E-FDC-DD
Fire damper
Fire protection
Version 1.0.0
Issue Date: 19.12.2023.
1. Damper frame 2
2. Galvanized steel casing 1
3. Actuator
4. Cold smoke seal 2
PRODUCT OVERVIEW
1
DIMENSIONS
INSTALLATIONS
ACTUATORS
ACCESSORIES
4
MAINTENANCE AND OPERATION
PRODUCT OVERVIEW
* The images shown are for illustration purposes only and may not be an exact representation of the product.
PRODUCT OVERVIEW
Fire dampers FDDD are used for prevention of fire spread
trough the ventilation ducts and between the fire sections. Fire
damper E-FDC-DD consists of galvanized sheet metal casing, Fire dampers are equipped with Belimo electric actuators
calcium silicate damper blade, high temperature resistant (24 V or 230 V versions). Actuator’s spring closes the
installation frame made from calcium silicate and electric damper blade when it’s thermal fuse senses the ambient
actuator. temperature has reached 72°C. Closing and reopening of
damper blade can also be done remotely via control signal.
Fire damper casing is made out of galvanized steel sheet.
Variants produced from stainless steel and powder coated Declared blade airtightness - class 3 and casing airtightness
steel are also available. Calcium silicate blade is equipped with - class C are tested according to EN 1751.
brass bearings and seals. Brass bearings are pressed into the
casing. Calcium silicate blade is equipped with the seal made
out of EPDM rubber.
2
PRODUCT OVERVIEW
DIMENSIONS
INSTALLATIONS
ACTUATORS
ACCESSORIES
PRODUCT OVERVIEW
PRODUCT OVERVIEW
FIRE RESISTANCE
CLASSIFICATION E - Integrity
I - Insulation
E-FDC-DD fire resistance is tested according to EN 1366-2
90 - Classification time in minutes
“Fire resistance tests for service installations- Part 2: Fire S - Smoke leakage
dampers”. Classification of the fire dampers is defined ve - Damper installed in vertical compartment
according to EN 13501-3 Fire classification of construction ho - Damper installed in horizontal compartment
products and building elements. i↔o - Fire performance criteria are met on both sides
3
1 6
7 16
PRODUCT OVERVIEW
8
DIMENSIONS
9
INSTALLATIONS
2 10
ACTUATORS
3 11
ACCESSORIES
4
E-FDC-DD-d100-M230-S 12 13
MAINTENANCE AND OPERATION
5
14
15
4
PRODUCT OVERVIEW
DIMENSIONS
E-FDC-DD INSTALLATIONS
ACTUATORS
Dimensional range
Diameter Cross section Net area
ACCESSORIES
Model
Ød [mm] [dm²] [dm²]
MAINTENANCE AND OPERATION
E-FDC-DD D100 98 0,74 0,50
E-FDC-DD D125 123 1,17 0,87
E-FDC-DD D160 158 1,93 1,55
E-FDC-DD D200 198 3,05 2,56
E-FDC-DD D250 248 4,79 4,18
E-FDC-DD D315 313 7,64 6,87
DIMENSIONS
50
50
S
S 60
60
X Y
d D+
+ 120
120
Weights Length of damper blade
(with Belimo actuator 1,1kg) outside of casing
Model Weight [kg] Model S X side Y side
E-FDC-DD D100 3,022 68 / /
E-FDC-DD D125 3,389 E-FDC-DD D125 78 / /
Φd
ØD
S
S
90
90
(d +
( D+120)
120) ++6060 170
170
255
255
5
PRODUCT OVERVIEW
DIMENSIONS
MODELS INSTALLATIONS
Casings ACTUATORS
E-FDC-DD ACCESSORIES
Cylindrical fire damper with 25 mm damper blade
and fire classification up to EI 90S. Sizes range MAINTENANCE AND OPERATION
from d100 till d315.
PRODUCT OVERVIEW
6
PRODUCT OVERVIEW
DIMENSIONS
INSTALLATION INSTALLATIONS
INSTALLATION
7
Range
Aerated concrete
( ≥ 550kg/m³)
Rigid wall ≥ 100 mm / EI 60 (ve i↔o)S 300Pa
Reinforced concrete
(≥ 2200kg/m³)
type A (EN520),
Flexible wall Plasterboard wall, type F (EN520),
mineral wool up to
60 kg/m³ Plasterboard wall, type A (EN520),
more than 100 mm thick
A: Plasterboard
type F (EN520), Floor/ Ceiling installation, Aerated
EI 90 (ve i↔o)S concrete ( ≥ 550kg/m³) Reinforced
mineral wool up to
60 kg/m³ concrete (≥ 2200kg/m³) more than
Installation with 100 mm thick
≥ 100 mm 300Pa
profile inserts
B: Plasterboard
type A (EN520),
EI 60 (ve i↔o)S FIRE DAMPER - E-FDC-DD
mineral wool up to
60 kg/m³
Aerated concrete
( ≥ 550kg/m³) Remote from floor/ceiling E-FDC-DD installation
Floor/ Ceiling ≥ 100 mm EI 60 (ho o↔i)S 300Pa
Reinforced concrete on the insulated duct
(≥ 2200kg/m³)
8
PRODUCT OVERVIEW
DIMENSIONS
installation ACTUATORS
INSTALLATION
6 5 4 3 2 1
1. Create a wall opening.
Edition Sheet
FDC-DD D315 1/1
6 5 4 3 2 1
9
PRODUCT OVERVIEW
DIMENSIONS
INSTALLATION
Edition Sheet
FDC-DD D315 1/1
6 5 4 3 2 1
10
Flexible wall
installation PRODUCT OVERVIEW
The wall is composed of 2x2 plasterboard
boards, DIMENSIONS
12,5 mm thick, installed on a steel frame
construction. To fulfill the classification it is NOT INSTALLATIONS
mandatory to use the mineral wool inside the wall
(mineral wool with density up to 60 kg/m³ can be ACTUATORS
used).The minimum thickness of the wall is 100
mm. ACCESSORIES
With subframe for flexibile wall
MAINTENANCE AND OPERATION
The wall is made out of type F or type A (EN520)
plasterboard - EI 60 (ve i↔o)S
With profile inserts
The wall is made out of
type F (EN520) -EI 90 (ve i↔o)S
or type A (EN520) - EI 60 (ve i↔o)S
plasterboard.
INSTALLATION
6 5 4 3 2 1
Create subframe for instalation in flexibile wall!
(page 13.)
D D
Marko Kokolic
Checked by Approved by Date Date
07.06.22
A
7. Schweißen Sie die entsprechenden Stifte für den 1-2 3-4 5 6-7
Lüftungskanal durch die eingebrachte Wolle (6 Stück
pro Umfang) gemäß den nachstehenden Anweisungen.
Die Stifte sollten 90 mm von der Kante des Wollstücks
entfernt sein.
12
PRODUCT OVERVIEW
DIMENSIONS
UW50
UW50 rail INSTALLATIONS
ACTUATORS
ACCESSORIES
d+15
(max)
MAINTENANCE AND OPERATION
CW50
CW50
rail
INSTALLATION
profiles inserts
d+15 (max)
UW50 rail
CW50
rail UW50 rail
13
PRODUKTÜBERSICHT
ABMESSUNGEN
Minimale Installa- INSTALLATION
tionsabstände ANTRIEBE
KOMMUNIKATIONS MODULE
75
ZUBEHÖR
ERSETZUNGEN
200
75 200
14
PRODUCT OVERVIEW
ELECTRIC DIMENSIONS
ACTUATOR INSTALLATIONS
E-M24-S-ST ACCESSORIES
Damper is delivered in closed position. When MAINTENANCE AND OPERATION
electric actuator is connected to the power supply,
damper blade will open. When the damper reaches
the end position (damper open), the electro
motor will stop. Closing fire damper takes place
automatically when a power failure occurs. Thermal
tripping device that comes with fire damper causes
power circuit break at a temperature of 72 °C. If
checking is needed for proper functioning of fire
damper, pushing the switch on the thermal tripping
device will close damper.
ACTUATORS
15
F
PRODUCT OVERVIEW
D DIMENSIONS
ACCESSORIES INSTALLATIONS
ACTUATORS
C Flexible duct connections - Flexible duct connec-
tors are used in HVAC systems for isolation from ACCESSORIES
structure-borne noise, expansion compensation
and fire damper connections (total length 150mm, MAINTENANCE AND OPERATION
flexible 60mm).
ACCESSORIES
16
PRODUCT OVERVIEW
DIMENSIONS
INSTALLATIONS
ACTUATORS
ACCESSORIES
MAINTENANCE
TRANSPORT MAINTENANCE AND It is not permitted to alter the dampers in any way nor
perform any changes to their structure (except for the
FUNCTIONS
After arrival, check the fire damper for transport damage
and shortcomings. In case of any damage or shortcom- OPERATION service procedures described in this manual) without the
manufacturer’s consent. Provide at least one annual check
• Release mechanism:
Damper blade can be closed and opened manually
ings, immediately contact your supplier. of the damper. The functional test must be carried out in • Electric actuator:
Fire dampers are designed with fully enclosed drive compliance with the basic maintenance principles of the
mechanism outside of the duct and as such do not require Signal testing - the damper blade must close/open
European norms EN 13306, EN 15423 and EN15650.
STORAGE cleaning and regular maintenance.
However, activation mechanism should be inspected for
If the damper is not installed immediately:
proper operation on regular basis. COMMISSIONING
• Remove any wrapping. • Provide at least one annual check of the damper • Carefully unpack E-FDC-DD fire damper - be careful
• Protect fire damper from dust and contamina- • After each intervention, provide a systematic cleaning of sharp edges and do not use excessive force for
tion. of dust unpacking
• Do not expose the fire damper to the effects of
weather - store fire damper in dry place.
• Check if the electrical terminals are tightened • Inspect the fire damper - check the fire damper for
• Cleaning instruction: clean with a sponge, with water or damage
• Do not store the unit below -20 °C or above 50 a mild detergent
°C. • Installation of the fire damper - according to the
• Disinfection instruction: spray disinfectant (desinfectant installation instructions (page 7.)
may contain alcohol which is flammable, take precau-
Please properly dispose of packaging material. • Before commissioning: check the fire damper
tion to avoid ignition)
functions.
17
FIRE DAMPER - E-FDC-DD