OFFICE INTERIOR FOR CUMI

ELECTRICAL INSTALLATION
SI. No. Item Description Unit Rate Amount
Qty

4(b) Supply & Fixing of TPN MCB DB of IP 42/43 protection with Set 17000 17000
suitable double door enclosure following with necessary dummys including 1
all terminations and earthing.
63A TPN MCB - 1No 0
32A DP MCB - 3 Nos 0
Lighting- 12 Nos, AC Power - 8 Nos, 0
0
5.0 Supplying and fixing of single phase double door DB of IP 42 Set 15000 30000
protection with double door with the following including all 2
terminations and earthing.
63 A DP MCB — 1 No. 0
16/10A SP MCB — 20 Nos 0
Lighting - 12 Nos, UPS -8 Nos, 0
0
0
8.00 Supply and fixing of 100 A 36 KA FP MCCB with water proof set 4000 4000
enclosure as per IS suitable for Outdoor applications for 3 phase AC in
1
concealed / surface manner as directed at site. For VRF Outdoor AC
unit.
0
9.00 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket Set 1200 2400
outlet, with 2pole and earth, metal enclosed plug top alongwith 20 amps
“C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with 2
chained metal cover for the socket out let and complete with connections,
testing and commissioning etc. as required for UPS.
0
0
10(f} Supply & laying 4C x 25 Sq mm XLPE insulated 1100V graded armoured RM 600 12000
Aluminium conductor cable ISI Marked with 2 runs of No.8 SWG bare
copper earth on surface of wall using clamps , spacers etc from Electrical
20
Panel room to Gen set room & LT-CT Panel room Coomon lighting/Sump
pump. Rate should include for suitable size cable glands, earth clamp etc
and end termination with cable lugs.
0
10(g) Supply & laying 4 Core x 10 sq. mm 1100 volt grade Copper RM. 450 13500
conductor XLPE insulated steel armoured cable ISI Marked with bare 10
30
SWG twin G.I earth wire. [Incoming for Power DB and UPS and LDB
TPN DBs]
0
10(i) Wiring for AC units with 2 x 4 sq. mm (+) 1 x 4 sq.mm wires of 1100 volt RM 280 33600
grade FRLS/ZHFR(HFFR) PVC insulated copper conductor, multy
120
strand in surface/ recessedby using 20 mm dia heavy duty FRLS PVC
conduit and conduit accessaries as required
10(j) Providing wiring with 3x2.5 Sq.mm 1100 volt grade ZHFR RM 200 12000
(HFFR)/FRLS copper conductor stranded wires for cassette AC units in
60
conduits in surface / recessed manner and connections at either end
and earthing
0
11.0 Point Wiring : 0
11(a) Providing point wiring with 3x1.5 Sq.mm 1100 volt grade ZHFR Points 700 42000
(HFFR)/FRLS copper conductor stranded wires for light point/ fan point/
exhaust fan point/ ordinary light points in surface / recessed suitable size 60
heavy duty FRLS PVC conduit and accessaries with modular switch,
modular plate suitable GI box etc. and other accessories if required.
0
0
11(b) Wiring --do- as per Item No 11.a) above but for group controlled light points Points 700 3500
5
of 6 points in one group.
0
0
11(d) do as above as per Item No. 11. a) but for providing wiring for 6 A power Points 750 18750
plug point away from switch board with modulat type 6 A switch and 6 A 25
3 pin socket etc
Point wiring for Wall mounting fans also 0
0
11(e) Supply and fixing 16 Amps modular type switch and 16/ 6 Amps combined Set 950 7600
socket with indicator in modular type surface box, plate and accessaries etc 8
for casseke AC units
0
11(g) Wiring --do-- as per item 11 (a) above but with 3 runs of 2.5 Sq mm 1100 Points 1200 14400
volt grade FRLS PVC insulated copper wires in heavy duty FRLS PVC
conduit for 16 A plug points including modular type 16 / 6A 6 pin 12
Socket, 16 A switch and PVC surface type / Metallic recessed type
switch Board and connections etc complete.
0
12.0 Light Fittings & Fans 0
12(a) SuppIy,Erection & commissioning of 2' x 2’ LED fitting( Philips make Each 3100 80600
or equivalent) by means of G I chain from ceiling to light fitting to be
26
recessed in the cutouts made in the false ceiling. Wiring to be taken
through flexible PVC conduit including connections & earthing.
0
0
12(c) Supply, Erection & commissioning of 18W Round penal light fittings ( Each 1500 51000
34
Philips make or equivalent) including connections.
0
12(d) Supply and erection of 300 mm heavy duty Exhaust fan by making Nos 3500 7000
suitable provision in ventilators / walls for fixing the same as required at
2
site.([EB SC room, Electrical panel room, AC Control panel
room,Records & Toilet locations]
0
12(e) Supply and erection of 5 star rated 400 mm sweep wall mounting fan with Nos 3500 14000
metalic blades / body by making suitable fixing arrangements and
4
connections (Manager cabins & Office hall locations]

0
0
13.0 Earth Installation & connections 0
13(a) Supplying and preparing Earth Station as per latest version of IS: 3043 for No 15000 30000
Plate earthing. Item includes 600 x 600 x 3 mm size copper plate,
earth electrode, excavation of earth in all types of soil upto the required
depth, placing the electrode, filling the pit with required qty of salt and
2
charcoal in alternate layers. GI pipe for taking 2 runs of No.8SWG copper
wires upto the surface and GI pipe for watering 2.7 mtrs long, brick masonry
chamber, RCC slab cover etc. complete and rate to include copper wire, GI
pipe etc.(Copper Plate Earth station.)
0
13(b) Do as above but 38 mm dia GI pipe earth station, but with 3.5M long GI pipe Nos 5000 10000
2
as earth electrode. [Electrical panel room, for panels]
0
13(c) Supplying and Laying 2 runs of No 8 SWG HD bare copper wire from Rmt 300 6000
panel board to earth stations in trench / on surface of wall or beam using 20
clamps.
0
13(d) Supplying and laying 15 mm dia GI pipe for protection of earth leads Rmt 400 8000
20
outside the Bldg on walls / underground.
0
13(e) Supply & fixing of copper earth strip of size 25 mm x 5 mm with Mtr 500 10000
20
necessary insulators.
0
0
14.0 Wiring for Computer points: 0
0
14(a) Wiring for circuit/ submain with 2 x 2.5 sq. mm (+) 1 x 2.5 sq. mm earth RM 150 90000
wire of FRLS/ZHFR(HFFR) PVC insulated copper conductor 1100
volt grade, single core cable in surface / recessed Heavy Duty PVC conduit 600
and accessaries including cutting the wall / floor and making good the
same in case of recessed conduit as required for Computers.
0
14(b) Supply & fixing of modular type Plug sockets for computer points consisting Set 600 45000
of 3nos 6A 3 pin sockets and 2 Nos 6A SP switches with indicator all of
modular type as a set including supply & fixing reccessed type switch boxes
75
suitable for modular range switches and sockets to be concealed in the
partitions / walls including suitable range Modular plates as directed.

(Rate is inclusive of Switches with indicator + Sockets + Box + 0


Plates.)
0
14(c Supply & fixing of two module metal box with two module plate with Set 750 11250
) 16A SP switche with indicator all of modular type as a set to be concealed
15
in the partitions / walls including suitable range
Modular 0
0
0
15.0 Telephone Wiring : 0
15(a) Supply and drawing 2 pair 0.5 mm size Copper conductor telephone RM 35 9450
wire through existing PVC conduit/ casing & caping 270
from tae block to the locations as directed
0
15(d) Supplying and fixing of 20 mm ISI marked FRLS heavy duty PVC conduit RM 40 20000
along with accessories in surface/recess including cutting the wall / floor
500
and making good the same in case of recessed conduit as required.

0
15(i) Supply anf fixing of 20 pair Krone Connector with MS box and Set 1200 3600
3
locking arrangement in concealed / surface manner.
0
16.0 Conventional Fire Alarm System: 0
16(a) Supplying, Installation, Testing & Commissioning of Set 1200 18000
conventional smoke detector with built in LED and mounting base 15
complete as required.
0
16(b) Supplying, installation, testing & commissioning of heat Set 1800 14400
detector with rate of rise cum fixed tempreature thermistor 8
COmDlete with base as reouired.
0
16(c) Supplying, installation, testing & commissioning response indicator on Set 1100 16500
surface/ recess MS box having two LEDs metallic cover complete with 15
all connections etc. as required.
0
16(d) Supplying, installation, testing & commissioning of manual call boxes Set 1200 6000
of MS construction in surface/recess with stainless steel chain & 5
hammer assembly complete with plass and push button etc. as required.
0
16(e) Supplying, installation, testing & commissioning of electronic hooter Set 1200 6000
5
and connections at either end complete
0
17.0 Supplying, installation, testing and commissioning of 4 zone Set 7000 7000
conventional fire alarm panel with touch keypad to program panel ,
1
stand by battery back up 24 V DC power supply with built in chaarger,
epoxy powder coated finish, 1000 event storage etc
0
18.0 Supplying & laying of 2 core 1.5 sqmm fire alarm armoured cable, RM 100 10000
600/1000V rated with annealed copper conductor having XLPE
100
insulation, steel wire armouring & FRLS outer sheath complete as reauired.

27.0 Removing the existing various connections from the existing old floor LS 10000 10000
1
panles and connecting to the new floor panles etc complete
27a Supplying and fixing 63A SFU in suitable size MS box in the rising No 1500 21000
14
main area to control supply to floor lighting / power DBs
ELECTRICAL INSTALLATION TOTAL 715550