Actual Values: Table 5-1 Actual Value Message Map
Actual Values: Table 5-1 Actual Value Message Map
ACTUAL VALUES
OVERVIEW
5. ACTUAL
VALUES
5.1
OVERVIEW
ACTUAL
ACTUAL
ACTUAL
!"GENERATOR STATUS
!"CURRENT METERING
!"PARAMETER AVERAGES
!"VOLTAGE METERING
!"RTD MAXIMUMS
!"ALARM STATUS
!"POWER METERING
!"ANALOG IN MIN/MAX
!"TRIP PICKUPS
!"TEMPERATURE
!"ALARM PICKUPS
!"DEMAND METERING
!"DIGITAL INPUTS
!"ANALOG INPUTS
!"SPEED
ACTUAL
ACTUAL
ACTUAL
!"TRIP COUNTERS
!"GENERAL COUNTERS
!"CALIBRATION INFO.
!"TIMERS
In addition to the Actual Value messages, there are also Diagnostic messages and Flash messages that appear only when certain
conditions occur. They are described later in this chapter.
5-1
A1 STATUS
5. ACTUAL VALUES
5.2 A1 STATUS
ENTER
"
#
GENERATOR THERMAL
$ CAPACITY USED: 0 %
ESCAPE
MESSAGE
Offline
ESCAPE
MESSAGE
! GENERATOR STATUS:
ESCAPE
% ON OVERLOAD: Never
RANGE: 0 -100
NOTE: this message is seen only if the thermal model is enabled
RANGE: 0 - 10000s, Never
NOTE: this message is seen only if the thermal model is enabled
DESCRIPTION:
These messages describe the status of the generator at any given point in time. If the generator has been tripped, is still offline, and the
489 has not yet been reset, the generator status will be Tripped. The thermal capacity used reflects an integrated value of both the
stator and rotor thermal capacity used. The values for estimated trip time on overload will appear whenever the 489 thermal model picks
up on the overload curve.
ENTER
"
#
5-2
RANGE: Mon/Day/Year
NOTE: this message is seen only if there has been a trip
RANGE: 0-3600
NOTE: this message is seen only if the function is assigned an input
RANGE: 0-999999
NOTE: this message represents current measured from the output CTs, seen only if there has been a trip
RANGE: 0 - 999999
NOTE: this message seen only if the differential element is enabled and represents differential current
RANGE: 0 -2000
NOTE: this message is seen only if there has been a trip
RANGE: 0.00- 200000.00
NOTE: this message not seen if the ground CT is programmed as None
RANGE: 0-50000
NOTE: This message is not seen if VT Connection is programmed as None
RANGE: 0.00 - 90.00
NOTE: This message is not seen if VT Connection is programmed as None
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
$ PreTrip:
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
RANGE: Hour/Min/Sec
NOTE: this message is seen only if there has been a trip
$ PreTrip:
ESCAPE
MESSAGE
RANGE: No Trip To Date, General Input A - G, Sequential Trip, Field-Bkr Discrep., Tachometer, Thermal Model, Offline Overcurrent, Phase Overcurrent, Neg.Seq.
Overcurrent, Ground Overcurrent, Phase Differential, RTDs 1-12, Undervoltage, Overvoltage, Voltz/Hertz, Phase Reversal, Underfrequency, Overfrequency, Neutral
O/V, Neutral U/V (3rd), Reactive Power, Reverse Power, Low Forward Power, Inadvertent Energ., Analog Inputs 1-4
ESCAPE
MESSAGE
0 Vbc: 0
0 V PreTrip
FREQUENCY
MESSAGE
Vab:
$ Vca:
$ Pretrip: 0.00 Hz
MESSAGE
GROUND CURRENT
% PreTrip: 0.00 A
ESCAPE
MESSAGE
MESSAGE
MESSAGE
0 b:
0
0 DA PreTrip
$ PreTrip: 0 % FLA
ESCAPE
MESSAGE
a:
ESCAPE
MESSAGE
0 B:
0
0 A PreTrip
$ c:
ESCAPE
MESSAGE
A:
$ C:
ESCAPE
MESSAGE
TACHOMETER
$ Pretrip: 3600 RPM
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
No Trip To Date
ESCAPE
MESSAGE
ESCAPE
5. ACTUAL VALUES
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
AMBIENT RTD
RTD#12: 0OC PreTrip
ANALOG INPUT 1
Pretrip: 0 Units
ANALOG INPUT 2
0 Units
ANALOG INPUT 3
0 Units
ANALOG INPUT 4
0 Units
Vab/Iab Pretrip
0
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
A1 STATUS
ESCAPE
MESSAGE
$ Pretrip:
$ Pretrip:
% Pretrip:
% 0.0 sec
DESCRIPTION:
Immediately prior to issuing a trip, the 489 takes a snapshot of generator parameters and stores them as pre-trip values which will allow
for troubleshooting after the trip occurs. The cause of last trip message is updated with the current trip and the screen defaults to that
message. All trip features are automatically logged as date and time stamped events as they occur. This information can be cleared using
the setpoint in S1 489 SETUP under CLEAR DATA. If the cause of last trip is No Trip To Date, the subsequent pretrip messages will not
appear. Last Trip Data will not update if a digital input programmed as Test Input is shorted.
ENTER
"
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! NO ALARMS
ESCAPE
ESCAPE
MESSAGE
Input A ALARM
$ STATUS: Active
Input B ALARM
$ STATUS: Active
RANGE: N/A
Note: This message seen when no alarms are active
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
Input C ALARM
$ STATUS: Active
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
Input D ALARM
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
$ STATUS: Active
Input E ALARM
$ STATUS: Active
Input F ALARM
$ STATUS: Active
Input G ALARM
$ STATUS: Active
TACHOMETER
$ ALARM: 3000 RPM
OVERCURRENT
$ ALARM: 10.00 x FLA
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: Active, Latched *The first line of this alarm message will reflect the Input Name as programmed
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: 0-3600
Note: The current measurement of the Tachometer Digital input will be shown here
RANGE: 0-20.00
Note: Overcurrent level will be shown here
RANGE: 0 - 100
Note: reflects the present negative sequence current level
GROUND OVERCURRENT
5.00 A
GROUND DIRECTIONAL
5.00 A
$ ALARM:
$ ALARM:
5-3
A1 STATUS
5. ACTUAL VALUES
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
5-4
OVERFREQUENCY
$ ALARM: 60.6 Hz
$ ALARM:
$ ALARM:
$ ALARM: +20.000
REVERSE POWER
MESSAGE
UNDERFREQUENCY
$ ALARM: 59.4 Hz
$ ALARM: -20.000 MW
MESSAGE
VOLTS/HERTZ ALARM
$ PER UNIT V/Hz: 1.15
ESCAPE
MESSAGE
OVERVOLTAGE ALARM
$ Vab=4992V 120% Rated
MESSAGE
MESSAGE
UNDERVOLTAGE ALARM
$ Vab= 3245V 78% Rated
Stator RTD #1
$ ALARM: 135O C
THERMAL MODEL
$ ALARM: 100% TC USED
TRIP COUNTER
$ ALARM: 25 Trips
BREAKER FAILURE
$ ALARM: Active
VT FUSE FAILURE
$ ALARM: Active
CURRENT DEMAND
$ ALARM: 1053 A
MW DEMAND
$ ALARM: 50.500 MW
Mvar DEMAND
$ ALARM: - 20.000
MVA DEMAND
$ ALARM: 20.000
Analog I/P 1
$ ALARM: 201 Units
Analog I/P 2
$ ALARM: 201 Units
Analog I/P 3
$ ALARM: 201 Units
Note: reflects the number of the RTD that caused the short/low temp. alarm
RANGE: 1 - 100
Note: Value of thermal capacity used is shown here.
RANGE: 1- 10000
Note: The total number of generator trips will be displayed here
RANGE: Active, Latched
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: Active, Latched
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: Active, Latched
Note: Alarm status is Active if the condition that caused the alarm is still present
RANGE: 1 - 999999
Note: The current value of Running Current Demand will be shown here
RANGE: -2000.000 to +2000.000
Note: The current value of Running MW Demand will be shown here
RANGE: -2000.000 to +2000.000
Note: The current value of Running Mvar Demand will be shown here
RANGE: 0 to 2000.000
Note: The current value of Running MVA Demand will be shown here
RANGE: -50000 to +50000 *The alarm message will reflect the Analog Input name and units as programmed,
5. ACTUAL VALUES
#
ESCAPE
MESSAGE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
Analog I/P 4
$ ALARM: 201 Units
MESSAGE
MESSAGE
A1 STATUS
ESCAPE
MESSAGE
RANGE: -50000 to +50000 *The alarm message will reflect the Analog Input name and units as programmed,
% Simulation Mode
IRIG-B FAILURE
% ALARM: Active
Range: Active
Note: this message is only seen if IRIG-B is enabled and the associated signal input is lost
Range: 1-1000000 h
Note: this message is only seen if Running Hour Alarm is enabled
DESCRIPTION:
Any active or latched alarms may be viewed here.
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
Input D
$ PICKUP: Not Enabled
Input E
$ PICKUP: Not Enabled
Input F
$ PICKUP: Not Enabled
Input G
$ PICKUP: Not Enabled
SEQUENTIAL TRIP
MESSAGE
Input C
$ PICKUP: Not Enabled
MESSAGE
Input B
$ PICKUP: Not Enabled
ESCAPE
MESSAGE
MESSAGE
MESSAGE
! Input A
ESCAPE
MESSAGE
FIELD-BKR DISCREP.
$ PICKUP: Not Enabled
TACHOMETER
$ PICKUP: Not Enabled
OFFLINE OVERCURRENT
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if the function is assigned an input
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
INADVERTENT ENERG.
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
PHASE OVERCURRENT
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NEG.SEQ. OVERCURRENT
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
GROUND OVERCURRENT
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
PHASE DIFFERENTIAL
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
GROUND DIRECTIONAL
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
5-5
A1 STATUS
5. ACTUAL VALUES
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
REACTIVE POWER
MESSAGE
ESCAPE
REVERSE POWER
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
5-6
LOSS OF EXCITATION 2
DISTANCE ZONE 2
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
LOSS OF EXCITATION 1
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
MESSAGE
DISTANCE ZONE 1
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
MESSAGE
UNDERFREQUENCY
OVERFREQUENCY
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
VOLTS/HERTZ
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
MESSAGE
OVERVOLTAGE
PHASE REVERSAL
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
UNDERVOLTAGE
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
MESSAGE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #1
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #2
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #3
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #4
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #5
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #6
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #7
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #8
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #9
$ PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
5. ACTUAL VALUES
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RTD #12
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
THERMAL MODEL
MESSAGE
RTD #11
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
ESCAPE
MESSAGE
RTD #10
$ PICKUP: Not Enabled
MESSAGE
MESSAGE
A1 STATUS
Analog I/P 1
$ PICKUP: Not Enabled
Analog I/P 2
$ PICKUP: Not Enabled
Analog I/P 3
$ PICKUP: Not Enabled
Analog I/P 4
% PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Trip, Latched Trip
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
DESCRIPTION:
The trip pickup messages may be very useful during testing. They will indicate if a trip feature has been enabled, if it is inactive (not
picked up), timing out (picked up and timing), active trip (still picked up, timed out, and causing a trip), or latched tip (no longer picked
up, but had timed out and caused a trip that is latched). These values may also be particularly useful as data transmitted to a master
device for monitoring.
5-7
A1 STATUS
5. ACTUAL VALUES
5.2.5 ALARM PICKUPS
! ALARM PICKUPS
! [ENTER] for more
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ESCAPE
Input E
$ PICKUP: Not Enabled
Input F
$ PICKUP: Not Enabled
Input G
$ PICKUP: Not Enabled
TACHOMETER
$ PICKUP: Not Enabled
OVERCURRENT
NEG.SEQ. OVERCURRENT
GROUND OVERCURRENT
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
GROUND DIRECTIONAL
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
UNDERVOLTAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
OVERVOLTAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
VOLTS/HERTZ
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
UNDERFREQUENCY
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
REACTIVE POWER
ESCAPE
REVERSE POWER
MESSAGE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if the function is assigned an input (will reflect name as programmed)
MESSAGE
MESSAGE
5-8
Input D
$ PICKUP: Not Enabled
OVERFREQUENCY
MESSAGE
Input C
$ PICKUP: Not Enabled
MESSAGE
Input B
$ PICKUP: Not Enabled
ESCAPE
MESSAGE
MESSAGE
MESSAGE
! Input A
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RTD #1
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RTD #2
$ PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
5. ACTUAL VALUES
#
ESCAPE
ESCAPE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
TRIP COUNTER
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
BREAKER FAILURE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
VT FUSE FAILURE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
MESSAGE
MESSAGE
OPEN SENSOR
$ PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #12
$ PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
THERMAL MODEL
MESSAGE
RTD #11
$ PICKUP: Not Enabled
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #10
$ PICKUP: Not Enabled
MESSAGE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
MESSAGE
RTD #9
SHORT/LOW TEMP
PICKUP: Not Enabled
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #8
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #7
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #6
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #5
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #4
$ PICKUP: Not Enabled
ESCAPE
MESSAGE
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
ESCAPE
MESSAGE
RTD #3
ESCAPE
MESSAGE
A1 STATUS
CURRENT DEMAND
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
MW DEMAND
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
Mvar DEMAND
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
MVA DEMAND
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
Analog I/P 1
$ PICKUP: Not Enabled
Analog I/P 2
$ PICKUP: Not Enabled
Analog I/P 3
$ PICKUP: Not Enabled
Analog I/P 4
$ PICKUP: Not Enabled
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
RANGE: Not Enabled, Inactive, Timing Out, Active Alarm, Latched Alarm
NOTE: this message is seen only if input is enabled (will reflect input name as programmed)
5-9
A1 STATUS
5. ACTUAL VALUES
DESCRIPTION:
The alarm pickup messages may be very useful during testing. They will indicate if a alarm feature has been enabled, if it is inactive (not
picked up), timing out (picked up and timing), active alarm (still picked up, timed out, and causing an alarm), or latched alarm (no longer
picked up, but had timed out and caused a alarm that is latched). These values may also be particularly useful as data transmitted to a
master device for monitoring.
"
#
ENTER
! ACCESS SWITCH
ESCAPE
STATE: Open
ESCAPE
BREAKER STATUS
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
ASSIGNABLE DIGITAL
TRIP COIL
% SUPERVISION: No Coil
DESCRIPTION:
The messages shown here may be used to monitor digital input status. This may be useful during relay testing or during installation.
5
5.2.7 REAL TIME CLOCK
! REAL TIME CLOCK
! [ENTER] for more
ENTER
"
ESCAPE
! DATE: 01/01/1994
TIME: 12:00:00
RANGE: 01-12/10-31/1995-2094
RANGE: 00-23:00-59:00 -59
DESCRIPTION:
The time and date from the 489 real time clock may be viewed here.
5-10
5. ACTUAL VALUES
A2 METERING DATA
ENTER
"
#
RANGE: 0 -2000
PHASE C CURRENT:
0A
0 O Lag
DIFF. A CURRENT:
0A
0 O Lag
DIFF. B CURRENT:
0A
0 O Lag
DIFF. C CURRENT:
0A
0 O Lag
GROUND CURRENT:
0.0 A
0 O Lag
GROUND CURRENT:
0.00 A
0 O Lag
ESCAPE
MESSAGE
NEGATIVE SEQUENCE
ESCAPE
MESSAGE
RANGE: 0 - 2000
ESCAPE
MESSAGE
GENERATOR LOAD:
0% FLA
ESCAPE
MESSAGE
RANGE: 0 - 999999
PHASE B CURRENT:
0A
0 O Lag
ESCAPE
MESSAGE
AVERAGE PHASE
0 Amps
ESCAPE
MESSAGE
RANGE: 0 - 999999
ESCAPE
MESSAGE
0 b:
0
0 Diff. Amps
ESCAPE
MESSAGE
RANGE: 0 - 999999
PHASE A CURRENT:
0A
0 O Lag
ESCAPE
MESSAGE
0 b:
0
0 Neut. Amps
ESCAPE
MESSAGE
RANGE: 0 - 999999
$ CURRENT: 0 % FLA
ESCAPE
MESSAGE
ESCAPE
MESSAGE
0 B:
0
0 Amps
$ CURRENT:
ESCAPE
MESSAGE
a:
$ c:
ESCAPE
MESSAGE
a:
$ c:
ESCAPE
MESSAGE
C:
ESCAPE
MESSAGE
! A:
ESCAPE
DESCRIPTION:
All measured current values are displayed here. A,B,C Line Amps represent the output side CT measurements. a,b,c Neut. Amps
represent the neutral end CT measurements. a,b,c Diff. Amps represent the differential operating current that is calculated as the
vectorial difference between the output side CT measurements and the neutral end CT measurements on a per phase basis. 489
negative sequence current is defined as the ratio of negative sequence current to generator rated full load amps, I2/ FLA x 100%. The
generator full load amps is calculated as: generator rated MVA / (3 x generator phase-phase voltage). Polar coordinates for measured
currents are also shown using Va (wye connection) or Vab (open delta connection) as a zero angle reference vector. In the absence of a
voltage signal (Va or Vab), IA output current is used as the zero angle reference vector.
5-11
A2 METERING DATA
5. ACTUAL VALUES
5.3.2 VOLTAGE METERING
! VOLTAGE METERING
! [ENTER] for more
ENTER
"
#
AVERAGE LINE
$ VOLTAGE: 0 Volts
ESCAPE
ESCAPE
ESCAPE
MESSAGE
$ OF V/Hz: 0.00
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
RANGE: 0 - 50000
NOTE: This message seen only if VT Connection is programmed as Wye
RANGE: 0 - 50000 A, 0 - 359
NOTE: This message is not seen if VT Connection is programmed as None
ESCAPE
MESSAGE
RANGE: 0 - 50000
NOTE: This message seen only if VT Connection is programmed as Wye
ESCAPE
MESSAGE
RANGE: 0 - 50000
NOTE: This message is not seen if VT Connection is programmed as None
ESCAPE
MESSAGE
AVERAGE PHASE
ESCAPE
MESSAGE
0 Vbn:
0 Volts
$ VOLTAGE: 0 Volts
ESCAPE
MESSAGE
$ Vcn:
ESCAPE
MESSAGE
Van:
ESCAPE
MESSAGE
RANGE: 0 - 50000
NOTE: This message is not seen if VT Connection is programmed as None
0 Vbc: 0
0 Volts
ESCAPE
MESSAGE
Vca:
MESSAGE
MESSAGE
! Vab:
ESCAPE
FREQUENCY:
0.00 Hz
NEUTRAL VOLTAGE
$ FUND: 0.0 V
NEUTRAL VOLTAGE
$ 3rd HARM: 0.0 V
TERMINAL VOLTAGE
% 0.0 sec
DESCRIPTION:
Measured voltage parameters will be displayed here. The V/Hz measurement is a per unit value based on Vab voltage/measured
frequency divided by VT nominal/nominal system frequency. Polar coordinates for measured phase and/or line voltages are also shown
using Va (wye connection) or Vab (open delta connection) as a zero angle reference vector. In the absence of a voltage signal (Va or
Vab), IA output current is used as the zero angle reference vector.
If VT Connection Type is programmed as None and Neutral Voltage Transformer is No in S2 SYSTEM, the following flash message
will appear when an attempt is made to enter this group of messages.
THIS FEATURE NOT
PROGRAMMED
5-12
5. ACTUAL VALUES
A2 METERING DATA
5.3.3 POWER METERING
! POWER METERING
! [ENTER] for more
ENTER
"
#
POSITIVE WATTHOURS:
0.000 MWh
POSITIVE VARHOURS:
0.000 Mvarh
NEGATIVE VARHOURS:
0.000 Mvarh
ESCAPE
MESSAGE
APPARENT POWER:
0.000 MVA
RANGE: 0 to 2000.000
ESCAPE
MESSAGE
REACTIVE POWER:
0.000 Mvar
RANGE: 0 to 2000.000
ESCAPE
MESSAGE
REAL POWER:
0.000 MW
RANGE: 0 to 2000.000
ESCAPE
MESSAGE
ESCAPE
MESSAGE
0.00
ESCAPE
MESSAGE
! POWER FACTOR:
ESCAPE
DESCRIPTION:
The values for power metering appear here. 3 phase total power quantities are displayed here. Watthours and varhours are also shown
here. Watthours and varhours will not update if a digital input programmed as Test Input is shorted.
NOTE: An induction generator, by convention generates Watts and consumes vars (+Watts and -vars). A synchronous
generator can also generate vars (+vars).
If .VT Connection Type is programmed as None in S2 SYSTEM SETUP, the following flash message will appear when an attempt is
made to enter this group of messages.
THIS FEATURE NOT
PROGRAMMED
5-13
A2 METERING DATA
5. ACTUAL VALUES
5.3.4 TEMPERATURE
! TEMPERATURE
! [ENTER] for more
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
RTD#1: 40 o C
RTD #1
$ TEMPERATURE: 40O C
RTD #2
$ TEMPERATURE: 40O C
RTD #3
$ TEMPERATURE: 40O C
RTD #4
$ TEMPERATURE: 40O C
RTD #5
$ TEMPERATURE: 40O C
RTD #6
$ TEMPERATURE: 40O C
RTD #7
$ TEMPERATURE: 40O C
RTD #8
$ TEMPERATURE: 40O C
RTD #9
$ TEMPERATURE: 40O C
RTD #10
$ TEMPERATURE: 40O C
RTD #11
$ TEMPERATURE: 40O C
RTD #12
% TEMPERATURE: 40O C
DESCRIPTION:
The current level of the 12 RTDs will be displayed here. If the RTD is not connected, the value will be No RTD. If no RTDs are
programmed in S7 RTD TEMPERATURE, the following flash message will appear when an attempt is made to enter this group of
messages.
THIS FEATURE NOT
PROGRAMMED
5-14
5. ACTUAL VALUES
A2 METERING DATA
5.3.5 DEMAND METERING
! DEMAND METERING
! [ENTER] for more
ENTER
"
#
Mvar DEMAND:
0.000 Mvar
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
MVA DEMAND:
0.000 MVA
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
PEAK CURRENT
0 Amps
RANGE: 0 - 999999
PEAK MW DEMAND:
0.000 MW
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
$ DEMAND:
ESCAPE
MESSAGE
ESCAPE
MESSAGE
RANGE: 0 - 2000.000
NOTE: This message is not seen if VT Connection Type is programmed as 'None'.
ESCAPE
MESSAGE
MW DEMAND:
0.000 MW
ESCAPE
MESSAGE
ESCAPE
MESSAGE
RANGE: 0 - 999999
0 Amps
ESCAPE
MESSAGE
DEMAND:
ESCAPE
MESSAGE
! CURRENT
ESCAPE
DESCRIPTION:
The values for current and power demand are shown here. Peak demand information can be cleared using the setpoint in S1 489 SETUP
under CLEAR DATA. Demand is shown only for positive real and positive reactive power (+Watts, +vars). Peak demand will not update if a
digital input programmed as Test Input is shorted.
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! Analog I/P 1
0 Units
Analog I/P 2
$ 0 Units
Analog I/P 3
$ 0 Units
Analog I/P 4
% 0 Units
DESCRIPTION:
The values for analog inputs are shown here. The name of the input and the units will reflect those programmed for each input.
If no Analog Inputs are programmed in S11 ANALOG I/O, the following flash message will appear when an attempt is made to enter this
group of messages.
THIS FEATURE NOT
PROGRAMMED
5-15
A2 METERING DATA
5. ACTUAL VALUES
5.3.7 SPEED
! SPEED
! [ENTER] for more
ENTER
"
! TACHOMETER: 0 RPM
ESCAPE
RANGE: 0-7200
NOTE: This message seen only if a Digital Input is configured as Tachometer
DESCRIPTION:
If the Tachometer function is assigned to one of the digital inputs, the tachometer readout may be viewed here. A bargraph on the
second line of this message represents speed from 0 RPM to rated speed.
If no digital input is configured as tachometer in S3 DIGITAL INPUTS, the following flash message will appear when an attempt is made
to enter this group of messages.
THIS FEATURE NOT
PROGRAMMED
5-16
5. ACTUAL VALUES
A3 LEARNED DATA
!"PARAMETER AVERAGES
! [ENTER] for more
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! AVERAGE GENERATOR
RANGE: 0 - 2000
RANGE: 0 - 2000
$ CURRENT: 0% FLA
AVERAGE PHASE-PHASE
0V
% VOLTAGE:
RANGE: 0 - 50000
NOTE: this message is not seen if the VT connection is programmed as None
DESCRIPTION:
The 489 calculates the average magnitude of several parameters over a period of time. This time is specified by the setpoint in the
preferences section of S1 489 SETUP (default 15 minutes). The calculation is a sliding window and is ignored when the generator is
offline. (ie. the value that was calculated just prior to going offline will be held until the generator is brought back online and a new
calculation is made. Parameter averages will not update if a digital input programmed as Test Input is shorted.
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! RTD #1
RTD #3
$ MAX. TEMP.: 40O C
RTD #4
$ MAX. TEMP.: 40O C
RTD #5
$ MAX. TEMP.: 40O C
RTD #6
$ MAX. TEMP.: 40O C
RTD #7
$ MAX. TEMP.: 40O C
RTD #8
$ MAX. TEMP.: 40O C
RTD #9
$ MAX. TEMP.: 40O C
RTD #10
$ MAX. TEMP.: 40O C
RTD #11
$ MAX. TEMP.: 40O C
RTD#12
% MAX. TEMP.: 40O C
DESCRIPTION:
The 489 will learn the maximum temperature for each RTD. This information can be cleared using the setpoint in S1 489 SETUP under
CLEAR DATA. RTD maximums will not update if a digital input programmed as Test Input is shorted.
If no RTDs are programmed in S7 RTD TEMPERATURE, the following flash message will appear when an attempt is made to enter this
group of messages.
THIS FEATURE NOT
PROGRAMMED
5-17
A3 LEARNED DATA
5. ACTUAL VALUES
5.4.3 ANALOG IN MIN/MAX
! ANALOG IN MIN/MAX
! [ENTER] for more
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! Analog I/P 1
MIN:0 Units
Analog I/P 1
$ MAX:0 Units
Analog I/P 2
$ MIN:0 Units
Analog I/P 2
$ MAX:0 Units
Analog I/P 3
$ MIN:0 Units
Analog I/P 3
$ MAX:0 Units
Analog I/P 4
$ MIN:0 Units
Analog I/P 4
% MAX:0 Units
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
RANGE: -50000 to +50000 * Message not seen if analog input programmed as None
*The message will reflect the Analog Input name and units as programmed,
DESCRIPTION:
The 489 will learn the Minimum and Maximum values of the analog inputs since they were last cleared. This information can be cleared
using the setpoint in S1 489 SETUP under CLEAR DATA. When the data is cleared, the present value of each analog input will be loaded as
a starting point for both minimum and maximum. The name of the input and the units will reflect those programmed for each input. Analog
Input minimums and maximums will not update if a digital input programmed as Test Input is shorted.
If no Analog Inputs are programmed in S11 ANALOG I/O, the following flash message will appear when an attempt is made to enter this
group of messages.
THIS FEATURE NOT
PROGRAMMED
5-18
5. ACTUAL VALUES
A4 MAINTENANCE
5.5 A4 MAINTENANCE
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! TOTAL NUMBER OF
RANGE: 0 - 50000
TRIPS: 0
DIGITAL INPUT
$ TRIPS: 0
SEQUENTIAL
RANGE: 0 -50000
*Caused by General Input Trip Features
RANGE: 0 -50000
$ TRIPS: 0
FIELD-BKR DISCREP.
RANGE: 0 -50000
$ TRIPS: 0
TACHOMETER
$ TRIPS: 0
OFFLINE OVERCURRENT
RANGE: 0 -50000
*Caused by Assignable Digital Input Programmed as Tachometer
RANGE: 0 -50000
$ TRIPS: 0
PHASE OVERCURRENT
RANGE: 0 -50000
$ TRIPS: 0
NEG.SEQ. OVERCURRENT
RANGE: 0 -50000
$ TRIPS: 0
GROUND OVERCURRENT
RANGE: 0 -50000
$ TRIPS: 0
PHASE DIFFERENTIAL
RANGE: 0 -50000
$ TRIPS: 0
GROUND DIRECTIONAL
RANGE: 0 -50000
$ TRIPS: 0
RANGE: 0 -50000
$ TRIPS: 0
UNDERVOLTAGE
RANGE: 0 -50000
$ TRIPS: 0
OVERVOLTAGE
RANGE: 0 -50000
$ TRIPS: 0
VOLTS/HERTZ
RANGE: 0 -50000
$ TRIPS: 0
PHASE REVERSAL
RANGE: 0 -50000
$ TRIPS: 0
UNDERFREQUENCY
RANGE: 0 -50000
$ TRIPS: 0
OVERFREQUENCY
RANGE: 0 -50000
$ TRIPS: 0
RANGE: 0 -50000
$ TRIPS: 0
RANGE: 0 -50000
$ TRIPS: 0
LOSS OF EXCITATION 1
RANGE: 0 -50000
$ TRIPS: 0
LOSS OF EXCITATION 2
RANGE: 0 -50000
$ TRIPS: 0
DISTANCE ZONE 1
RANGE: 0 -50000
$ TRIPS: 0
DISTANCE ZONE 2
RANGE: 0 -50000
$ TRIPS: 0
5-19
A4 MAINTENANCE
#
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
5. ACTUAL VALUES
REACTIVE POWER
RANGE: 0 -50000
$ TRIPS: 0
REVERSE POWER
RANGE: 0 -50000
$ TRIPS: 0
RANGE: 0 -50000
$ TRIPS: 0
STATOR RTD
RANGE: 0 -50000
$ TRIPS: 0
BEARING RTD
RANGE: 0 -50000
$ TRIPS: 0
OTHER RTD
RANGE: 0 -50000
$ TRIPS: 0
AMBIENT RTD
RANGE: 0 -50000
$ TRIPS: 0
THERMAL MODEL
RANGE: 0 -50000
$ TRIPS: 0
INADVERTENT ENERG.
RANGE: 0 -50000
$ TRIPS: 0
Analog I/P 1
$ TRIPS: 0
Analog I/P 2
$ TRIPS: 0
Analog I/P 3
$ TRIPS: 0
Analog I/P 4
$ TRIPS: 0
RANGE: 0 -50000
*The message will reflect the Analog Input name and units as programmed,
RANGE: 0 -50000
*The message will reflect the Analog Input name and units as programmed,
RANGE: 0 -50000
*The message will reflect the Analog Input name and units as programmed,
RANGE: 0 - 100
*The message will reflect the Analog Input name and units as programmed,
COUNTERS CLEARED:
% Jan 1, 1995
DESCRIPTION: A breakdown of number of trips by type is displayed here. When the Total reaches 50000, all counters reset. This
information can be cleared using the setpoint in S1 489 SETUP under CLEAR DATA. Trip counters will not update if a digital input
programmed as Test Input is shorted. In the event of multiple trips, the only the first trip will increment the trip counters.
5-20
5. ACTUAL VALUES
A4 MAINTENANCE
! GENERAL COUNTERS
! [ENTER] for more
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
! NUMBER OF BREAKER
RANGE: 0 -50000
OPERATIONS: 0
NUMBER OF THERMAL
% RESETS: 0
RANGE: 0 -50000
NOTE: this message is seen only one of the assignable digital inputs is assigned to thermal reset
DESCRIPTION:
One of the 489 general counters will count the number of breaker operations over time. This may be useful information for breaker
maintenance. The number of breaker operations is incremented whenever the breaker status changes from closed to open and all phase
currents are zero. Another counter counts the number of thermal resets if one of the assignable digital inputs is assigned to thermal
reset. This may be useful information when troubleshooting. When either of these counters reaches 50000, that counter will reset to 0.
Each counter can also be cleared using the setpoint in S1 489 SETUP under CLEAR DATA. Number of breaker operations will not update if
a digital input programmed as Test Input is shorted.
5.5.3 TIMERS
! TIMERS
! [ENTER] for more
ENTER
"
ESCAPE
! GENERATOR HOURS
ONLINE:
RANGE: 0 - 1000000
0h
DESCRIPTION:
The 489 accumulates the total online time for the generator. This may be useful for scheduling routine maintenance. When this timer
reaches 1 000 000, it will reset to 0. This timer can be cleared using the setpoints in S1 489 SETUP under CLEAR DATA. Generator hours
online will not update if a digital input programmed as Test Input is shorted.
5-21
A5 EVENT RECORDER
5. ACTUAL VALUES
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
..
ESCAPE
MESSAGE
GROUND CURRENT
0.00 A
Vab:
RANGE: 0-50000
NOTE: This message is not seen if VT Connection is programmed as None
% E65535:
$ Vca:
0 Vbc: 0
0 V E65535
FREQUENCY
$ E65535: 0.00 Hz
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
ESCAPE
HOTTEST STATOR
MESSAGE
$ E65535:
$ E65535:
$ 0.0 sec
$ E65535:
$ E65535:
$ E65535:
ESCAPE
HOTTEST BEARING
MESSAGE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
ESCAPE
MESSAGE
5-22
RANGE: 0 -2000
NOTE: this message is seen only if there has been a event
ESCAPE
MESSAGE
RANGE: 0 - 999999
NOTE: this message seen only if the differential element is enabled and represents differential current
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
MESSAGE
0 b:
0
0 DA E65535
ESCAPE
MESSAGE
a:
$ c:
RANGE: 0-999999
NOTE: this message represents current measured from the output CTs, seen only if there has been a event
RANGE: 0 to 2000.000
NOTE: This message is not seen if VT Connection is None
MESSAGE
0 B:
0
0 A E65535
ESCAPE
MESSAGE
A:
$ C:
RANGE: 0-3600
NOTE: this message is seen only if the function is assigned an input
MESSAGE
TACHOMETER
$ E65535: 3600 RPM
Vab/Iab E65535:
0
ESCAPE
MESSAGE
RANGE: 1-2
$ GROUP E65535: 1
RANGE: 0 - 25000.0
NOTE: This message seen only if there is a neutral voltage transformer
MESSAGE
ACTIVE SETPOINT
RANGE: Mon/Day/Year
NOTE: this message is seen only if there has been a event
ESCAPE
MESSAGE
DATE OF E65535:
$ Jan. 01, 1992
RANGE: Hour/Min/Sec
NOTE: this message is seen only if there has been a event
RANGE: 0 - 25000.0
NOTE: This message seen only if there is a neutral voltage transformer
MESSAGE
00:00:00.0
ESCAPE
MESSAGE
! TIME OF E65535:
HOTTEST OTHER
$ RTD#11: 0OC E65535
AMBIENT
$ RTD#12: 0OC E65535
ANALOG INPUT 1
0 Units
ANALOG INPUT 2
0 Units
ANALOG INPUT 3
0 Units
ANALOG INPUT 4
0 Units
$ E65535:
$ E65535:
$ E65535:
% E65535:
5. ACTUAL VALUES
A5 EVENT RECORDER
DESCRIPTION:
The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event is stored and
a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for troubleshooting. Events
include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which always records as events), loss of
control power, application of control power, thermal resets, simulation, serial communication starts/stops and general input control
functions optionally.
5-23
A5 EVENT RECORDER
5. ACTUAL VALUES
The highest event number is the most recent event, and lowest event number is the oldest event. Each new event bumps the other
event records down until the 40th event is reached. The 40th event record is lost when the next event occurs. This information can be
cleared using the setpoint in S1 489 SETUP under CLEAR DATA. An event number of 65535 signifies that no event has occurred since
the last clearing of the event record. The event record will not update if a digital input programmed as Test Input is shorted.
Table 5-2 CAUSE OF EVENT TABLE
TRIPS
*Input A Trip
*Input B Trip
*Input C Trip
*Input D Trip
*Input E Trip
*Input F Trip
*Input G Trip
Sequential Trip
Fld-Bkr Discr. Trip
Tachometer Trip
Offline O/C Trip
Phase O/C Trip
Neg. Seq. O/C Trip
Ground O/C Trip
Differential Trip
Undervoltage Trip
Overvoltage Trip
Phase Reversal Trip
Volts/Hertz Trip
Underfrequency Trip
Overfrequency Trip
Neutral O/V Trip
Neut. U/V (3rd)Trip
Reactive Factor Trip
Reverse Power Trip
Low Fwd Power Trip
*Stator RTD 1 Trip
*Stator RTD 2 Trip
*Stator RTD 3 Trip
*Stator RTD 4 Trip
*Stator RTD 5 Trip
*Stator RTD 6 Trip
*Bearing RTD 7 Trip
*Bearing RTD 8 Trip
*Bearing RTD 9 Trip
*Bearing RTD10 Trip
*RTD11 Trip
*Ambient RTD12 Trip
Thermal Model Trip
*Analog I/P 1 Trip
*Analog I/P 2 Trip
*Analog I/P 3 Trip
*Analog I/P 4 Trip
Loss of Excitation 1
Loss of Excitation 2
Gnd. Directional Trip
Hiset Phase O/C Trip
Distance Zone 1 Trip
Distance Zone 2 Trip
5-24
OTHER
*Input A Alarm
*Input B Alarm
*Input C Alarm
*Input D Alarm
*Input E Alarm
*Input F Alarm
*Input G Alarm
Tachometer Alarm
Overcurrent Alarm
NegSeq Current Alarm
Ground O/C Alarm
Undervoltage Alarm
Overvoltage Alarm
Volts/Hertz Alarm
Underfrequency Alarm
Overfrequency Alarm
Neutral O/V Alarm
Neut. U/V 3rd Alarm
Reactive Power Alarm
Reverse Power Alarm
Low Fwd Power Alarm
*Stator RTD 1 Alarm
*Stator RTD 2 Alarm
*Stator RTD 3 Alarm
*Stator RTD 4 Alarm
*Stator RTD 5 Alarm
*Stator RTD 6 Alarm
*Bearing RTD 7 Alarm
*Bearing RTD 8 Alarm
*Bearing RTD 9 Alarm
*Bearing RTD10 Alarm
*RTD11 Alarm
*Ambient RTD12 Alarm
Open RTD Alarm
Short/Low RTD Alarm
Trip Counter Alarm
Breaker Failure
Trip Coil Monitor
VT Fuse Fail Alarm
Current Demand Alarm
MW Demand Alarm
Mvar Demand Alarm
MVA Demand Alarm
Thermal Model Alarm
*Analog I/P 1 Alarm
*Analog I/P 2 Alarm
*Analog I/P 3 Alarm
*Analog I/P 4 Alarm
Gnd. Directional Alarm
Service Alarm
Control Power Lost
Control Power Applied
Thermal Reset Close
Thermal Reset Open
Serial Comm. Start
Serial Comm. Stop
489 Not Inserted
Simulation Started
Simulation Stopped
*Input A Control
*Input B Control
*Input C Control
*Input D Control
*Input E Control
*Input F Control
*Input G Control
Setpoint 1 Active
Setpoint 2 Active
Dig I/P Waveform Trig
Serial Waveform Trig
IRIG-B Failure
5. ACTUAL VALUES
A6 PRODUCT INFO
ENTER
"
#
ESCAPE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
! ORDER CODE:
RANGE: N/A
489-P5-HI-A20
489 SERIAL NO:
RANGE: N/A
$ A3260001
489 REVISION:
RANGE: N/A
$ 32E100A4.000
RANGE: N/A
% 32E100A0.000
DESCRIPTION:
All of the 489 Model information may be viewed here when the unit is powered up. In the event of a product software upgrade or service
question, the information shown here should be jotted down prior to any inquiry.
"
#
ENTER
! ORIGINAL CALIBRATION
ESCAPE
ESCAPE
MESSAGE
LAST CALIBRATION
RANGE: Mon/Day/Year
RANGE: Mon/Day/Year
DESCRIPTION:
The date of the original calibration and last calibration may be viewed here.
5-25
DIAGNOSTICS
5. ACTUAL VALUES
5.8 DIAGNOSTICS
|
|
|
ANALOG INPUT 4
Pretrip: 0 Units
ACTIVE ALARMS
Stator RTD #1
ALARM: 135O C
5-26
NEXT
5. ACTUAL VALUES
DIAGNOSTICS
5.8.2 FLASH MESSAGES
Flash messages are warning, error, or general information messages that are temporarily displayed in response to certain key presses.
These messages are intended to assist with navigation of the 489 messages by explaining what has happened or by prompting the user
to perform certain actions.
Table 5-3 FLASH MESSAGES
NEW SETPOINT HAS
BEEN STORED
ROUNDED SETPOINT
HAS BEEN STORED
ACCESS DENIED,
SHORT ACCESS SWITCH
ACCESS DENIED,
ENTER PASSCODE
INVALID PASSCODE
ENTERED !
NEW PASSCODE
HAS BEEN ACCEPTED
PASSCODE SECURITY
NOT ENABLED, ENTER 0
PLEASE ENTER A
NON-ZERO PASSCODE
SETPOINT ACCESS IS
NOW PERMITTED
SETPOINT ACCESS IS
NOW RESTRICTED
DATE ENTRY
OUT OF RANGE
TIME ENTRY
OUT OF RANGE
NO TRIPS OR ALARMS
TO RESET
RESET PERFORMED
SUCCESSFULLY
CONDITION IS PRESENT
RESET NOT POSSIBLE
DEFAULT MESSAGE
HAS BEEN ADDED
DEFAULT MESSAGE
LIST IS FULL
PRESS [ENTER] TO
REMOVE MESSAGE
DEFAULT MESSAGE
HAS BEEN REMOVED
DEFAULT MESSAGES
6 of 20 ARE ASSIGNED
INVALID SERVICE
CODE ENTERED
KEY PRESSED IS
INVALID HERE
DATA CLEARED
SUCCESSFULLY
TOP OF PAGE
THIS FEATURE NOT
PROGRAMMED
END OF PAGE
THIS PARAMETER IS
ALREADY ASSIGNED
TOP OF LIST
END OF LIST
NO ALARMS ACTIVE
NEW SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored as shown on the
display.
ROUNDED SETPOINT HAS BEEN STORED: Since the 489 has a numeric keypad, a setpoint value may entered that is in between
valid setpoint values. The 489 will detect this condition and store a value that has been rounded to the nearest valid setpoint value. To
find the valid range and step for a given setpoint, simply press the [HELP] key while the setpoint is being displayed.
OUT OF RANGE! ENTER: #### - ##### by #: If a setpoint value that is outside of the acceptable range of values is entered, the 489
will display this message, substituting the proper values for that setpoint. An appropriate value may then be entered.
ACCESS DENIED, SHORT ACCESS SWITCH: In order to store any setpoint values, the Access Switch must be shorted. If this
message appears and it is necessary to change a setpoint, short the Access terminals C1 & C2.
ACCESS DENIED, ENTER PASSCODE: The 489 has a PASSCODE SECURITY feature. If that feature has been enabled, not only do
the Access Switch terminals have to be shorted, but the Passcode must also be entered. If the correct passcode has been lost or
forgotten, contact the factory with the Encrypted access code. All passcode features may be found in S1 489 SETUP under
PASSCODE.
INVALID PASSCODE ENTERED: If an invalid passcode is entered for passcode security feature, this message will flash on the display.
NEW PASSCODE HAS BEEN ACCEPTED: When changing the Passcode for the Passcode Security feature, this message will appear
as an acknowledge that the new passcode has been accepted.
PASSCODE SECURITY NOT ENABLED, ENTER 0: The Passcode Security feature is disabled whenever the passcode is zero (factory
default). Any attempts to enter a passcode when the feature is disabled will result in this flash message. It is meant to prompt the user to
enter 0 as the passcode. When this has been done, the feature may be enabled by entering a non-zero passcode.
PLEASE ENTER A NON-ZERO PASSCODE: If the passcode is zero, the passcode security feature is disabled. If the Change
Passcode Setpoint is entered as yes, this flash message will appear prompting the user to enter a non-zero passcode which in turn will
enable the feature.
SETPOINT ACCESS IS NOW PERMITTED: Any time that the Passcode Security feature is enabled and a valid passcode is entered,
this flash message will appear to notify that the Setpoint s may now be altered and stored.
5-27
DIAGNOSTICS
5. ACTUAL VALUES
SETPOINT ACCESS IS NOW RESTRICTED: IF the passcode security feature is enabled and a valid passcode has been entered,
when the setpoint under S1 489 SETUP, PASSCODE, SETPOINT ACCESS: is altered to Restricted, this message will appear. Also,
any time that Setpoint access is permitted and the access jumper is removed, this message will also appear.
DATE ENTRY WAS NOT COMPLETE: Since the Date setpoint is special, consisting of MM/DD/YYYY, if the enter key is pressed
before all of the information has been entered, this message will appear and the new value will not be store. Another attempt will have to
be made with the complete information.
DATE ENTRY WAS OUT OF RANGE: If and invalid entry is made for the date (eg. 15 entered for month), this message will appear.
TIME ENTRY WAS NOT COMPLETE: Since the Time setpoint is special, consisting of HH/MM/SS.S, if the enter key is pressed before
all of the information has been entered, this message will appear and the new value will not be store. Another attempt will have to be
made with the complete information.
TIME ENTRY WAS OUT OF RANGE: If and invalid entry is made for the time (eg. 35 entered for hour), this message will appear.
NO TRIPS OR ALARMS TO RESET: If the [RESET] key is pressed when there are no trips or alarms present, this message will
appear.
RESET PERFORMED SUCCESSFULLY: If all trip and alarm features that are active can be cleared (i.e. the conditions that caused
these trips and/or alarms are no longer present), then this message will appear when a RESET is performed, indicating that all trips and
alarms have been cleared.
ALL POSSIBLE RESETS HAVE BEEN PERFORMED: If only some of the trip and alarm features that are active can be cleared (ie. the
conditions that caused some of these trips and/or alarms are still present), then this message will appear when a RESET is performed,
indicating that only trips and alarms that could be reset have been reset.
CONDITION IS PRESENT RESET NOT POSSIBLE: If no trip and alarm features that are active can be cleared (ie. the condition that
caused these trips and/or alarms is still present), then this message will appear when the [RESET] key is pressed.
ARE YOU SURE? PRESS [ENTER] TO VERIFY: If the [RESET] key is pressed and resetting of any trip or alarm feature is possible,
this message will appear to ask for verification of the operation. If [RESET] is pressed again while the message is still on the display, the
reset will be performed.
PRESS [ENTER] TO ADD DEFAULT MESSAGE: Any where in the 489 Actual Value Message Structure, if the[.] key is pressed,
immediately followed by the [ENTER] key. This message will appear to prompt the user to press [ENTER] to add a new default
message. To add a new default message, [ENTER] must be pressed while this message is being displayed.
DEFAULT MESSAGE HAS BEEN ADDED: Any time a new default message is added to the Default message list, this message will
appear as verification.
DEFAULT MESSAGE LIST IS FULL: If an attempt is made to add a new default message to the default message list when 20
messages are already assigned, this message will appear. In order to add a message, one of the existing messages must be removed.
PRESS [ENTER] TO REMOVE MESSAGE: Under S1 489 SETUP, DEFAULT MESSAGES, if the[.] key is pressed, immediately
followed by the [ENTER] key, this message will appear to prompt the user to press [ENTER] to remove a default message. To remove
the default message, [ENTER] must be pressed while this message is being displayed.
DEFAULT MESSAGE HAS BEEN REMOVED: Any time a default message is removed from the Default message list, this message will
appear as verification.
DEFAULT MESSAGES 6 of 20 ARE ASSIGNED: This message will appear each time the DEFAULT MESSAGES subgroup of S1 489
SETUP is entered. It is intended to notify the user of the number of default messages that are assigned.
INVALID SERVICE CODE ENTERED: Under S12 489 TESTING, FACTORY SERVICE, if an invalid code is entered, this message will
appear.
KEY PRESSED HERE IS INVALID: Under certain situations, certain keys have no function (eg. any number key while viewing Actual
Values). If a key is pressed where it should have no function, this message will appear.
DATA CLEARED SUCCESSFULLY: Under S1 489 SETUP, CLEAR DATA, if data is cleared or reset, this message will appear to
confirm that action.
5-28
5. ACTUAL VALUES
DIAGNOSTICS
[.] KEY IS USED TO ADVANCE THE CURSOR: Any time a setpoint that requires text editing is viewed, this message will appear
immediately to prompt the user to use the [.] key for cursor control. If the setpoint is not altered for 1 minute, the message will flash
again.
TOP OF PAGE: This message will indicate when the top of a page has been reached.
BOTTOM OF PAGE: This message will indicate when the bottom of a page has been reached.
TOP OF LIST: This message will indicate when the top of subgroup has been reached.
BOTTOM OF LIST: This message will indicate when the bottom of a subgroup has been reached.
NO ALARMS ACTIVE: If an attempt is made to enter the Alarm Status message subgroup, but there are no active alarms, this message
will appear.
THIS FEATURE NOT PROGRAMMED: If an attempt is made to enter an actual value message subgroup, when the setpoints are not
configured for that feature, this message will appear.
THIS PARAMETER IS ALREADY ASSIGNED: A given analog output parameters can only be assigned to one output. If an attempt is
made to assign a parameter to a second output, this message will appear.
THAT INPUT ALREADY USED FOR TACHOMETER: If a digital input is assigned to the tachometer function, it cannot be used for any
other digital input function. If an attempt is made to assign a digital input to a function when it is already assigned to tachometer, this
message will appear.
TACHOMETER MUST USE INPUT 4, 5, 6, or 7: Only digital inputs 4,5,6,or 7 may be used for the tachometer function. If an attempt is
made to assign inputs 1,2,3, or 4 to the tachometer function, this message will appear.
THAT DIGITAL INPUT IS ALREADY IN USE: If an attempt is made to assign a digital input to tachometer when it is already assigned
to another function, this message will appear.
To edit use VALUE UP or VALUE DOWN key: If a numeric key is pressed on a setpoint parameter that is not numeric, this message
will prompt the user to use the value keys.
GROUP 1 SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored to setpoint Group
1 as shown on the display.
GROUP 2 SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored to setpoint Group
2 as shown on the display.
5-29