The document provides technical specifications for the SITOP PSU100L/1AC/24VDC/20A power supply, detailing its input and output characteristics, efficiency, protection features, and safety certifications. It supports a wide input voltage range of 100-240 V AC and outputs a stabilized 24 V DC at 20 A, with various adjustable settings and protections against overvoltage and short circuits. Additional information includes installation dimensions, environmental conditions, and cybersecurity recommendations for safe operation.

Uploaded by

Mauricio Campos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views4 pages

6EP13361LB00 Datasheet en

The document provides technical specifications for the SITOP PSU100L/1AC/24VDC/20A power supply, detailing its input and output characteristics, efficiency, protection features, and safety certifications. It supports a wide input voltage range of 100-240 V AC and outputs a stabilized 24 V DC at 20 A, with various adjustable settings and protections against overvoltage and short circuits. Additional information includes installation dimensions, environmental conditions, and cybersecurity recommendations for safe operation.

Uploaded by

Mauricio Campos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Data sheet 6EP1336-1LB00

SITOP PSU100L/1AC/24VDC/20A

SITOP PSU100L 24 V/20 A Stabilized power supply input: 100-240 V AC output:


24 V DC/20 A

input
type of the power supply network 1-phase AC or DC
supply voltage at AC
● minimum rated value 100 V
● maximum rated value 240 V
● initial value 85 V
● full-scale value 264 V
supply voltage at DC 100 ... 240 V
input voltage at DC 88 ... 370 V
wide range input Yes
buffering time for rated value of the output current in the event of 20 ms
power failure minimum
operating condition of the mains buffering at Vin = 93/187 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 5.55 A
● at rated input voltage 230 V 2.35 A
current limitation of inrush current at 25 °C maximum 45 A
duration of inrush current limiting at 25 °C
● typical 15 ms
I2t value maximum 3.3 A²·s
fuse protection type T 10 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: from 10 A characteristic C
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer


adjustable output voltage 22.8 ... 26.4 V
relative overall tolerance of the voltage 3%
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 1%
residual ripple
● maximum 150 mV
● typical 50 mV
voltage peak
● maximum 240 mV

6EP13361LB00 Subject to change without notice


3/19/2025
Page 1/4 © Copyright Siemens
● typical 100 mV
display version for normal operation Green LED for 24 V OK
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 20 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; +45 ... +70 °C: Derating 2.5%/K

supplied active power typical 480 W


bridging of equipment Yes
number of parallel-switched equipment resources for increasing 2
the power
efficiency
efficiency in percent 92 %
power loss [W]
● at rated output voltage for rated value of the output 45 W
current typical
closed-loop control
relative control precision of the output voltage with rapid 0.5 %
fluctuation of the input voltage by +/- 15% typical
relative control precision of the output voltage at load step of 3%
resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical 0.7 ms
● load step 90 to 10% typical 6 ms
protection and monitoring
design of the overvoltage protection < 33 V
property of the output short-circuit proof Yes
design of short-circuit protection Constant current characteristic
● typical 24 A
enduring short circuit current RMS value
● typical 24 A
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.8 mA
protection class IP IP20
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● EAC approval Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41184349
● CB-certificate Yes
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No

6EP13361LB00 Subject to change without notice


3/19/2025
Page 2/4 © Copyright Siemens
● cCSAus, Class 1, Division 2 No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval No
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) No
● French marine classification society (BV) No
● Det Norske Veritas (DNV) No
● Lloyds Register of Shipping (LRS) No
ambient conditions
ambient temperature
● during operation -25 ... +70; with natural convection
● during transport -40 ... +85
● during storage -40 ... +85
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection screw terminal
● at input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.5 ... 2.5 mm²
● for auxiliary contacts -
mechanical data
width × height × depth of the enclosure 110 × 125 × 125 mm
installation width × mounting height 110 mm × 225 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
● DIN-rail mounting Yes
● S7 rail mounting No
● wall mounting No
housing can be lined up Yes
net weight 1.8 kg
further information internet links
internet link
● to website: Industry Mall [Link]
● to web page: selection aid TIA Selection Tool [Link]
● to web page: power supplies [Link]
● to website: CAx-Download-Manager [Link]
● to website: Industry Online Support [Link]
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
[Link]/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
[Link] (V4.7)

6EP13361LB00 Subject to change without notice


3/19/2025
Page 3/4 © Copyright Siemens
Classifications
Version Classification

eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04

Approvals Certificates
General Product Approval

Manufacturer Declara- Declaration of Con-


tion formity

last modified: 11/25/2024

6EP13361LB00 Subject to change without notice


3/19/2025
Page 4/4 © Copyright Siemens