connected data circuits
6
IEC 61850 Substation Architecture
IEC61850-enabled IEDs get digitalized power grid condition data via process bus and merge units IEDs communicate with each other using substation buses Legacy devices use IEC61850 wrapper
7
Core Components of IEC 61850
An object model describing the information available from the different primary equipment and from the substation automation functions
Abstract definitions of services, data and Common Data Class, independent of underlying protocols
A specification of the communication between the IEDs of the substation automation system.
Maps the services to actual protocols
A configuration language
Exchange configuration information
8
IEC 61850 Standards
Basic principles Glossary General Requirements System and project management Part 1 Part 2 Part 3 Part 4 Part 5 Part 6 Part 7
Communication requirements Substation Automation System Configuration
Basic Communication Structure
Primary Parts
Part 8
Mapping to MMS and Ethernet
Sampled Measured Values
Mapping to Ethernet
Part 9
Conformance testing
Part 10
IEC 61850 Primary Parts
Part 6-1: Substation Configuration Language (SCL) Part 7-2: Abstract Communications Service Interface (ACSI) and base types Part 7-3: Common Data Classes (CDC) Part 7-4: Logical Nodes Part 8-1: Specific Communications Service Mappings (SCSM) MMS & Ethernet Part 9-2: SCSM - Sampled Values over Ethernet Part 10-1: Conformance Testing
10
IEC 61850 Is Unique
Not a recast serial RTU protocol Designed specifically for LANs to lower life cycle cost to use a device:
Cost to install, configure, and maintain
Real object-oriented approach for SA:
Supports standardized device models using names instead of object/register numbers and indexes. Standardized configuration language (SCL). Feature rich with support for functions difficult to implement otherwise.
11
Benefits of IEC 61850
Supports a comprehensive set of substation functions Easy for design, specification, configuration, setup, and maintenance.
High-level services enable self-describing devices & automatic object discovery Standardized naming conventions with power system context Configuration file formats eliminate device dependencies and tag mapping and enables exchange of device configuration.
Strong functional support for substation communication
Higher performance multi-cast messaging for inter-relay communications
Extensible enough to support system evolution
12
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
13
IEC 61850 Modeling Approach
14
IEC 61850 Class Model
Data Objects
ctrVal stVal
Physical Device
1 1..*
Access by network address
Logical Nodes
XCBR1 XCBR2
Logical Device
1 1..*
Collections of logical nodes, implemented in one IED, i.e. not distributed
Logical Device (e.g. Breaker1)
Logical Node
1 1..*
Functions in the real devices e.g. XCBR: circuit breaker
Data
Physical Device
(Protection device)
1 1..*
Data Attribute
Properties of logic nodes e.g. Position Dedicated data values Structured and well-defined semantic Exchanged according to well-defined rules and performance Configuration: assign selected values and exchange mechanisms
15
Logical Node
A named grouping of data and associated services that is logically related to some power system function.
dddXCBR1
Logical Node Instance # Logical Node Name per IEC 61850-7-4 (breaker) Optional Application Specific Prefix
16
Data Example of Logical Node
Attr. Name Attr. Type Functional Constraint TrgOp Value/Value Range M/O/C
ctrVal BOOLEAN CO
stVal CODED ENUM ST dchg
OFF (False) | off | on | badON (True) state O M
Common Data Class: Double Points Control
17
Logical Nodes Information Categories
Common logical node information
Information independent from the dedicated function represented by the LN, e.g., mode, health, name plate, ...
Status information
Information representing either the status of the process or of the function allocated to the LN, e.g., switch type, switch operating capability
Settings
Information needed for the function of a logical node, e.g., first, second, and third reclose time
Measured values
Analogue data measured from the process or calculated in the functions like currents, voltages, power, etc., e.g., total active power, total reactive power, frequency
Controls
Data, which are changed by commands like switchgear state (ON/OFF), resetable counters, e.g., position, block opening
88 pre-defined logical nodes and extensible
18
Logical Node Class Example - XCBR
SPS
19
Single Point Status (SPS) CDC (e.g. Loc)
stVal
Attribute Name
Type
Functional Constraint
Range of Values
Mandatory/ Optional 20
Object Name Structure
Relay1/XCBR1$Loc$stVal
Attribute Data Logical Node Logical Device
21
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
22
IEC 61850 Communication Scope
1. 2. Protection-data exchange between bay and station level Protection-data exchange between bay level and remote protection Data exchange within bay level CT and VT instantaneous data exchange between process and bay levels Control-data exchange between process and bay level Control-data exchange between bay and station level Data exchange between substation and remote engineers workplace Direct data exchange between the bays especially for fast functions like interlocking Data exchange within station level Control-data exchange between substation (devices) and a remote control center
3. 4.
5. 6. 7.
8.
9. 10.
23
ACSI: Abstract Communications Service Interface
None timing critical message transmitting
Used for configuration, maintenance, log Three basic components
A set of objects A set of services to manipulate and access those objects A base set of data types for describing objects
24
ACSI Server Building Block
25
Basic Information Models
SERVER
Represents the external visible behavior of a (physical) device Communicate with a client Send information to peer devices
LOGICAL-DEVICE (LD)
Contains the information produced and consumed by a group of domain-specific application functions, which are defined as LOGICAL-NODEs
LOGICAL-NODE (LN)
Contains the information produced and consumed by a domain specific application function
DATA
Status and meta-information of object it presents in substation Provide means to specify typed information
26
Services Operating on Data
DATA-SET
The grouping of data and data attributes A view of DATA
SETTING-GROUP
How to switch from one set of setting values to another one How to edit setting groups
REPORT and LOG
Describe the conditions for generating reports and logs based on parameters set by the client Reports may be sent immediately or deferred Logs can be queried for later retrieval
Generic Substation Event (GSE) control block (GSSE/GOOSE)
Supports a fast and reliable system-wide distribution of input and output data values
Sampled Values Transmission control block
Fast and cyclic transfer of samples
27
Services Operating on Data (cont.)
Control
Provide client mechanisms to control the DATA related to external devices, control outputs, or other internal functions
Substitution
Support replacement of a process value (measurands of analogue values or status values) by another value
Get/Set
Retrieve or write particular DataAttribute Values
Dir/Definition
Retrieve ObjectReferences and definitions of all sub-objects.
28
Other Services
Association
How the communication between the various types of devices is achieved Two-party and Multicast Access Control
Time Synchronization
Provide the UTC synchronized time to devices and system
File Transfer
Defines the exchange of large data blocks such as programs
29
Communication Model
Two-Party-Application-Association (TPAA)
A bi-directional connection-oriented information exchange Reliable and end-to-end flow control
MultiCast-Application-Association (MCAA)
A unidirectional information exchange Between one source (publisher) and one or many destinations (subscriber) The subscriber shall be able to detect loss and duplication of information received The receiver shall notify the loss of information to its user and shall discard duplicated information
30
Principle of TPAA and MCAA
Two-Party-Application-Association
MultiCast-Application-Association
31
ACSI Communication Model
32
Generic Substation Event (GSE) Model
A fast and reliable system-wide distribution of input and output data values
Based on a publisher/subscriber mechanism
Simultaneous delivery of the same generic substation event information to more than one physical device through the use of multicast/broadcast services GSSE/GOOSE
33
GOOSE: Generic Object Oriented Substation Event
Used for fast transmission of substation events, such as commands, alarms, indications, as messages A single GOOSE message sent by an IED can be received several receivers
Take advantage of Ethernet and supports real-time behavior
Examples:
Tripping of switchgear Providing position status of interlocking
34
Generic Object Oriented Substation Event (GOOSE)
Exchange of a wide range of possible common data organized by a DATA-SET
35
GSSE: Generic Substation Status Event Provide backward compatibility with the UCA GOOSE Just support a fixed structure of the data to be published
Based on multicast
36
Generic Substation State Event (GSSE)
Convey state change information (a simple list of status information)
37
Application Of GSE Model
38
Application of GSE Model (cont.)
1. PDIS (distance protection) detects a fault 2. PTRC issues a <Trip> command to XCBR0 (circuit break); the switchgear opens the circuit breaker; 3. The new status information is immediately sent; the reporting model may report the change;
4. RREC (auto-reclosing) issues <Reclose> to XCBR0 according to the configured behavior;
5. XCBR0 receives the GOOSE message with the value <Reclose>; the switchgear closes the circuit breaker. XCBR0 issues another GOOSE message with the new position value
39
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
40
Mapping To Real Communication Systems
IEC 61850 is just a high level description of substation automation Use MMS to implement IEC61850 Map each IEC 61850 object to a MMS object Map each IEC 61850 service to a MMS operation
All but GOOSE messages and transmission of sampled values are mapped to MMS protocol stack
41
MMS: Manufacturing Message Specification
ISO 9506 standard used in Control Networks A reduced OSI stack with the TCP/IP protocol in the transport/network layer Ethernet and/or RS-232C as physical media Defines communication messages transferred between controllers as well as between the engineering station and the controller (e.g. downloading an application or reading/writing variables)
42
ACSI Objects Mapping
ACSI Object Class (7-2)
SERVER class LOGICAL DEVICE class LOGICAL NODE class DATA class
MMS Object (8-1)
Virtual Manufacturing Device (VMD) Domain Named Variable Named Variable
DATA-SET class
SETTING-GROUP-CONTROL-BLOCK class REPORT-CONTROL-BLOCK class LOG class LOG-CONTROL-BLOCK class GOOSE-CONTROL-BLOCK class GSSE-CONTROL-BLOCK class CONTROL class Files
Named Variable List
Named Variable Named Variable Journal Named Variable Named Variable Named Variable Named Variable Files
43
ACSI Services Mapping
ACSI Services (7-2) LogicalDeviceDirectory GetAllDataValues GetDataValues SetDataValues GetDataDirectory GetDataDefinition GetDataSetValues SetDataSetValues CreateDataSet DeleteDataSet GetDataSetDirectory Report (Buffered and Unbuffered) GetBRCBValues/GetURCBValues SetBRCBValues/SetURCBValues GetLCBValues SetLCBValues QueryLogByTime QueryLogAfter GetLogStatusValues Select SelectWithValue Cancel Operate Command-Termination MMS Services (8-1) GetNameList Read Read Write GetNameList GetVariableAccessAttributes Read Write CreateNamedVariableList DeleteNamedVariableList GetNameList InformationReport Read Write Read Write ReadJournal ReadJournal GetJournalStatus Read/Write Read/Write Write Write Write
44
Protocol Mapping Profile
45
IEC61850 Protocol Stack
ACSI Core Services SMV GOOSE
Application Presentation Session Transport
MMS (ISO/IEC 9506)
ISO Presentation (ISO 9576) ASN.1 (ISO/IEC 8824/8825)
ISO Session (ISO 8327) ISO Transport (ISO/IEC 8073) Transport Class 0 RFC 1006 TCP (RFC 793)
Network Data Link
IP (RFC 791) ARP (RFC 826) Logical Link Control (ISO 8802), 802-3 Ethertype Media Access Control (ISO 8803)
46
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
47
Sampled Measured Values
A method for transmitting sampled measurements from transducers such as CTs, VTs, and digital I/O.
Enables sharing of I/O signals among IEDs Supports 2 transmission methods:
Multicast service (MSVC) over Ethernet Unicast (point-to-point) service (USVC) over serial links.
48
SMV Application
49
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
50
SCL: Substation Configuration Language
Purpose: interoperable exchange of communication system configuration data between an IED configuration tool and a system configuration tool from different manufacturers.
A formal description of
Relations between substation automation system and the switchyard Relations of the switchyard structure to the SAS functions (logical nodes) configured on the IEDs
51
Intended Engineering Process With SCL
1.
Functional specification input to SAS engineering
A system specification in terms of the single line diagram, and allocation of logical nodes (LN) to parts and equipment of the single line to indicate the needed functionality.
2.
IED capability description results after IED pre-engineering
Pre-configured IEDs with a fixed number of logical nodes (LNs), but with no binding to a specific process . may only be related to a very general process function part. Pre-configured IEDs with a pre-configured semantic for a process part of a certain structure, for example a double bus-bar GIS line feeder.
3.
SA system description - result after SAS engineering
Complete process configuration with all IEDs bound to individual process functions and primary equipment, enhanced by the access point connections and possible access paths in sub-networks for all possible clients. As item d) above, but additionally with all predefined associations and client server connections between logical nodes on data level. This is needed if an IED is not capable of dynamically building associations or reporting connections (either on the client or on the server side).
52
Approach
Define an object model describing the IEDs, their communication connections, and their allocation to the switchyard (Part 7) Describe how this model shall be represented in a file to be exchanged between engineering tools in a standardized way (Part 6)
53
Information Flow in the Configuration Process
54
Information Flow in the Configuration Process (cont.)
IED Configurator
A manufacturer-specific tool used to import or export SCL files Provides IED-specific settings and generates IED specific configuration files Loads the IED configuration into the IED
System Configurator
An IED independent system level tool used to import or export SCL files Imports configuration files from several IEDs, as needed for system level engineering Adds system information shared by different IEDs (by the configuration engineer) Generates a substation related configuration file, which may be fed back to the IED Configurator for system related IED configuration Reads a system specification file for example as a base for starting system engineering, or to compares it with an engineered system for the same substation.
55
SCL Object Model
The primary (power) system structure
Which primary apparatus functions are used How the apparatus are connected
The communication system
How IEDs are connected to subnetworks and networks And at which of their communication access points (communication ports)
The application level communication
How data is grouped into data sets for sending How IEDs trigger the sending and which service they choose, which input data from other IEDs is needed
Each IED
The logical devices configured on the IED The logical nodes with class and type belonging to each logical device The reports and their data contents Logged data The (pre-configured) associations
Instantiable logical node (LN)
Mandatory, optional and user defined DATA (here abbreviated DO) as well as optional services
56
SCL Object Model (cont.)
57
Substation Model
Substation: the object identifying a whole substation. VoltageLevel: an identifiable, electrically connected substation part having an identical voltage level. Bay: an identifiable part or sub-function of the switchyard (substation) within one voltage level. Equipment: an apparatus within the switchyard. The single line diagram of a switchyard shows the electrical connections between these primary devices. SubEquipment: a part of an Equipment, which might especially be one phase of a three phase equipment. ConnectivityNode: the (electrical) connectivity node object connecting different primary devices. Typical connectivity node examples are: connecting nodes within a bay, bus bars connecting several bays in the same voltage level, lines connecting bays in different substations Terminal: an electrical connection point of a primary apparatus at single line level. A terminal can be connected to a ConnectivityNode. Within SCL terminals can be explicitly named, or exist implicitly.
58
Product (IED) Model
IED: a substation automation device performing SA functions by means of logical nodes (LNs). Server: a communication entity within an IED. It allows access via the communication system and its only access point to the data of the logical devices and logical nodes contained in the server. LDevice: logical device (LD) LNode: logical node (LN) DO: the DATA contained in the LNs
59
Communication System Model
Subnetwork: a connecting node for direct (link layer) communication between access points.
One LD should have at most one connection to a subnetwork
Access point: a communication access point of the LD(s) of an IED to a sub-network.
One access point can serve multiple LDs LNs on one LD can access different subnetworks via APs on different LDs
Router: a function hosted on an IED which extends access to servers connected to another subnetwork at another access point of the hosting IED Clock: a master clock used to synchronize the internal clocks of all (other) IEDs connected to this ubnetwork.
60
SCL File Types
SSD: System Specification Description
Data exchange from a system specification tool to the system configuration tool. Describes the single line diagram of the substation and the required logical nodes.
ICD: IED Capability Description
Data exchange from the IED configuration tool to the system configuration tool. Describes the capabilities of an IED.
SCD: Substation Configuration Description
Data exchange from the system configuration tool to IED configuration tools. Describes all IEDs, a communication configuration section and a substation description section.
CID: Configured IED Description
Data exchange from the IED configuration tool to the IED. Describes an instantiated IED within a project.
The communication section contains the current address of the IED. The substation section related to this IED may be present and then shall have name values assigned according to the project specific names. Possibly a stripped-down SCD file to what the concerned IED shall know.
61
SCL UML Diagram Overview
62
SCL Syntax Elements: Header
Header: identify an SCL configuration file and its version
Text History
Hitem
63
Header UML Diagram
64
SCL Syntax Elements: Header and Substation
Substation: describes the functional structure of a substation; identifies the primary devices and their electrical connections
65
Substation UML Diagram
66
SCL Syntax Elements - IED
IED: describes the (pre-) con- LN DataSet figuration of an IED: access ReportControl points, the logical devices, and LogControl logical nodes. DOI
Services (ACSI services) AccessPoint
Server xor LN (LN0)
Inputs
LN0 (extends LN)
GSEControl SampledValueControl SettingControl SCLControl Log
Server
Authentication LDevice Association
67
IED UML Diagram
68
SCL Syntax Elements Communication
Communication
SubNetwork
BitRate ConnectedAP
Address GSE SMV PhysConn
69
Communication UML Diagram
70
SCL Syntax Elements DataTypeTemplate
DataTypeTemplate
LNodeType: an instantiable logical node type
DO
DOType: an instantiable DATA type
SDO xor DA
DAType: an instantiable structured attribute type EnumType: An enumeration type
EnumVal
71
DataTypeTemplate UML Diagram
72
Agenda
Overview Data modeling approach Communication model Communication service mapping Sampled measured values Configuration description language Conclusion Reference
73
Conclusion
IEC 61850 is a migration from the analog world to the digital world for substation
Standardization of data names Creation of a comprehensive set of services Implementation over standard protocols and hardware Definition of a process bus.
Multi-vendor interoperability has been demonstrated Discussions are underway to utilize IEC 61850 as the substation to control center communication protocol IEC 61850 will become the protocol of choice as utilities migrate to network solutions for the substations and beyond.
74
Reference
IEC 61850 Communication Networks and Systems In Substations, Technical Committee 57, International Electrotechnical Commission, Secure Intelligent Electronic Devices (SIEDs). C. A. Gunter, S. T. King, J. Zhang. PSERC 2007 Overview of IEC 61850 and Benefits, R. E. Mackiewicz. PES TD 2005/2006
IEC 61850 Communication Networks and Systems In Substations: An Overview for Users. D. Baigent, M. Adamiak and R. Mackiewicz. SIPSEP 2004