Sensor Datasheet 22D..C..
-11
Duct Sensor CO₂
For CO₂ measurement in duct applications.
Dual channel CO₂ technology.
NEMA 4X / IP65 rated enclosure.
Type Overview
Output signal
Output signal Output signal Output signal Output signal
Type passive
active CO₂ active VOC active temperature active CO₂/VOC
temperature
22DC-11 DC 0...5 V, - - - -
DC 0...10 V
22DC-110L DC 0...5 V, - - NTC10k (10k2) -
DC 0...10 V
22DCK-11 DC 0...5 V, DC 0...5 V, DC 0...5 V, - DC 0...5 V,
DC 0...10 V DC 0...10 V DC 0...10 V DC 0...10 V
22DCM-11 DC 0...5 V, DC 0...5 V, DC 0...5 V, - -
DC 0...10 V DC 0...10 V DC 0...10 V
22DCV-11 DC 0...5 V, DC 0...5 V, - - -
DC 0...10 V DC 0...10 V
22DTC-11 DC 0...5 V, - DC 0...5 V, - -
DC 0...10 V DC 0...10 V
Technical Data
Electrical data Power Supply DC 15...24 V, ±10%, 1.5 W
Power Supply AC 24 V, ±10%, 2.9 VA
Electrical connection Removable spring loaded terminal block max.
2.5 mm²
Cable entry cable gland PG11 Ø6...10 mm, with strain
relief Ø6...8 mm
Functional data Sensor Technology NDIR (non dispersive infrared) with stainless
steel wire mesh filter
Output signal active note Output DC 0...5/10 V with Jumper adjustable
Voltage output: min. 10 kΩ load
Media Air
Measuring data Measured values CO₂
VOC
Mix CO₂/VOC
Temperature
Measuring range CO₂ 0...2000 ppm
Measuring range humidity 0...100% rH
Accuracy CO₂ ±75 ppm; >750 ppm: ±10% of measuring
value
Accuracy humidity ±2% between 10...90% rH @ 21 °C
Accuracy temperature ±1% of measuring range @ 21 °C
NTC10k (10k2): ±0.22 °C @ 25 °C
Operating condition air flow min. 0.3 m/s
max. 10 m/s
www.belimo.com 22D..C..-11 • en-gb • 2017-03-31 • Subject to change 1/4
Sensor Datasheet 22D..C..-11
Materials Cable gland PA6, black
Housing Cover: Lexan, Belimo orange NCS S0580-
Y6OR
Bottom: Lexan, Belimo orange NCS S0580-
Y6OR
Seal: 0467 NBR70, black
Probe material PA6, black
Safety data Ambient humidity 85% r.h., non-condensing
Ambient Temperature 0...50 °C [32...122 °F]
Operating condition air flow min. 0.3 m/s
max. 10 m/s
Protection class IEC/EN III Safety Extra-Low Voltage (SELV)
Protection class UL UL Class 2 Supply
EU Conformity CE Marking
Certification IEC/EN IEC/EN 60730-1
Certification UL pending
Degree of protection IEC/EN IP65
Degree of protection NEMA/UL NEMA 4X
Quality Standard ISO 9001
Safety notes
The installation and assembly of electrical equipment should only be performed by
authorized personnel.
The product should only be used for the intended application. Unauthorised modifications
are prohibited! The product must not be used in relation with any equipment that in case of
a failure may threaten, directly or indirectly, human health or life or result in danger to
human beings, animals or assets. Ensure all power is disconnected before installing. Do not
connect to live/operating equipment.
Please comply with
• Local laws, health & safety regulations, technical standards and regulations
• Condition of the device at the time of installation, to ensure safe installation
• This data sheet and installation manual
Remarks
Information Self-Calibration Feature CO₂ All gas sensors are subject to drift caused by components, resulting in regular re-calibration
or replacement units. However the dual channel technology integrates automatic self-
calibration technology vs common used ABC-Logic sensors. Dual channel self-calibration
technology is ideally suited for applications operating 24/7 hours such as hosiptals or other
commerical applications. Manual calibration is not required.
Accessories
Scope of delivery Mounting flange
www.belimo.com 22D..C..-11 • en-gb • 2017-03-31 • Subject to change 2/4
Sensor Datasheet 22D..C..-11
Wiring diagram
Wiring diagram for 22DC-..1, 22DTC-..1
① Status LED
www.belimo.com 22D..C..-11 • en-gb • 2017-03-31 • Subject to change 3/4
Sensor Datasheet 22D..C..-11
Dimensions
www.belimo.com 22D..C..-11 • en-gb • 2017-03-31 • Subject to change 4/4